Bradford-White Corp EF Series warranty Direct Vent Maximum Vent Length, Power Vent Installation

Page 24

Maximum Vent Length :

Direct Vent Maximum Vent Length

Model

Max Vent Length (feet)

Max Vent Length (feet)

Number

3" PVC, CPVC, or ABS

4" PVC, CPVC, or ABS

EF60T125, EF100T150

120

170

EF60T150, EF100T199

100

150

EF60T199, EF100T250

80

130

EF100T300

60

120

Table 3

Determining required vent length:

1.Determine the total length of straight vent pipe (in feet) required for both the intake and the exhaust.

2.Add 5 feet of venting for every 90° elbow.

3.Add 2 ½ feet of venting for every 45° elbow.

4.Total vent length can not exceed “Max Ve nt Length” in Table 3.

5.Air intake can not exceed exhaust by more than 30 feet in any venting situation.

NOTICE

Do not include the 3” exhaust elbow or vent terminals in determining maximum vent length.

POWER VENT INSTALLATION

Power venting is where the indoor air is used and the exhaust is vented to the outside. Venting may be run horizontally through an outside wall or vertically through a roof through using either 3 inch (7.6 cm) or 4 inch (10.2 cm) diameter PVC, ABS or CPVC. This water heater is supplied with a screened intake and exhaust 90° elbow referred to as the exhaust vent terminal and the air intake terminal.

Power Vent Terminal Location

Refer to the “Direct Vent Terminal Location” section previously mention to determine the proper exhaust vent location. Plan the vent system layout so that proper clearances are maintained from plumbing and wiring.

Vent pipes serving power vented appliances are classified by building codes as “vent connectors”. Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF WATER HEATER and CLEARANCES, and with National Fuel Gas Code and local codes.

NOTICE

This unit can be vented using only PVC (Class 160, ASTM D-2241 Schedule 40, ASTM D-1785; or Cellular Core Schedule 40 DWV, ASTM F-891), Schedule 40 CPVC (ASTM F-411), or ABS (ASTM D-2661) pipe. The fittings, other than the TERMINATIONS should be equivalent to PVC - DWV fittings meeting ASTM F-2665. (Use CPVC fittings, ASTM F-438 for CPVC pipe and ABS fittings, ASTM D-266/3311 for ABS pipe.) If CPVC or ABS pipe and fittings are used, then the proper cement must be used for all joints, including joining the pipe to the Termination (PVC material). PVC materials should use ASTM –D2564 grade cement; CPVC materials should use ASTM F-493 grade cement; and ABS materials should use ASTM D-2235 grade cement.

For water heaters in locations with high ambient temperatures (above 100°F) and/or insufficient dilution air, it is recommended that CPVC or ABS pipe and fittings (MUST USE SUPPLIED VENT TERMINAL) be used.

24

Image 24
Contents With Troubleshooting Guide What to do if YOU Smell GASTable of Contents Page If YOU Smell GAS Do not Operate the Appliance Until the Leakage is CorrectedSpecifications SectionFeatures Section III General InformationTemperature and Pressure Relief Valve Dishwashing Machine Requirements Condensate Elbow With LoopSection IV Installation Instructions Unpacking Minimum Clearance To CombustibleLocation Remove CrateAIR Requ Rements Mechanical Exhausting of Room AIR Unconfined SpaceConfined Space Chemical Vapor CorrosionTypical Installation Illustration Typical Front Inlet ConnectionTypical Two Water Heater Connection Section V Water Connections Instructions for ConnectionsApproximate TIME/TEMPERATURE Relationships in Scalds ScaldingAlternate Space Heating Water Connections Alternate Space Heating ConnectionsTypical Plumbing Schematic for Zoned Heating Section VI VentingDirect Vent Installation VentingExceptions for Installations Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Power Vent Installation Direct Vent Maximum Vent LengthTypical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Coaxial Venting Installation ProcedureDimensional Layout of Concentric Vent Kit Concentric Vent Roof Top Attachment Vent Pipe Preparation Initial PreparationSection VII GAS Connections Selection of MaterialsGAS Meter Size Natural Gases only GAS Pressure RegulationWiring Diagram and Schematic Section Viii Electrical ConnectionsSection IX Operating Instructions General InstructionsTo Fill the Water Heater Sequence of OperationTemperature Adjustm NT Lighting InstructionsBurner Flame Check Sight Glass LocationSection X Maintenance Maintenance ScheduleGeneral Flushing Water Heater Draining Water HeaterFilling Water Heater Sediment and Lime Scale RemovalAnode Inspection and Replacement Drain Valve and Tank Access PanelRelief Valve Vent and AIR Intake System Combustion System InspectionSection XI Troubleshooting Guide ReferenceIs there continuity across the Hot Surface Ignitor? If Section XI Parts List EF Series Water HeaterCombustion Surround Assy CC Ignition Control Assy