Bradford-White Corp EFR-1-60T1206EN, EFR160T120 warranty

Page 23

The vent system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the National Fuel Gas Code, ANSI Z223.1.73.4e and 7.8a, b as follows:

1.Do not terminate near soffit vents or crawl space or other area where condensate or vapor could create a nuisance or hazard or cause property damage.

2.Do not terminate the exhaust vent terminal where condensate or vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.

3.Do not terminate the exhaust vent terminal over public area or walkways where condensate or vapor can cause nuisance or hazard.

4.The vent shall terminate a minimum of 12 inches (30.5 cm) above expected snowfall level to prevent blockage of the vent termination.

5.The manufacturer requires the centerline distances between the air intake and exhaust vent terminals to be a minimum of 36 inches (91.4 cm) apart and the exhaust terminal must extend 6 inches (15.2 cm) past the air intake terminal.

Vent pipes serving power vented appliances are classified by building codes as “vent connectors”. Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF WATER HEATER and CLEARANCES, and with National Fuel Gas Code and local codes.

NOTICE

This unit can be vented using only PVC (Class 160, ASTM D-2241 Schedule 40, ASTM D-1785; or Cellular Core Schedule 40 DWV, ASTM F-891), Schedule 40 CPVC (ASTM F-411), or ABS (ASTM D-2661) pipe. The fittings, other than the TERMINATIONS should be equivalent to PVC- DWV fittings meeting ASTM F-2665. (Use CPVC fittings, ASTM F-438 for CPVC pipe and ABS fittings, ASTM D-266/3311 for ABS pipe.) If CPVC or ABS pipe and fittings are used, then the proper cement must be used for all joints, including joining the pipe to the Termination (PVC material). PVC materials should use ASTM –D2564 grade cement; CPVC materials should use ASTM F-493 grade cement; and ABS materials should use ASTM D-2235 grade cement.

For water heaters in locations with high ambient temperatures (above 100°F (38ºC)) and/or insufficient dilution air, it is recommended that CPVC or ABS pipe and fittings (MUST USE SUPPLIED VENT TERMINAL) be used.

Horizontal Installation:

In a horizontal application, it is important that condensate not be allowed to buildup in the exhaust vent pipe. To prevent this from happening, the pipe should be installed with a slight upward slope so the condensate will run back toward the water heater. The vent system must be supported every 5 feet (1.5 m) of vertical run and every 3 feet (.9 m) of horizontal run of vent pipe length.

CAUTION

Failure to properly support the vent piping with hangers and clamps may result in damage to the water heater or venting system.

Stress levels in the pipe and fittings can be significantly increased by improper installation. If rigid pipe clamps are used to hold the pipe in place, or if the pipe cannot move freely through a wall penetration, the pipe may be directly stressed, or high thermal stresses may be formed when the pipe heats up and expands. Install accordingly to minimize such stresses.

Follow the following procedure to vent through the wall:

1.Cut two 2 ½ inch (6.4 cm) diameter holes for 2 inch (5.1 cm) diameter pipe, in the wall with the centerline hole distances at least 36 inches (91.4 cm) apart in the location where the exhaust vent and air intake terminals will exit the outside wall if vented on the same wall. If venting with 3 inch (7.6 cm) pipe or 4 inch (10.2 cm) diameter pipe, use a bell reducer to reduce to 2 inch (5.1 cm) pipe before exiting the wall to use the supplied 2 inch (5.1 cm) diameter vent terminals.

23

Image 23
Contents What to do if YOU Smell GAS With Troubleshooting GuideTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected Dimensions Inches Section II SpecificationsSection III General Information FeaturesTemperature and Pressure Relief Valve Condensate Elbow With Trap Do not Operate the Appliance Until the Leakage is Corrected Section IV Installation InstructionsUnpacking Minimum Clearance To Combustible Material AIR Requirements LocationRemove Crate Confined Space Typical Installation IllustrationMechanical Exhausting of Room AIR Unconfined SpaceTypical Front Inlet Connection Typical Two Water Heater Connection Scalding Section V Water ConnectionsInstructions for Connections Alternate Space Heating Water Connections Approximate TIME/TEMPERATURE Relationships in ScaldsSection VI Venting Page Venting Direct Vent InstallationCanadian US Installations2 Installations1 Direct Vent Terminal Clearances Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Cm PVC, Cpvc Power Vent InstallationPage Typical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Multiple INTAKE/EXHAUST Terminal Separation Distances Concentric Vent Terminal Installation Procedure Vertical InstallationRain Cap to Small Vent Pipe Assembly Vent Pipe Preparation Horizontal InstallationSelection of Materials Section VII GAS ConnectionsInitial Preparation GAS Pressure Regulation GAS Meter Size Natural Gases onlySection Viii Electrical Connections Wiring Diagram and SchematicSequence of Operation Section IX Operating InstructionsGeneral Instructions To Fill the Water HeaterLighting and SHUT-DOWN Instructions For Your Safety Read Before LightingTemperature Adjustment Read Operational Status IndicatorOr Service Needed Reads Idle or HeatingSetpoint flashes for 10 seconds Press SET Button for setting to take effect immediatelyTo Decrease Setpoint Temperature Changes to C Press selectPress select Step Symbol F/C Stops FlashingPress Set Setpoint shown in FBurner Flame Check Section X MaintenanceGeneral Sight Glass Location Maintenance ScheduleSediment and Lime Scale Removal Flushing Water HeaterDraining Water Heater Filling Water HeaterRelief Valve Anode Inspection and ReplacementDrain Valve and Tank Access Panel Combustion System Inspection Vent and AIR Intake SystemSection XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Max Setpoint value Water Heater Display Water Heater DisplayHeating No current error codes Max Setpoint Flashes Max Setpoint stops flashing Max Setpoint continues to flashTo Display Flame Sense Current of the Pilot Flame Sensor Display of Water TemperatureSetpoint Flashes To Display and Change Temperature SetpointSetpoint Stops Flashing Flashes Changes to C F/C FlashesSymbol Stops Flashing Press for 3 seconds to reset control in service mode How to reset the control from Lockout ConditionsResetting Error Codes in Soft Lockout Condition Resetting Error Codes in Hard Lockout ConditionNo Current Error Code Error Code HistoryTo view previous error codes No Error Code Shown for Code Index Error Code IndexStored Error Code For Code Index #9 ExitingSELECTServiceSETMode Page Procedure for Checking Thermostat Sensors EF Series Water Heater Section XII Parts ListCombustion Surround Assembly Ignition Control Assembly Combustion Assembly pictured previous
Related manuals
Manual 76 pages 32.48 Kb

EFR-1-60T1206EN, EFR160T120 specifications

Bradford-White Corporation is a leading manufacturer of residential and commercial water heating solutions, and one of its standout products is the EFR160T120, also known as the EFR-1-60T1206EN. This innovative electric water heater is designed for those seeking reliable performance, energy efficiency, and long-lasting durability.

The EFR160T120 has an impressive capacity of 60 gallons, making it suitable for households with higher hot water demands. This model features a compact design, allowing it to fit into various installation spaces, such as utility rooms or small basements, without compromising on performance. Its vertical configuration and dimensions ensure that it occupies minimal floor space while delivering optimal hot water supply.

One of the most notable features of the EFR160T120 is its high-efficiency electric heating elements. This water heater is equipped with multiple heating elements that provide quick recovery rates, ensuring that hot water is readily available when it is needed most. The intelligent design employs a top-mounted thermostat that allows for accurate temperature control, promoting consistent hot water delivery for showers, baths, and household chores.

In terms of technology, the EFR160T120 incorporates advanced insulation technology that minimizes heat loss, enhancing energy efficiency. This feature not only contributes to reduced energy bills but also lowers carbon emissions, aligning with modern eco-conscious standards. The unit features an integrated temperature and pressure relief valve, which enhances safety by preventing excessive pressure build-up and protecting the tank from potential damage.

Durability is another strong suit of the EFR160T120, as it is constructed from high-quality materials. The tank is coated with a glass lining that protects against corrosion, extending the overall life of the unit. The heater is also backed by Bradford-White's reputation for quality craftsmanship, providing peace of mind for consumers.

Furthermore, the EFR160T120 is designed with user convenience in mind. Maintenance is straightforward, and replacement parts are readily available, which facilitates easy repairs and servicing. Overall, the Bradford-White EFR160T120 water heater stands out as a reliable and efficient choice for homes that require ample hot water supply without sacrificing space or energy efficiency.