Bradford-White Corp EFR160T120, EFR-1-60T1206EN warranty Cm PVC, Cpvc, Power Vent Installation

Page 26

Maximum Vent Length:

Direct Vent Maximum Vent Length (Combined Maximum Length for Intake and Exhaust)

 

Max Vent Length in

Max Vent Length in

Max Vent Length in

Model

feet (meters) for 2 inch

feet (meters) for 3 inch

feet (meters) for 4 inch

Number

(5.1 cm) PVC, CPVC,

(7.6 cm) PVC, CPVC,

(10.2 cm) PVC, CPVC,

 

or ABS

or ABS

or ABS

EFR60T120

60 (18)

120 (36)

170 (51)

Table 3

Note: The venting distance shown in the chart above is the combined maximum distance for the intake and exhaust pipe and elbows. The intake and exhaust vent terminals may be in different locations (i.e., different walls or one wall, one roof) provided the intake equivalent venting distance does not exceed the exhaust by more than 30 feet (9 m).

Determining required vent length:

1.Determine the total length of straight vent pipe (in feet) required for both the intake and the exhaust.

2.Add 5 feet (1.5 m) of venting for every 90° elbow.

3.Add 2 ½ feet (.7 m) of venting for every 45° elbow.

4.Total vent length cannot exceed “Max Vent Length” in Table 3.

5.Air intake cannot exceed exhaust by more than 30 feet (9 m) in any venting situation.

Example of Total Direct Vent Length for EF100T199:

A 3 inch (7.6 cm) venting system has a total of six 90-degree elbows and a total straight pipe length of 65 feet (19.5

m)(includes both intake and exhaust pipe).

Equivalent vent length for elbows: 6 x 5 feet (1.5 m) = 30 feet (9 m).

Total equivalent vent distance = 65 feet (19.5 m) + 30 feet (9 m) = 95 feet (28.5 m) total equivalent vent length. This is below the maximum allowed distance of 100 feet (30 m) for this model using 3 inch (7.6 cm) vent.

NOTICE

Do not include the condensate elbow or vent terminals in determining maximum vent length.

POWER VENT INSTALLATION

Power venting is where the indoor air is used and the exhaust is vented to the outside. Venting may be run horizontally through an outside wall or vertically through a roof through using either 2 inch (5.1 cm), 3 inch (7.6 cm) or 4 inch (10.2 cm) diameter PVC, ABS or CPVC. This water heater is supplied with a 2 inch (5.1 cm) diameter screened intake and exhaust elbow, referred to as the air intake terminal and the exhaust vent terminal.

Power Vent Terminal Location:

Refer to the “Direct Vent Terminal Location” section previously mentioned to determine the proper exhaust vent location. Plan the vent system layout so that proper clearances are maintained from plumbing and wiring.

Vent pipes serving power vented appliances are classified by building codes as “vent connectors”. Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF WATER HEATER, and CLEARANCES, and with National Fuel Gas Code and local codes.

26

Image 26
Contents With Troubleshooting Guide What to do if YOU Smell GASTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected Section II Specifications Dimensions InchesFeatures Section III General InformationTemperature and Pressure Relief Valve Condensate Elbow With Trap Section IV Installation Instructions Do not Operate the Appliance Until the Leakage is CorrectedUnpacking Minimum Clearance To Combustible Material AIR Requirements LocationRemove Crate Unconfined Space Typical Installation IllustrationMechanical Exhausting of Room AIR Confined SpaceTypical Front Inlet Connection Typical Two Water Heater Connection Scalding Section V Water ConnectionsInstructions for Connections Approximate TIME/TEMPERATURE Relationships in Scalds Alternate Space Heating Water ConnectionsSection VI Venting Page Direct Vent Installation VentingCanadian US Installations2 Installations1 Direct Vent Terminal Clearances Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Power Vent Installation Cm PVC, CpvcPage Typical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Multiple INTAKE/EXHAUST Terminal Separation Distances Vertical Installation Concentric Vent Terminal Installation ProcedureRain Cap to Small Vent Pipe Assembly Horizontal Installation Vent Pipe PreparationSelection of Materials Section VII GAS ConnectionsInitial Preparation GAS Meter Size Natural Gases only GAS Pressure RegulationWiring Diagram and Schematic Section Viii Electrical ConnectionsTo Fill the Water Heater Section IX Operating InstructionsGeneral Instructions Sequence of OperationFor Your Safety Read Before Lighting Lighting and SHUT-DOWN InstructionsTemperature Adjustment Reads Idle or Heating Status IndicatorOr Service Needed Read OperationalPress SET Button for setting to take effect immediately Setpoint flashes for 10 secondsTo Decrease Setpoint Temperature Press select Changes to CSetpoint shown in F Symbol F/C Stops FlashingPress Set Press select StepBurner Flame Check Section X MaintenanceGeneral Maintenance Schedule Sight Glass LocationFilling Water Heater Flushing Water HeaterDraining Water Heater Sediment and Lime Scale RemovalRelief Valve Anode Inspection and ReplacementDrain Valve and Tank Access Panel Vent and AIR Intake System Combustion System InspectionSection XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Water Heater Display Max Setpoint value Water Heater DisplayHeating No current error codes Max Setpoint Flashes Max Setpoint continues to flash Max Setpoint stops flashingDisplay of Water Temperature To Display Flame Sense Current of the Pilot Flame SensorTo Display and Change Temperature Setpoint Setpoint FlashesSetpoint Stops Flashing Changes to C F/C Flashes FlashesSymbol Stops Flashing Resetting Error Codes in Hard Lockout Condition How to reset the control from Lockout ConditionsResetting Error Codes in Soft Lockout Condition Press for 3 seconds to reset control in service modeNo Current Error Code Error Code HistoryTo view previous error codes Error Code Index No Error Code Shown for Code IndexStored Error Code For Code Index #9 ExitingSELECTServiceSETMode Page Procedure for Checking Thermostat Sensors Section XII Parts List EF Series Water HeaterCombustion Surround Assembly Combustion Assembly pictured previous Ignition Control Assembly