Bradford-White Corp EFR160T120, EFR-1-60T1206EN Max Setpoint Next to Temperature Setpoint value

Page 52

ACCESSING SERVICE MODE ON THE WATER HEATER DISPLAY (FOR SERVICE PERSONNEL ONLY)

The display has a “Service Mode” for changing the maximum setpoint and accessing information in aiding servicing of the water heater. This procedure is for service and installation personnel only. To enter the Service Mode, follow the steps illustrated below:

WARNING

The following procedure is for service and installation personnel only. Resetting lockout conditions without correcting the malfunction can result in a hazardous condition.

Step 1: Press “Select” and “Temperature Up” buttons together and hold for 3 seconds until “Max Setpoint” is shown in the display.

°F Max

Setpoint

idle

Status Operational

SELECTSET

"Max Setpoint"

next to Temperature

%Setpoint value.

NOTICE

30 Seconds after the last button press, the display will automatically return to the “User Mode”. Simultaneously pressing the “Select” and “Temperature Up” buttons will switch the display immediately to the “User Mode”.

Step 2: Pressing “Select” button will change display to next mode

°F Water

Temp

idle

Status Operational

&SELECTSET

52

Image 52
Contents With Troubleshooting Guide What to do if YOU Smell GASTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected Section II Specifications Dimensions InchesFeatures Section III General InformationTemperature and Pressure Relief Valve Condensate Elbow With Trap Section IV Installation Instructions Do not Operate the Appliance Until the Leakage is CorrectedUnpacking Minimum Clearance To Combustible Material Remove Crate LocationAIR Requirements Typical Installation Illustration Mechanical Exhausting of Room AIRUnconfined Space Confined SpaceTypical Front Inlet Connection Typical Two Water Heater Connection Instructions for Connections Section V Water ConnectionsScalding Approximate TIME/TEMPERATURE Relationships in Scalds Alternate Space Heating Water ConnectionsSection VI Venting Page Direct Vent Installation VentingCanadian US Installations2 Installations1 Direct Vent Terminal Clearances Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Power Vent Installation Cm PVC, CpvcPage Typical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Multiple INTAKE/EXHAUST Terminal Separation Distances Vertical Installation Concentric Vent Terminal Installation ProcedureRain Cap to Small Vent Pipe Assembly Horizontal Installation Vent Pipe PreparationInitial Preparation Section VII GAS ConnectionsSelection of Materials GAS Meter Size Natural Gases only GAS Pressure RegulationWiring Diagram and Schematic Section Viii Electrical ConnectionsSection IX Operating Instructions General InstructionsTo Fill the Water Heater Sequence of OperationFor Your Safety Read Before Lighting Lighting and SHUT-DOWN InstructionsTemperature Adjustment Status Indicator Or Service NeededReads Idle or Heating Read OperationalPress SET Button for setting to take effect immediately Setpoint flashes for 10 secondsTo Decrease Setpoint Temperature Press select Changes to CSymbol F/C Stops Flashing Press SetSetpoint shown in F Press select StepGeneral Section X MaintenanceBurner Flame Check Maintenance Schedule Sight Glass LocationFlushing Water Heater Draining Water HeaterFilling Water Heater Sediment and Lime Scale Removal Drain Valve and Tank Access Panel Anode Inspection and Replacement Relief Valve Vent and AIR Intake System Combustion System InspectionSection XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Water Heater Display Max Setpoint value Water Heater DisplayHeating No current error codes Max Setpoint Flashes Max Setpoint continues to flash Max Setpoint stops flashingDisplay of Water Temperature To Display Flame Sense Current of the Pilot Flame SensorTo Display and Change Temperature Setpoint Setpoint FlashesSetpoint Stops Flashing Changes to C F/C Flashes FlashesSymbol Stops Flashing How to reset the control from Lockout Conditions Resetting Error Codes in Soft Lockout ConditionResetting Error Codes in Hard Lockout Condition Press for 3 seconds to reset control in service modeTo view previous error codes Error Code HistoryNo Current Error Code Error Code Index No Error Code Shown for Code IndexStored Error Code For Code Index #9 ExitingSELECTServiceSETMode Page Procedure for Checking Thermostat Sensors Section XII Parts List EF Series Water HeaterCombustion Surround Assembly Combustion Assembly pictured previous Ignition Control Assembly