Bradford-White Corp EFR160T120, EFR-1-60T1206EN warranty Power Vent Maximum Vent Length

Page 30

Through The Wall Venting With Low Ground Clearance:

When venting cannot exit through the wall at a height greater than or equal to 12 inches (30.5 cm) (and above expected snow level) from the ground, then the installation must be modified as shown below (see Figure 18). Refer to Tables 3 or 4 for maximum venting lengths using 2 inch (5.1 cm), 3 inch (7.6 cm) or 4 inch (10.2 cm) diameter plastic pipe.

Figure 18. Vent Terminal (Low Ground Clearance)

Maximum Vent Length Determination

Power Vent Maximum Vent Length

 

Max Vent Length in feet

Max Vent Length in feet

Max Vent Length in

Model

(meters) for 2 inch

(meters) for 3 inch

feet (meters) for 4 inch

Number

(5.1 cm) PVC, CPVC,

(7.6 cm) PVC, CPVC,

(10.2 cm) PVC, CPVC,

 

or ABS

or ABS

or ABS

EFR60T120, EF100T150

60 (18)

120 (36)

170 (51)

Table 4

Determining required vent length:

1.Determine the total length of straight vent pipe (in feet) required.

2.Add 5 feet (1.5 m) of venting for every 90° elbow.

3.Add 2 ½ feet (.7 m) of venting for every 45° elbow.

4.Total vent length cannot exceed “Max. Vent Length” in Table 4.

Example of Total Vent Length for EF100T199 with a power vented installation:

A 3 inch (7.6 cm) venting system has a total of six 90-degree elbows and a total straight pipe length of

55feet (16.5 m).

Equivalent vent length for elbows: 6 x 5 feet (1.5 m) = 30 feet (9 m).

Total equivalent vent distance = 55 feet (16.5 m) + 30 feet (9 m) = 85 feet (25.5 m) total equivalent vent length. This is below the maximum allowed distance of 100 feet (30 m) for this model using 3 inch (7.6 cm) vent.

NOTICE

Do not include the 3 inch (7.6 cm) condensate elbow or vent terminals in determining maximum vent length.

30

Image 30
Contents With Troubleshooting Guide What to do if YOU Smell GASTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected Section II Specifications Dimensions InchesFeatures Section III General InformationTemperature and Pressure Relief Valve Condensate Elbow With Trap Section IV Installation Instructions Do not Operate the Appliance Until the Leakage is CorrectedUnpacking Minimum Clearance To Combustible Material Location Remove CrateAIR Requirements Unconfined Space Typical Installation IllustrationMechanical Exhausting of Room AIR Confined SpaceTypical Front Inlet Connection Typical Two Water Heater Connection Section V Water Connections Instructions for ConnectionsScalding Approximate TIME/TEMPERATURE Relationships in Scalds Alternate Space Heating Water ConnectionsSection VI Venting Page Direct Vent Installation VentingCanadian US Installations2 Installations1 Direct Vent Terminal Clearances Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Power Vent Installation Cm PVC, CpvcPage Typical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Multiple INTAKE/EXHAUST Terminal Separation Distances Vertical Installation Concentric Vent Terminal Installation ProcedureRain Cap to Small Vent Pipe Assembly Horizontal Installation Vent Pipe PreparationSection VII GAS Connections Initial PreparationSelection of Materials GAS Meter Size Natural Gases only GAS Pressure RegulationWiring Diagram and Schematic Section Viii Electrical ConnectionsTo Fill the Water Heater Section IX Operating InstructionsGeneral Instructions Sequence of OperationFor Your Safety Read Before Lighting Lighting and SHUT-DOWN InstructionsTemperature Adjustment Reads Idle or Heating Status IndicatorOr Service Needed Read OperationalPress SET Button for setting to take effect immediately Setpoint flashes for 10 secondsTo Decrease Setpoint Temperature Press select Changes to CSetpoint shown in F Symbol F/C Stops FlashingPress Set Press select StepSection X Maintenance GeneralBurner Flame Check Maintenance Schedule Sight Glass LocationFilling Water Heater Flushing Water HeaterDraining Water Heater Sediment and Lime Scale RemovalAnode Inspection and Replacement Drain Valve and Tank Access PanelRelief Valve Vent and AIR Intake System Combustion System InspectionSection XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Water Heater Display Max Setpoint value Water Heater DisplayHeating No current error codes Max Setpoint Flashes Max Setpoint continues to flash Max Setpoint stops flashingDisplay of Water Temperature To Display Flame Sense Current of the Pilot Flame SensorTo Display and Change Temperature Setpoint Setpoint FlashesSetpoint Stops Flashing Changes to C F/C Flashes FlashesSymbol Stops Flashing Resetting Error Codes in Hard Lockout Condition How to reset the control from Lockout ConditionsResetting Error Codes in Soft Lockout Condition Press for 3 seconds to reset control in service modeError Code History To view previous error codesNo Current Error Code Error Code Index No Error Code Shown for Code IndexStored Error Code For Code Index #9 ExitingSELECTServiceSETMode Page Procedure for Checking Thermostat Sensors Section XII Parts List EF Series Water HeaterCombustion Surround Assembly Combustion Assembly pictured previous Ignition Control Assembly