American Water Heater HPE10280H045DV, HPE10260H045DV manual Section C of Control Board con’t

Page 18

Section “C” of Control Board (con’t)

CN 211/215 UIM Communication Cable:

Pin 1 - +5 V

Pin 2 - +12 V

Pin 3 - Signal A+

Pin 4 - Signal B+

Pin 5 - Ground

Note: Both CN211 and CN215 are identical and either can be used for the UIM communication.

CN 208 Overload Detection:

Pin 1 - High pressure switch.

Pin 2 - High pressure switch.

Pin 3 - Low pressure switch.

Pin 4 - Low pressure switch.

Pin 5 - Not used

Pin 6 - Not used

Pin 7 - Not used

Pin 8 - Not used

Pin 9 - Condensate pump signal overflow (optional)

Pin 10 - Condensate pump signal overflow (optional)

Note: Pin 9 and 10 are connected by a jumper wire. This wire should be cut and wired in series to the overflow switch of the field supplied condensation pump (optional).

SW 201 Dip Switch:

SW 1 - Not used

SW 2 - Not used

SW 3 - Not used

SW 4 - Not used

Led 201 Power Indicator:

LED 201 when illuminated, indicate that 5 and 12 Volts DC are present for the UIM

Figure 9

 

Section D

LED

203 / 202

Section D

LED 202/203 Powered Anode Indicators:

LED 202-

One (1) flash/second (approx.), indicates there is power to the anode circuit.

LED 203-

Two (2) flashes/second (approx.), indicates proper operation.

Four (4) flashes/second (approx.), indicates a fault.

18

Image 18
Contents Service Handbook HPE10260H045DV 60 GAL HPE10280H045DV 80 GALTable of Contents Introduction Certifications and ApprovalsTerms, Definitions and Formulas Safety Precautions Explosion HazardInstallation Checklist Potential Installation Issues Symptom Cause SolutionPowered Anode Operation Checking the Powered Anode for Proper OperationDry Fire Element Protection Piping Installation Water Piping SystemClosed System/Thermal Expansion Temperature and Pressure Relief ValveTemperature & Pressure Relief Valve Discharge LineRoutine Preventive Maintenance General Service informationCleaning/Replacing the Air Filter Air Filter Cleaning/ReplacementHeat Pump Water Heater Operation Operating Mode DescriptionsOperational Overview User Interface Module OverviewOperating Your Heat Pump Water Heater Adjusting Set Point TemperatureSelecting Operating Mode Turning the Unit OnControl Board Overview Heat Pump Water Heater Control Board OverviewSection a of Control Board CN 203 Powered Anode Section B of Control BoardRY 203 Upper Element Relay CN 204 Upper and Lower tank water temperature sensors CN 212 Temperature SensorsSection C of Control Board Section C of Control Board con’t Wiring Diagram for Models With Relay Heater Wiring DiagramWiring Diagram for Non-Relay Models FIigureAccessing the Maintenance Display Accessing the Maintenance DisplayInterpreting the fault code history Screen Message MeaningElement Test Continuity Tester IIA. Testing for a Burned Out ElementIIB. Testing for a Grounded Element Preparing for the TestElement Test OhmMeter Heating Element Replacement Resetting a tripped ECO Energy Cutout ECO Switch TroubleshootingECO Function and Troubleshooting Relay Number Load Check PinsChecking the Run Capacitor Replacing the Powered Anode Powered Anode Troubleshooting and ReplacementRemoving the Powered Anode Removing the Top Housing Shroud± 5% Compressor Check Flow ChartCheck Voltage Resistance Values with 240 VAC inputPowered Anode Check Flow Chart Fan Check Flow Chart UIMFan Check Flow Chart Sensor Connector Chart Pins Temperature SensorsTemperature Sensor Resistance Measurement OverviewResistance vs. Temperature Charts Chart #1Pressure-Temperature Chart for Refrigerant R-134a Chart #3Cleaning the Evaporator Important Do not spray cleaner on the fan motorImportant Do not damage the fan blades Troubleshooting Common Service Problems Problem Possible Cause TEST/CORRECTIVE ActionOperating Costs Cap T&P discharge pipeCrackling, gurgling Drain valve, reliefValve, etc Popping, rumblingFault Code Troubleshooting Guide Fan Connect Fault Heat pump fan circuit is openFault Code Troubleshooting Guide Low Water Level Alarm The tank is not full of water Heat Pump Low Pressure Fault Lower pressure switch is openHeat Pump High Pressure Fault High pressure switch is open Main Control Board ROM Fault Main board failure Main Control Board Crystal Fault Main board failureMain Control Board RAM Fault Main board failure Main Control Board Eeprom Fault Main board failureLow Supply Voltage Fault Very low input voltage Power Anode Over Current Powered anode circuit not workingPower Anode ADC Error Powered anode circuit not working No Display on User Interface Module UIMDraining and Filling the Water Heater Draining and Filling the Water HeaterCondensate Pump Troubleshooting Condensate Drain MaintenanceDisposal of Condensate Part Number

RESIDENTIAL HYBRID ELECTRIC HEAT PUMP WATER HEATER, HPE10260H045DV, HPE10280H045DV specifications

The American Water Heater HPE10280H045DV and HPE10260H045DV are pioneering residential hybrid electric heat pump water heaters designed to deliver energy-efficient performance while meeting the hot water demands of modern households. These innovative units fuse traditional electric heating with advanced heat pump technology, allowing for significant reductions in energy consumption compared to conventional electric water heaters.

One of the primary features of these hybrid models is their outstanding energy efficiency ratings. Both units typically achieve an impressive Energy Factor (EF) that reflects their ability to convert electricity into hot water. By utilizing ambient air to heat water, these heat pump water heaters pull in heat from the surrounding environment and transfer it to the water, thus consuming less electricity. This technology not only reduces energy bills but also decreases the overall carbon footprint of the home.

The HPE10280H045DV and HPE10260H045DV boast a sleek, compact design that allows for flexible installation options, making them suitable for various locations within a home. Their user-friendly digital interface provides homeowners with intuitive controls to manage temperature settings and monitor performance. These models are equipped with smart technology that includes an intuitive display for adjusting modes and settings. They feature selectable operating modes, including electric, heat pump, and hybrid, allowing users to choose the most efficient heating method based on current needs.

In terms of capacity, the HPE10280H045DV offers a substantial 80-gallon tank, while the HPE10260H045DV provides a 60-gallon capacity, ensuring that households of different sizes can enjoy ample hot water for showers, laundry, and dishwashing simultaneously. Both models are designed with durability in mind, featuring robust components and corrosion-resistant tanks that promise longevity and maintenance-free operations.

Another significant aspect of these hybrid water heaters is their whisper-quiet operation, which makes them ideal for installation in living spaces or areas close to bedrooms. The noise level is minimized by the efficient insulation and placement of the compressor, ensuring that the serenity of the home is maintained.

In summary, the American Water Heater HPE10280H045DV and HPE10260H045DV represent a leap forward in the water heating industry, combining innovative heat pump technology with user-friendly features, energy efficiency, and ample capacity, making them an excellent choice for environmentally conscious homeowners looking for reliable hot water solutions.