American Water Heater HPE10260H045DV manual Temperature and Pressure Relief Valve, Discharge Line

Page 10

Temperature and Pressure Relief Valve

Explosion Hazard

‡ 7HPSHUDWXUHSUHVVXUHUHOLHI

YDOYHPXVWFRPSO\ZLWK$16,

=&6$DQG$60(

FRGH

‡ 3URSHUO\VL]HGWHPSHUDWXUH

SUHVVXUHUHOLHIYDOYHPXVWEH

LQVWDOOHGLQRSHQLQJSURYLGHG

‡ &DQUHVXOWLQRYHUKHDWLQJ

DQGH[FHVVLYHWDQNSUHVVXUH

‡ &DQFDXVHVHULRXVLQMXU\RU

GHDWK

tubing so that any discharge from the valve exits only within 6 in. (152mm) above drain, or at any distance below, the structural floor, and does not contact any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstance.

IMPORTANT: Only a new temperature and pressure relief valve should be used with your water heater. Do not use an old or existing valve as it may be damaged or not adequate

for the working pressure of the new water heater. Do not place any valve between the relief valve and the tank.

The Temperature & Pressure Relief Valve:

Shall not be in contact with any electrical part.

Shall be connected to an adequate discharge line.

Shall not be rated higher than the working pres- sure shown on the data plate of the water heater.

Figure 3

Temperature and Pressure

Relief Valve Installation

Temperature and

Pressure Relief Valve

Discharge Pipe

(Do Not Plug or Cap)

Drain Pan

2 1/2” (63.5mm) Depth Maximum and 2” (51mm) wider than the water heater.

Drain Line 3/4” (19mm)

Drain

ID Minimum

 

6” (152mm)

Maximum

Air Gap

The Discharge Line:

Shall not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line.

Shall not be capped, blocked, plugged or contain any valve between the relief valve and the end of the discharge line.

Shall terminate a maximum of 6 in. (152mm) above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the build- ing.

Shall be of material listed for hot water distribution.

Shall be installed to allow complete drainage of both the valve and discharge line.

Closed System/Thermal Expansion

As water is heated, it expands (thermal expansion). In a closed system, the volume of water will grow. As the volume of water grows, there will be a corresponding increase in water pressure due to thermal expansion.

For protection against excessive pressures and temperatures, a temperature and pressure relief valve must be installed in the opening marked “T & P RELIEF VALVE” (Figure 3).

To reduce the risk of excessive pressures and temperatures in this water heater, install temperature and pressure relief protective equipment required by local codes, but no less than a combination temperature and pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of the production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Shutoff Devices for Hot Water

Supply Systems, ANSI Z21.22 - latest edition. This valve must

be marked with the maximum set pressure not to exceed the marked maximum working pressure of the water heater. Install the valve into an opening provided and marked for this purpose in the water heater, and orient it or provide

Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent temperature-pressure relief valve operation: water discharge from the valve due to excessive pressure build up. The temperature pressure relief is not intended for the constant relief of thermal expansion. This condition is not covered under the limited warranty.

A properly-sized thermal expansion tank should be installed on all closed systems to control the harmful effects of thermal expansion. Contact a plumbing service agency or your retail supplier reguarding the installation of a thermal expansion tank.

10

Image 10
Contents Service Handbook HPE10260H045DV 60 GAL HPE10280H045DV 80 GALTable of Contents Introduction Certifications and ApprovalsTerms, Definitions and Formulas Safety Precautions Explosion HazardInstallation Checklist Potential Installation Issues Symptom Cause SolutionChecking the Powered Anode for Proper Operation Powered Anode OperationDry Fire Element Protection Piping Installation Water Piping SystemClosed System/Thermal Expansion Temperature and Pressure Relief ValveTemperature & Pressure Relief Valve Discharge LineRoutine Preventive Maintenance General Service informationCleaning/Replacing the Air Filter Air Filter Cleaning/ReplacementHeat Pump Water Heater Operation Operating Mode DescriptionsOperational Overview User Interface Module OverviewOperating Your Heat Pump Water Heater Adjusting Set Point TemperatureSelecting Operating Mode Turning the Unit OnControl Board Overview Heat Pump Water Heater Control Board OverviewSection a of Control Board Section B of Control Board CN 203 Powered AnodeRY 203 Upper Element Relay CN 212 Temperature Sensors CN 204 Upper and Lower tank water temperature sensorsSection C of Control Board Section C of Control Board con’t Wiring Diagram for Models With Relay Heater Wiring DiagramWiring Diagram for Non-Relay Models FIigureAccessing the Maintenance Display Accessing the Maintenance DisplayInterpreting the fault code history Screen Message MeaningElement Test Continuity Tester IIA. Testing for a Burned Out ElementIIB. Testing for a Grounded Element Preparing for the TestElement Test OhmMeter Heating Element Replacement Resetting a tripped ECO Energy Cutout ECO Switch TroubleshootingECO Function and Troubleshooting Relay Number Load Check PinsChecking the Run Capacitor Replacing the Powered Anode Powered Anode Troubleshooting and ReplacementRemoving the Powered Anode Removing the Top Housing Shroud± 5% Compressor Check Flow ChartCheck Voltage Resistance Values with 240 VAC inputPowered Anode Check Flow Chart Fan Check Flow Chart UIMFan Check Flow Chart Sensor Connector Chart Pins Temperature SensorsTemperature Sensor Resistance Measurement OverviewResistance vs. Temperature Charts Chart #1Pressure-Temperature Chart for Refrigerant R-134a Chart #3Important Do not spray cleaner on the fan motor Cleaning the EvaporatorImportant Do not damage the fan blades Troubleshooting Common Service Problems Problem Possible Cause TEST/CORRECTIVE ActionOperating Costs Cap T&P discharge pipeCrackling, gurgling Drain valve, reliefValve, etc Popping, rumblingFault Code Troubleshooting Guide Fan Connect Fault Heat pump fan circuit is openFault Code Troubleshooting Guide Heat Pump Low Pressure Fault Lower pressure switch is open Low Water Level Alarm The tank is not full of waterHeat Pump High Pressure Fault High pressure switch is open Main Control Board ROM Fault Main board failure Main Control Board Crystal Fault Main board failureMain Control Board RAM Fault Main board failure Main Control Board Eeprom Fault Main board failureLow Supply Voltage Fault Very low input voltage Power Anode Over Current Powered anode circuit not workingPower Anode ADC Error Powered anode circuit not working No Display on User Interface Module UIMDraining and Filling the Water Heater Draining and Filling the Water HeaterCondensate Drain Maintenance Condensate Pump TroubleshootingDisposal of Condensate Part Number

RESIDENTIAL HYBRID ELECTRIC HEAT PUMP WATER HEATER, HPE10260H045DV, HPE10280H045DV specifications

The American Water Heater HPE10280H045DV and HPE10260H045DV are pioneering residential hybrid electric heat pump water heaters designed to deliver energy-efficient performance while meeting the hot water demands of modern households. These innovative units fuse traditional electric heating with advanced heat pump technology, allowing for significant reductions in energy consumption compared to conventional electric water heaters.

One of the primary features of these hybrid models is their outstanding energy efficiency ratings. Both units typically achieve an impressive Energy Factor (EF) that reflects their ability to convert electricity into hot water. By utilizing ambient air to heat water, these heat pump water heaters pull in heat from the surrounding environment and transfer it to the water, thus consuming less electricity. This technology not only reduces energy bills but also decreases the overall carbon footprint of the home.

The HPE10280H045DV and HPE10260H045DV boast a sleek, compact design that allows for flexible installation options, making them suitable for various locations within a home. Their user-friendly digital interface provides homeowners with intuitive controls to manage temperature settings and monitor performance. These models are equipped with smart technology that includes an intuitive display for adjusting modes and settings. They feature selectable operating modes, including electric, heat pump, and hybrid, allowing users to choose the most efficient heating method based on current needs.

In terms of capacity, the HPE10280H045DV offers a substantial 80-gallon tank, while the HPE10260H045DV provides a 60-gallon capacity, ensuring that households of different sizes can enjoy ample hot water for showers, laundry, and dishwashing simultaneously. Both models are designed with durability in mind, featuring robust components and corrosion-resistant tanks that promise longevity and maintenance-free operations.

Another significant aspect of these hybrid water heaters is their whisper-quiet operation, which makes them ideal for installation in living spaces or areas close to bedrooms. The noise level is minimized by the efficient insulation and placement of the compressor, ensuring that the serenity of the home is maintained.

In summary, the American Water Heater HPE10280H045DV and HPE10260H045DV represent a leap forward in the water heating industry, combining innovative heat pump technology with user-friendly features, energy efficiency, and ample capacity, making them an excellent choice for environmentally conscious homeowners looking for reliable hot water solutions.