American Water Heater HPE10280H045DV, HPE10260H045DV manual Fault Code Troubleshooting Guide

Page 39

Fault Code Troubleshooting Guide

Upper Element Connect Fault (Upper heating element circuit is open):

Loose connection or damaged wire-

Turn off power at the circuit breaker / fuse box and check for a loose connection at the element. For access directions see “Heating Element Replacement” (p.24).

Upper element faulty-

Check resistance of the element itself to see if it’s around 12.4 Ω. If it is broken, replace non- functioning element. See “Heating Element Replacement” (p.24).

Control board faulty-

If the error persist, the problem may be caused by the control. Replace the control board.

If replacing the control board doesn’t resolve the issue, contact technical support.

Lower Element Connect Fault (lower heating element circuit is open):

Loose connection or damaged wire-

Turn off power at the circuit breaker / fuse box and check for a loose connection at the element. For access directions see “Heating Element Replacement” (p.24).

Lower element faulty-

Check resistance of the element itself to see if it is around 28 Ω. If it is broken , replace non- functioning element. See “Heating Element Replacement” (p.24).

Important: Using an element greater than 2000 watts in place of the lower element will damage the water heater and void the warranty.

Control board faulty-

If the error still persists, this problem may be caused by the control board. Replace the control board.

Heat Pump Connect Fault (Heat pump compressor circuit is open):

Loose connection or damaged wire-

Turn off power at the circuit breaker / fuse box.

Check wire harness connections at compressor, control board, run capacitor and compressor relay.

Inspect wires for damage.

Compressor thermal protector open-

Compressor will restart after coolling off. Faulty run capacitor-

Check the capacitor, see “Checking the Run Capacitor” (p.26), replace if defective. Control board faulty-

Replace control board.

If replacing the control board doesn’t resolve the issue, contact technical support. Compressor faulty-

Check the compressor, refer to the “Checking the compressor” flowchart p.28, replace if defective.

Fan Connect Fault (Heat pump fan circuit is open):

Loose connection or damaged wire-

Turn off power at the circuit breaker / fuse box

Check that connector CN207 on control board is seated.

Check wires for damage

The internal protector of fan motor may be open or the fan motor is broken-

Check the fan motor, refer to “Checking the fan motor” flowcharts (p.30-31). Replace if defective. Control board faulty-

Replace control board.

If replacing the control board doesn’t resolve the issue, contact technical support.

39

Image 39
Contents HPE10260H045DV 60 GAL HPE10280H045DV 80 GAL Service HandbookTable of Contents Certifications and Approvals IntroductionTerms, Definitions and Formulas Explosion Hazard Safety PrecautionsInstallation Checklist Symptom Cause Solution Potential Installation IssuesPowered Anode Operation Checking the Powered Anode for Proper OperationDry Fire Element Protection Water Piping System Piping InstallationDischarge Line Temperature and Pressure Relief ValveTemperature & Pressure Relief Valve Closed System/Thermal ExpansionAir Filter Cleaning/Replacement General Service informationCleaning/Replacing the Air Filter Routine Preventive MaintenanceUser Interface Module Overview Operating Mode DescriptionsOperational Overview Heat Pump Water Heater OperationTurning the Unit On Adjusting Set Point TemperatureSelecting Operating Mode Operating Your Heat Pump Water HeaterHeat Pump Water Heater Control Board Overview Control Board OverviewSection a of Control Board CN 203 Powered Anode Section B of Control BoardRY 203 Upper Element Relay CN 204 Upper and Lower tank water temperature sensors CN 212 Temperature SensorsSection C of Control Board Section C of Control Board con’t Heater Wiring Diagram Wiring Diagram for Models With RelayFIigure Wiring Diagram for Non-Relay ModelsScreen Message Meaning Accessing the Maintenance DisplayInterpreting the fault code history Accessing the Maintenance DisplayPreparing for the Test IIA. Testing for a Burned Out ElementIIB. Testing for a Grounded Element Element Test Continuity TesterElement Test OhmMeter Heating Element Replacement Relay Number Load Check Pins Energy Cutout ECO Switch TroubleshootingECO Function and Troubleshooting Resetting a tripped ECOChecking the Run Capacitor Removing the Top Housing Shroud Powered Anode Troubleshooting and ReplacementRemoving the Powered Anode Replacing the Powered AnodeValues with 240 VAC input Compressor Check Flow ChartCheck Voltage Resistance ± 5%Powered Anode Check Flow Chart UIM Fan Check Flow ChartFan Check Flow Chart Overview Temperature SensorsTemperature Sensor Resistance Measurement Sensor Connector Chart PinsChart #1 Resistance vs. Temperature ChartsChart #3 Pressure-Temperature Chart for Refrigerant R-134aCleaning the Evaporator Important Do not spray cleaner on the fan motorImportant Do not damage the fan blades Problem Possible Cause TEST/CORRECTIVE Action Troubleshooting Common Service ProblemsCap T&P discharge pipe Operating CostsPopping, rumbling Drain valve, reliefValve, etc Crackling, gurglingFan Connect Fault Heat pump fan circuit is open Fault Code Troubleshooting GuideFault Code Troubleshooting Guide Low Water Level Alarm The tank is not full of water Heat Pump Low Pressure Fault Lower pressure switch is openHeat Pump High Pressure Fault High pressure switch is open Main Control Board Eeprom Fault Main board failure Main Control Board Crystal Fault Main board failureMain Control Board RAM Fault Main board failure Main Control Board ROM Fault Main board failurePower Anode Over Current Powered anode circuit not working Low Supply Voltage Fault Very low input voltageNo Display on User Interface Module UIM Power Anode ADC Error Powered anode circuit not workingDraining and Filling the Water Heater Draining and Filling the Water HeaterCondensate Pump Troubleshooting Condensate Drain MaintenanceDisposal of Condensate Part Number

RESIDENTIAL HYBRID ELECTRIC HEAT PUMP WATER HEATER, HPE10260H045DV, HPE10280H045DV specifications

The American Water Heater HPE10280H045DV and HPE10260H045DV are pioneering residential hybrid electric heat pump water heaters designed to deliver energy-efficient performance while meeting the hot water demands of modern households. These innovative units fuse traditional electric heating with advanced heat pump technology, allowing for significant reductions in energy consumption compared to conventional electric water heaters.

One of the primary features of these hybrid models is their outstanding energy efficiency ratings. Both units typically achieve an impressive Energy Factor (EF) that reflects their ability to convert electricity into hot water. By utilizing ambient air to heat water, these heat pump water heaters pull in heat from the surrounding environment and transfer it to the water, thus consuming less electricity. This technology not only reduces energy bills but also decreases the overall carbon footprint of the home.

The HPE10280H045DV and HPE10260H045DV boast a sleek, compact design that allows for flexible installation options, making them suitable for various locations within a home. Their user-friendly digital interface provides homeowners with intuitive controls to manage temperature settings and monitor performance. These models are equipped with smart technology that includes an intuitive display for adjusting modes and settings. They feature selectable operating modes, including electric, heat pump, and hybrid, allowing users to choose the most efficient heating method based on current needs.

In terms of capacity, the HPE10280H045DV offers a substantial 80-gallon tank, while the HPE10260H045DV provides a 60-gallon capacity, ensuring that households of different sizes can enjoy ample hot water for showers, laundry, and dishwashing simultaneously. Both models are designed with durability in mind, featuring robust components and corrosion-resistant tanks that promise longevity and maintenance-free operations.

Another significant aspect of these hybrid water heaters is their whisper-quiet operation, which makes them ideal for installation in living spaces or areas close to bedrooms. The noise level is minimized by the efficient insulation and placement of the compressor, ensuring that the serenity of the home is maintained.

In summary, the American Water Heater HPE10280H045DV and HPE10260H045DV represent a leap forward in the water heating industry, combining innovative heat pump technology with user-friendly features, energy efficiency, and ample capacity, making them an excellent choice for environmentally conscious homeowners looking for reliable hot water solutions.