American Water Heater HPE10260H045DV Condensate Pump Troubleshooting, Disposal of Condensate

Page 46

Condensate Pump Troubleshooting

A condensate pump may be necessary if the drain point is above the level of the condensate drain on the heat pump water heater. A condensate pump failure detect is provided with the heat pump water heater control. Follow the instructions in the installation and operation manual for connection of the condensate pump failure switch to the heat pump control.

Should the condensate pump fail to operate and clear the condensate from the pump reservoir, the float switch provided with the pump will open. The heat pump control will detect condensate pump failure and shut off the heat pump in order to stop condensate from being produced. “HEAT PUMP FAULT” will be displayed on the user interface and the heat pump will not operate until the fault is cleared. By checking the MAINTENANCE DISPLAY, the fault can be narrowed down. For

a condensate pump failure, the MAINTENANCE DISPLAY will indicate CONDENSATE DRAIN ALARM.

In order to determine the cause of the condensate drain alarm, first ensure that the condensate pump has power. Check that the condensate pump is plugged into an outlet and that the socket that the condensate pump is plugged into is powered. If the pump has power, check the outlet tubing for clogs or kinks that could prevent flow of condensate. Also check the pump inlet in the sump for debris that might block flow. Follow the condensate pump manufacturer’s instructions for seperating the pump section from the tank.

If condensate pump appears to be functioning properly but is unable to clear the condensate from the tank, make sure the height of the discharge point does not exceed the pump manufacturer’s specification. Consult the manufacturer’s literature for this information.

Condensate Drain Maintenance

Condensate may be produced when the heat pump runs, depending on the amount of humidity in the air. If the relative humidity is high, the amount

of condensate can exceed 20 oz per hour. The condensate is collected in a plastic pan under the evaporator. Two drain ports are provided for connection of primary and secondary drain lines. 1/2 inch PVC is recommended for connection to the drain ports. The condensate pan, drain ports and lines should be inspected and cleaned periodically. Shut off power to the appliance before performing any maintenance or repair. Access to the drain pan can be gained by removing right side of louver panel. The black plastic pan is inside located below the evaporator and the two drain ports are located toward the back of the unit. Wipe the inside of the condensate pan with a clean rag to remove any debris or algea that may be present. Use an old toothbrush or a bottle brush to clean the inside of the two drain ports. Flush the ports with a small amount of clean water. Clean the condensate pump, if one is installed, in accordance with the manufacturer’s instructions.

Disposal of Condensate

Condensate should be disposed of in accordance with any applicable local codes that may exist. Guidelines for HVAC systems are applicable to the heat pump water heater.

Inspection/Cleaning of the Condensate Drain Pan & Condensate Drain Lines

IMPORTANT: Before attempting to clean or replace the condensate drain pan or lines press the power button to place the water heater in Standby Mode and shut-off power to the water heater at the circuit breaker/fuse box.

1.Remove the access panel (fan side) by loosening the screws securing it to the unit.

2.Check the condensate drain pan and drain lines for any dirt or debris that might interfere with proper drainage. Wipe out any dirt or debris with a damp cloth.

3.Once the condensate drain pan and lines have been inspected/cleaned, secure the access panel to the water heater.

4.Restore power to the water heater and press the power button to turn the water heater on. NOTE: The water heater will conduct an eight (8) minute system diagnostic prior to operation.

46

Image 46
Contents Service Handbook HPE10260H045DV 60 GAL HPE10280H045DV 80 GALTable of Contents Introduction Certifications and ApprovalsTerms, Definitions and Formulas Safety Precautions Explosion HazardInstallation Checklist Potential Installation Issues Symptom Cause SolutionChecking the Powered Anode for Proper Operation Powered Anode OperationDry Fire Element Protection Piping Installation Water Piping SystemClosed System/Thermal Expansion Temperature and Pressure Relief ValveTemperature & Pressure Relief Valve Discharge LineRoutine Preventive Maintenance General Service informationCleaning/Replacing the Air Filter Air Filter Cleaning/ReplacementHeat Pump Water Heater Operation Operating Mode DescriptionsOperational Overview User Interface Module OverviewOperating Your Heat Pump Water Heater Adjusting Set Point TemperatureSelecting Operating Mode Turning the Unit OnControl Board Overview Heat Pump Water Heater Control Board OverviewSection a of Control Board Section B of Control Board CN 203 Powered AnodeRY 203 Upper Element Relay CN 212 Temperature Sensors CN 204 Upper and Lower tank water temperature sensorsSection C of Control Board Section C of Control Board con’t Wiring Diagram for Models With Relay Heater Wiring DiagramWiring Diagram for Non-Relay Models FIigureAccessing the Maintenance Display Accessing the Maintenance DisplayInterpreting the fault code history Screen Message MeaningElement Test Continuity Tester IIA. Testing for a Burned Out ElementIIB. Testing for a Grounded Element Preparing for the TestElement Test OhmMeter Heating Element Replacement Resetting a tripped ECO Energy Cutout ECO Switch TroubleshootingECO Function and Troubleshooting Relay Number Load Check PinsChecking the Run Capacitor Replacing the Powered Anode Powered Anode Troubleshooting and ReplacementRemoving the Powered Anode Removing the Top Housing Shroud± 5% Compressor Check Flow ChartCheck Voltage Resistance Values with 240 VAC inputPowered Anode Check Flow Chart Fan Check Flow Chart UIMFan Check Flow Chart Sensor Connector Chart Pins Temperature SensorsTemperature Sensor Resistance Measurement OverviewResistance vs. Temperature Charts Chart #1Pressure-Temperature Chart for Refrigerant R-134a Chart #3Important Do not spray cleaner on the fan motor Cleaning the EvaporatorImportant Do not damage the fan blades Troubleshooting Common Service Problems Problem Possible Cause TEST/CORRECTIVE ActionOperating Costs Cap T&P discharge pipeCrackling, gurgling Drain valve, reliefValve, etc Popping, rumblingFault Code Troubleshooting Guide Fan Connect Fault Heat pump fan circuit is openFault Code Troubleshooting Guide Heat Pump Low Pressure Fault Lower pressure switch is open Low Water Level Alarm The tank is not full of waterHeat Pump High Pressure Fault High pressure switch is open Main Control Board ROM Fault Main board failure Main Control Board Crystal Fault Main board failureMain Control Board RAM Fault Main board failure Main Control Board Eeprom Fault Main board failureLow Supply Voltage Fault Very low input voltage Power Anode Over Current Powered anode circuit not workingPower Anode ADC Error Powered anode circuit not working No Display on User Interface Module UIMDraining and Filling the Water Heater Draining and Filling the Water HeaterCondensate Drain Maintenance Condensate Pump TroubleshootingDisposal of Condensate Part Number

RESIDENTIAL HYBRID ELECTRIC HEAT PUMP WATER HEATER, HPE10260H045DV, HPE10280H045DV specifications

The American Water Heater HPE10280H045DV and HPE10260H045DV are pioneering residential hybrid electric heat pump water heaters designed to deliver energy-efficient performance while meeting the hot water demands of modern households. These innovative units fuse traditional electric heating with advanced heat pump technology, allowing for significant reductions in energy consumption compared to conventional electric water heaters.

One of the primary features of these hybrid models is their outstanding energy efficiency ratings. Both units typically achieve an impressive Energy Factor (EF) that reflects their ability to convert electricity into hot water. By utilizing ambient air to heat water, these heat pump water heaters pull in heat from the surrounding environment and transfer it to the water, thus consuming less electricity. This technology not only reduces energy bills but also decreases the overall carbon footprint of the home.

The HPE10280H045DV and HPE10260H045DV boast a sleek, compact design that allows for flexible installation options, making them suitable for various locations within a home. Their user-friendly digital interface provides homeowners with intuitive controls to manage temperature settings and monitor performance. These models are equipped with smart technology that includes an intuitive display for adjusting modes and settings. They feature selectable operating modes, including electric, heat pump, and hybrid, allowing users to choose the most efficient heating method based on current needs.

In terms of capacity, the HPE10280H045DV offers a substantial 80-gallon tank, while the HPE10260H045DV provides a 60-gallon capacity, ensuring that households of different sizes can enjoy ample hot water for showers, laundry, and dishwashing simultaneously. Both models are designed with durability in mind, featuring robust components and corrosion-resistant tanks that promise longevity and maintenance-free operations.

Another significant aspect of these hybrid water heaters is their whisper-quiet operation, which makes them ideal for installation in living spaces or areas close to bedrooms. The noise level is minimized by the efficient insulation and placement of the compressor, ensuring that the serenity of the home is maintained.

In summary, the American Water Heater HPE10280H045DV and HPE10260H045DV represent a leap forward in the water heating industry, combining innovative heat pump technology with user-friendly features, energy efficiency, and ample capacity, making them an excellent choice for environmentally conscious homeowners looking for reliable hot water solutions.