TROUBLESHOOTING WITH THE LED
| LED STATUS | INDICATES |
| CHECK/REPAIR | |
| OFF | No power to system control. |
| 1. | Appliance On/Off switch in the Off position. |
|
|
|
| 2. | Line voltage input power at L1 and L2 connectors. |
|
|
|
| 3. | System wiring harness in good condition and securely |
|
|
|
|
| connected at both ends. |
|
|
|
|
| |
| BRITE - DM | Normal Operation |
| Not Applicable. | |
|
|
|
|
| |
|
| This indication shows whenever the system is |
|
|
|
|
| powered, unless some abnormal event has occurred. |
|
|
|
|
|
|
|
|
|
| 1 FLASH | Setpoint error, internal failure detected. |
| 1. | Replace control. |
|
|
| |||
|
|
|
|
|
|
|
| Airflow proving switch remains open longer than |
| 1. | Airflow proving switch stuck closed. |
|
| 30 seconds after a call for heat begins. |
| 2. | Airflow proving switch |
| 2 FLASHES |
|
|
|
|
|
| Combustion air blower is not energized |
|
| WARNING |
|
| until airflow proving switch opens. |
|
| Line Voltage Hazard. |
|
|
|
|
| Can cause property damage, severe injury or |
|
|
|
|
| death. |
|
|
|
|
| Turn off appliance before coming in contact with |
|
|
|
|
| pressure switch and/or electrical connections. |
|
|
|
|
|
|
| 3 FLASHES | Airflow proving switch remains open longer than |
| 1. | Airflow proving switch operation, tubing and wiring. |
|
| 30 seconds after combustion air blower energized. |
| 2. | Obstructions or restrictions in appliance air intake |
|
|
|
|
| or exhaust flue system that prevent proper combustion |
|
| System goes into 5 minute delay period, with |
|
| air flow. |
|
| combustion air blower off. At the end of the |
|
|
|
|
| 5 minute delay, another ignition cycle will begin. |
|
| WARNING |
|
|
|
|
| Line Voltage Hazard. |
|
|
|
|
| Can cause property damage, severe injury or |
|
|
|
|
| death. |
|
|
|
|
| Turn off appliance before coming in contact with |
|
|
|
|
| pressure switch and/or electrical connections. |
|
|
|
|
|
|
|
| Thermal Cutoff open. |
| 1. | Replace Control. |
| 4 FLASHES | Combustion air blower is energized. |
|
|
|
|
| Internal hardware failure. |
|
|
|
|
|
|
|
|
|
|
| Flame signal sensed out of proper sequence. |
| 1. | Flame at main burner. |
| 5 FLASHES | Combustion air blower is energized. |
| 2. | Replace control. |
|
|
|
|
|
|
|
| System Lockout. |
| 1. | Gas supply off or at too low pressure to operate. |
|
|
|
| 2. | Damaged or broken HSI element. |
| 6 FLASHES | After 1 hour lockout reset delay, control will reset |
| 3. | Appliance not properly earth grounded. |
|
| and initiate a new ignition sequence if the call for |
| 4. | Flame sense rod contaminated or in incorrect location. |
|
| heat is still present. |
| 5. | HSI element located incorrect position. |
|
|
|
| 6. | HSI element or flame sense rod wiring in good |
|
|
|
|
| condition and properly connected. |
|
|
|
| 7. | Less than 100 Vac between flame rod and burner |
|
|
|
|
| pan with 120 Vac input to control. |
|
|
|
| 8. | Cycle external power or remove request for heat for |
|
|
|
|
| 2 seconds and reapply. |
|
|
|
|
|
|