A.O. Smith BTF-75 warranty AIR Requirements, Unconfined Space, Confined Space, Water Connections

Page 5

The heater is design certified by the Canadian Standards for installation on combustible flooring in a closet having minimum clearances from combustible material of: 2" clearance from sides and rear, 6" from the front and 24" from the top. (Standard clearance.) If clearances stated on the heater differ from standard clearances, install water heater according to clearances stated on heater.

A minimum clearance of 4" must be allowed for access to replaceable parts such as the thermostats, drain valve and relief valve. A top clearance of 24" should be allowed for blower assembly service.

Adequate clearance for servicing this appliance should be considered before installation, such as changing the anodes, etc. Minimum clearances for proper operation are given above.

WARNING

In cold climates provide protection against freeze-up.

THEHEATERSHOULDBELOCATEDINANAREAWHERELEAKAGEOF THE TANK OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE AREA ADJACENT TO THE HEATER OR TO LOWER FLOORS OF THE STRUCTURE. When such locations cannot be avoided, a suitable drain pan should be installed under the heater, see fig. 1. The pan must not restrict combustion air flow. Such pans should have a minimum length and width of at least 2 inches greater than the diameter of the heater and should be piped to an adequate drain. Drain pans suitable for these heaters are available from your dealer or A. O. Smith Water Products Company, 5621 W. 115th Street, Alsip, Illinois 60803.

WARNING

DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A CARPETED FLOOR. A FIRE HAZARD MAY RESULT. Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches (76.2mm) in any direction. If the heater is installed in a carpeted alcove or closet, the entire floor shall be covered by the panel.

AIR REQUIREMENTS

In calculating the free area of a vent opening, the blocking effect of screens, louvers and grills should be considered. Screens shall not be of a mesh smaller than 1/4 inch square. If the free area is not known, the latest edition of National Fuel Gas Code ANSI Z223.1 recommends using figures of 20-25 percent free area for wood louvers or 60-75 percent for metal grills or louvers.

UNCONFINED SPACE

In buildings of conventional frame, brick or stone construction, unconfined spaces may provide adequate air for combustion, ventilation, and dilution air for power venter.

If the unconfined space is within a building of tight construction (building using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion, ventilation, and venter dilution must be obtained from outdoors. The installation instructions for confined spaces must be followed.

CONFINED SPACE

When drawing combustion and dilution air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings. ONE WITHIN 12 INCHES OF THE ENCLOSURE TOP AND ONE WITHIN 12 INCHES OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of one square inch per 1000 Btuh of the total input of all appliances in the enclosure, but not less than 100 square inches.

If the confined space is within a building of tight construction, air for combustion, ventilation and power venter dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating through vertical ducts, two permanent openings, located in the above manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btuh of the total input of all appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2000 Btuh of the total input of all appliances in the enclosure.

WATER CONNECTIONS

Refer to figure 12 for typical installation. A suitable pipe thread sealant must be used to prevent leakage.

WATER (POTABLE) HEATING AND SPACE

HEATING

1.All piping components connected to this unit for space heating applications shall be suitable for use with potable water.

2.Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.

3.This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance.

4.When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to Fig. 2 for suggested piping arrangement.

5

Image 5
Contents SmartValve is a Registered Trademark of Honeywell Inc Commercial GAS, GLASS-LINED, TANK-TYPE Water HeaterALL Dimensions in Inches ROUGH-IN-DIMENSIONSRecovery Capacities ForewordGeneral Safety Information Table of ContentsInstallation Unconfined Space AIR RequirementsConfined Space Water ConnectionsClosed Water System Venting Single TemperatureRelief Valve Vent Pipe TerminationIf using 4 inch vent pipe If using 3 inch vent pipePlanning the Vent System Number Maximum Elbows Pipe FeetPreparation of Blower Assembly Installation of Sidewall Vent SystemVent Terminal INSTALLATION, Sidewall Power Vent Wiring Schematic Figure Installation of Vertical Vent System Installation of Vent SYSTEM, SidewallVent Pipe Preparation Initial PreparationCement PrimerMaking the Joint Step aGAS Connections OperationConnection of GAS Pipe To Operate the HeaterDo not TRY to Light the Burner by Hand WatertemperatureadjustmentWhat to do if YOU Smell GAS Do not TRY to Light the Burner by HandTemperature Regulation MaintenanceWater Temperature Adjusting Dial PurgingPower Venter Maintenance High Temperature CUT-OFF SwitchVenting System ValveTrouble Shooting Service and RepairCondensation Cathodic PROTECTION-ANODEVent Pipe TOO HOT TroubleshootingAbove 170 F Yellow FlameFlash Troubleshooting with the LEDOFF YES Check for Proper Voltage ATTurn on GAS Supply Plug Replace HSIClaim Procedure Service and Repair ExpensesTank ALL Other Parts