A.O. Smith BTI 120 warranty Venting, Multiple Heater Manifold

Page 8

ILLUSTRATION OF MINIMUM COMBUSTIBLE CLEARANCES INANALCOVE - FIGURE 6

AND ONE IN OR WITHIN 12 INCHES (30.5cm) OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch per 1000 Btuh (2,225mm2/kW)of the total input of all appliances in the enclosure, but not less than 100 square inches (645 square cm).

If the confined space is within a building of tight construction, air for combustion, ventilation, and drafthood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating with the outdoors through vertical ducts, two permanent openings, located in the above manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btuh (550mm2/kW) of the total input of all appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2000 Btuh (1102mm2/kW) of the total input of all appliances in the enclosure.

VENTING

WARNING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.

Heater must be protected from freezing downdrafts.

Remove all soot or other obstructions from the chimney that will retard a free draft.

Type B venting is recommended with these heaters. For typical venting application see TECHNICAL DATA VENTING on pages 9 and 10.

This water heater must be vented in compliance with all local codes, the current revision of the National Fuel Gas Code (ANSI-Z223.1) and with the Category I Venting Tables.

If any part of the vent system are exposed to ambient temperatures below 40°F (5°C) it must be insulated to prevent condensation.

The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation.

1.Seal any unused openings in the venting system.

2.Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3.So far as is practical, close all building doors and windows and all doors between the space in which the water heater(s) connected to the venting system are located and other spaces of the building. Turn on all appliances not connected to the venting system. Turn on all exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at

maximum speed. Close fireplace dampers.

4.Follow the lighting instruction. Place the water heater being inspected in operation. Adjust thermostat so appliance shall operate continuously.

5.After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

6.If improper venting is observed during any of the above tests, the venting system must be corrected.

WARNING

FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS.

If the back draft cannot be corrected by the normal method or if a suitable draft cannot be obtained, a blower type flue gas exhauster must be employed to assure proper venting and correct combustion.

Do not connect the heater to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by many local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems.

FIGURE7

Where a separate vent connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace, the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe.

MULTIPLE HEATER MANIFOLD

Figure 8 and tables on pages 9 and 10 should be used for horizontally manifolding two or more heaters.

FIGURE8

8

Image 8 Contents
Models BTI 120 Thru 400/A Commercial GAS, GLASS-LINED, TANK-TYPE Water HeaterGasand Electrical Characteristics ROUGH-IN-DIMENSIONSFront View TOP View Back View ROUGH-IN-DIMENSIONS Table of Contents Foreword General Safety Information High Limit Switch FeaturesHigh Altitude Installations Electronic Ignition Control Exhaust Inducer Blower AssyCirculating Pump Dishwashing Machine RequirementLeveling ClearancesHard Water AIR RequirementsVenting Multiple Heater ManifoldModel BTI-154 Type B GAS VentModel BTI-120 Model BTI-310 Model BTI-250Model BTI-275 Water Line Connections Water Potable Heating and SpaceGAS Piping System ConnectionsGAS Piping and Dirt LEG Installation GAS Pressure RegulatorGAS Meter Size Natural Gases only Type of GASHeater Wiring Single Unit Wiring Diagram BTI-120 Through 400AInstallation DIAGRAMS-TOP INLET/OUTLET Usage Tube Inlet InstallationGeneral Code RestrictionsVertical Storage Tank and Forced Circulation Horizontal Storage Tank and Forced CirculationPage Installation DIAGRAMS-SIDE INLET/OUTLET Usage Circulating Return Line ConnectionHeater with Mixing Valve and Recirculated Sanitizing Loop TWO PRE-HEATERS with Booster Heater Horizontal Storage Tank Model Dimension a Manifold KitsOperation Sequence of Operation For Your Safety Read Before Operating What to do if YOU Smell GASPreventive Maintenance Water Temperature ControlCheck the Ignitor Assembly Ignitor AssemblyRemote Storage Tank Temperature Control GAS ValvesChecking the Input Venting SystemHOT Water Odor Anode ROD InspectionFlushing DrainingDeliming Solvents Tank Cleanout ProcedureDeliming Using FLO-JUG Method Service Replacement PartsSystem Diagnostics Ignition Module SystemSequence of Operation Flow Chart YESRemedy Operational ChecklistComplaint Cause User Serviceman Service and Repair Expenses Claim ProcedureKeepthiswarrantypostedadjacenttotheheaterforfuturereference Tank