Mitsubishi Electronics PCH42GK, PCH24GK OC277-31, Detecting abnormalities in the outdoor unit

Page 31

(4)Detecting abnormalities in the outdoor unit

After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the dif- ference is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code “P8” appears on remote controller.

RANGE A : Indoor coil temperature is more than 9 degrees above room temperature.

RANGE B : Indoor coil temperature is within 9 degrees either way of room temperature.

RANGE C : Indoor coil temperature is more than 9 degrees below room temperature.

Indoor coil temperature minus room temperature

(degree)

+9

0

-9

RANGE A

RANGE B

RANGE C

OC277-31

Image 31
Contents OC277-1 ContentsOC277-2 FeaturesOC277-3 Easy Maintenance no Maintenance Necessary for 2500 HoursImproving Efficiency of Piping Work OC277-4 Part Names and FunctionsOC277-5 Remote controller operation buttonsOC277-6 Remote controller displayOC277-7 SpecificationsModels PCH24GK, PCH30GK, PCH36GK, PCH42GK CFM SHC TPC DataOC277-8 Models PCH24GK, PCH30GK, PCH36GK, PCH42GK Performance DataCFM OC277-9Performance Curve OC277-10PCH36GK Cooling Capacity PCH36GK Heating Capacity OC277-11Condensing Pressure and Suction Pressure OC277-12PCH30GK OC277-13PCH36GK OC277-14PCH42GK OC277-15Standard Operation Data OC277-16SHF PCH24GK PCH30GK PCH36GK PCH42GK Additional Refrigerant Charge R22oz OC277-17Operating Range Outlet AIR Speed and Coverage RangePCH36GK PCH42GK OC277-18Noise Criterion Curves PCH24GK PCH30GKOC277-19 Outlines and DimensionsIndoor unit PCH24GK Indoor unit PCH30/36/42GK OC277-20PCH30GK PCH36GK PCH42GK Refrigerant System DiagramRemote controller OC277-21Model PCH24/30/36/42GK Wiring Diagram Wiring DiagramOC277-22 OC277-23 Operation FLOW-CHARTMain Operation Cooling Operation OC277-24YES OC277-25DRY Operation DRYHeating Operation OC277-26OC277-27 Microprocessor ControlOutline of Microprocessor Control Compressor control How to operateOC277-28 Indoor Unit ControlTermination conditions OC277-29Start condition Coil frost protectionAuto Return OC277-30Auto vane control SwingDetecting abnormalities in the outdoor unit OC277-31Range a Range B Range C OC277-32 DRY operation time chart How to operateDRY operation OC277-33 Display in Heat operation Heat operation time chartOC277-34 Heat operationOverheat prevention OC277-35Overheat protection Booster heater controlOC277-36 Indoor coil temperature abnormality detectionDefrosting operation OC277-37 Initial mode How to operateMode change Temperature rangeCOOL/DRY operation OC277-38Auto return Test run Before test run Timer operationTimer function OC277-39Emergency operation OC277-40Before emergency operation On indoor controller board Dip switch functionsOn remote controller board OC277-41PCH36, 42GK Fan motor max. rotational frequency Service RefOC277-42 PCH24GK PCH30GK PCH36GK PCH42GK SW7 OFFRemote Controller Display Abnormality Trouble ShootingOC277-43 Example Check Unit code address When malfunction occurs during operationFor group control using one remote controller OC277-44OC277-45 Heat Wrong Wiring on SiteOC277-46 CoolOther Troubles and Causes OC277-47OC277-48 How to check the partsPCH OC277-49 PAC-SA89TA-E System ControlOC277-50 Variety of System Control FunctionsOC277-51 Group Control with a Single Remote ControllerHow to wire How to set unit-addressRemote controller LCD indication Control Using TWO Remote ControllersRemote ON-OFF and Individual Remote Controls How to set SW17-7 See FigureOC277-53 Individual Control by Grouping the Remote ControllersBasic wiring Switch function of remote ON-OFF switchAuto Restart Function Multiple Remote Control DisplayTimer Operation or the Operation by AN External Signal OC277-54Removing the air intake grille Disassembly ProcedurePCH24GK Operating Procedure OC277-55Removing the side panel OC277-56Removing the fan motor Removing the sirocco fanRemoving the Indoor coil thermistor Operating Procedure PhotosOC277-57 Removing the vane motorRemove the intake grille OC277-58Removing the drain pan Removing the guide vaneRemoving the support heater OC277-59Removing the heat exchanger OC277-60 Parts ListStructural Part PCH24GK OC277-61 Structural Part PCH30GK PCH36GK PCH42GK OC277-62OC277-63 FAN and Heater Parts PCH24GK OC277-64FAN and Heater Parts PCH30GK PCH36GK PCH42GK OC277-65Electrical Parts PCH24GK10 PCH30GK PCH36GK PCH42GK OC277-66Optional Parts TimerOC277-67 SET Back Display PAC-SC32PTA Weekly Timer Setting DisplayOC277-68 Names and functionsRefrigerant Pipes Timer AdapterMultiple Remote Controller Adapter OC277-69Specifications are subject to change without notice