2. GROUP CONTROL WITH A SINGLE REMOTE CONTROLLER
A maximum of 50 units can be started in order according to the dip switch settings
2-1 How to wire
(1) | Connect the remote controller to the double terminal block |
| on the indoor controller board of the master unit (No.0 unit). |
| (See Figure 1.) |
(2) | Connect the double terminal block of the master unit to the |
| double terminal block of No.1 unit. |
(3) | Connect the double terminal block of No.1 unit to the dou- |
| ble terminal block of No.2 unit. |
(4) | Continue the process until all the units are connected with |
| |
(5) | Remove the connector CN40 from the indoor controller |
| board of each unit except the master unit. (See Figure 3.) |
Figure 1
To remote controller
Master unit |
|
electrical box | GR |
| L1 L2 |
| 3 |
| 2 |
| 1 |
To next |
| To next unit | |
unit |
| ||
|
| ||
Next unit | L2 GR | The last unit | |
dose not have | |||
electrical box | L1 | ||
3 | this wire. | ||
| |||
| 2 |
| |
| 1 |
|
(6) Set the |
controller board following the instructions below. |
2-2 How to set unit-address
The
(1)Each lever of SW2 shows the number as follows.
(2)Total number of levers turned to ON shows the address of the unit.
For example, to set No.3 unit, turn ON
(3)In this way, set from the master unit to the last unit. Do not forget to set the master (No. 0) unit.
Figure 2 |
|
|
|
Master | No.1 unit | No.2 unit | Last unit |
unit |
| ||
|
|
Figure 3
Indoor controller board ▼
Should be removed from all units other than unitNo.0:
(Master Unit).
CN40
CN40
SW2
SW2
ON
1
2
3
4
6 5
Setting examples
| Master (No. 0) unit | No. 1 unit | No. 2 unit | No. 4 unit | No. 8 unit | No. 16 unit | No. 32 unit | |||||||
| ALL OFF | 1 ON | 2 ON |
| 3 ON | 4 ON |
| 5 ON | 6 ON | |||||
SW2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 6 |
| 6 |
| 6 |
| 6 |
| 6 |
| 6 |
| 6 |
|
| 5 |
| 5 |
| 5 |
| 5 |
| 5 |
| 5 |
| 5 |
|
| 4 |
| 4 |
| 4 |
| 4 |
| 4 |
| 4 |
| 4 |
|
| 3 |
| 3 |
| 3 |
| 3 |
| 3 |
| 3 |
| 3 |
| 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 |
Unit address & start |
| 0 |
| 1 |
| 2 |
| 4 |
| 8 |
| 16 |
| 32 |
delay in seconds. |
|
|
|
|
|
|
|
2-3 Unit control
The remote controller can control all units each unit turns ON or OFF individually to
ON/OFF, temperature, air flow, and swing louver. However, the thermostat in adjust to the room temperature.