Mitsubishi Electronics PCH42GK, PCH24GK OC277-35, Overheat protection, Booster heater control

Page 35

(1)Compressor control

13-minute time delay

To prevent overload, the compressor will not start within 3 minutes after stop.

2The compressor runs when the room temperature is lower than the set temperature.

The compressor stops when the room temperature is equal to or higher than the set temperature.

3The compressor stops in check mode or during protective functions.

4Overheat protection

<Start condition>

When the indoor coil thermistor reads 158°F or above, the overheat protection will start.

<Overheat protection>

The compressor stops for 6 minutes, and then restarts.

If the start condition is satisfied again within 10 minutes of compressor operation, both the indoor and outdoor units stop, displaying a check code of “P6” on the remote controller.

<Termination conditions>

Overheat protection is terminated when the start condition is not satisfied again during the allowance (10-minute compres- sor operation), when operation mode changes to other mode, or when thermostat turns OFF.

(2)Indoor fan control

(a)Normal control

( i )The indoor fan runs on EXTRA-LOW speed during the thermostat OFF.

EXTRA-LOW speed can be changed to LOW or HIGH speed by setting the dip switch SW1-5 and SW1-6.

If the indoor coil temperature becomes more than 5 degrees below the room temperature during the thermostat OFF, the indoor fan will stop. After, when the indoor coil temperature becomes within 5 degrees of room tempera- ture, the indoor fan will run on EXTRA-LOW speed.

( ii )Hot adjustment

Hot adjustment is a warm-up for HEAT operation <Start conditions>

The hot adjustment works under any of the following conditions.

HEAT operation starts.

Defrosting ends.

Thermostat turns ON.

[Hot adjustment]

Initially, the indoor fan runs on EXTRA-LOW speed. When 5 minutes have passed or the indoor coil temperature exceeds 95°F, the fan speed changes to LOW. 2 minutes later, the hot adjustment ends. Then, the fan speed depends on the remote controller setting.

(iii)The indoor fan stops when the indoor coil temperature is within 9 degrees either way of room temperature. (iv)To eliminate the remaining heat, the indoor fan runs for the first 1 minute after the booster heater is turned OFF.

(3)Auto vane control

Auto vane position is set to 70 degrees airflow at the start-up of HEAT operation.

(a) Vane position set mode & swing mode.

( i ) Every time AIR DISCHARGE button is pressed, setting will be changed . ( ii ) Airflow direction can be changed with AIR DISCHARGE button.

horizontal

20°

40°

60°

SWING

NOTE : In the following cases, the discharge direction is horizontal regardless of the remote controller setting.

1During the hot adjustment with fan speed at EXTRA-LOW

2 During defrosting with indoor fan OFF

3 During thermostat OFF

(4)Booster heater control

When the room temperature is 6 degrees below the set temperature, the booster heater will turn ON. When the room temperature is equal to the set temperature, booster heater will turn OFF.

During the hot adjustment, the booster heater will not work.

<Overheat prevention>

When the indoor coil thermistor rises to 140°F or above, the booster heater cannot work. When the indoor coil thermistor falls to 131°F or below, the booster heater can work.

OC277-35

Image 35
Contents OC277-1 ContentsOC277-2 FeaturesImproving Efficiency of Piping Work Easy Maintenance no Maintenance Necessary for 2500 HoursOC277-3 OC277-4 Part Names and FunctionsOC277-5 Remote controller operation buttonsOC277-6 Remote controller displayModels PCH24GK, PCH30GK, PCH36GK, PCH42GK SpecificationsOC277-7 CFM SHC TPC DataOC277-8 Models PCH24GK, PCH30GK, PCH36GK, PCH42GK Performance DataCFM OC277-9Performance Curve OC277-10PCH36GK Cooling Capacity PCH36GK Heating Capacity OC277-11Condensing Pressure and Suction Pressure OC277-12PCH30GK OC277-13PCH36GK OC277-14PCH42GK OC277-15SHF PCH24GK PCH30GK PCH36GK PCH42GK OC277-16Standard Operation Data Additional Refrigerant Charge R22oz OC277-17Operating Range Outlet AIR Speed and Coverage RangePCH36GK PCH42GK OC277-18Noise Criterion Curves PCH24GK PCH30GKIndoor unit PCH24GK Outlines and DimensionsOC277-19 Indoor unit PCH30/36/42GK OC277-20PCH30GK PCH36GK PCH42GK Refrigerant System DiagramRemote controller OC277-21OC277-22 Wiring DiagramModel PCH24/30/36/42GK Wiring Diagram Main Operation Operation FLOW-CHARTOC277-23 Cooling Operation OC277-24YES OC277-25DRY Operation DRYHeating Operation OC277-26Outline of Microprocessor Control Microprocessor ControlOC277-27 Compressor control How to operateOC277-28 Indoor Unit ControlTermination conditions OC277-29Start condition Coil frost protectionAuto Return OC277-30Auto vane control SwingRange a Range B Range C OC277-31Detecting abnormalities in the outdoor unit DRY operation DRY operation time chart How to operateOC277-32 OC277-33 Display in Heat operation Heat operation time chartOC277-34 Heat operationOverheat prevention OC277-35Overheat protection Booster heater controlDefrosting operation Indoor coil temperature abnormality detectionOC277-36 OC277-37 Initial mode How to operateMode change Temperature rangeAuto return OC277-38COOL/DRY operation Test run Before test run Timer operationTimer function OC277-39Before emergency operation OC277-40Emergency operation On indoor controller board Dip switch functionsOn remote controller board OC277-41PCH36, 42GK Fan motor max. rotational frequency Service RefOC277-42 PCH24GK PCH30GK PCH36GK PCH42GK SW7 OFFOC277-43 Trouble ShootingRemote Controller Display Abnormality Example Check Unit code address When malfunction occurs during operationFor group control using one remote controller OC277-44OC277-45 Heat Wrong Wiring on SiteOC277-46 CoolOther Troubles and Causes OC277-47PCH How to check the partsOC277-48 OC277-49 PAC-SA89TA-E System ControlOC277-50 Variety of System Control FunctionsOC277-51 Group Control with a Single Remote ControllerHow to wire How to set unit-addressRemote controller LCD indication Control Using TWO Remote ControllersRemote ON-OFF and Individual Remote Controls How to set SW17-7 See FigureOC277-53 Individual Control by Grouping the Remote ControllersBasic wiring Switch function of remote ON-OFF switchAuto Restart Function Multiple Remote Control DisplayTimer Operation or the Operation by AN External Signal OC277-54Removing the air intake grille Disassembly ProcedurePCH24GK Operating Procedure OC277-55Removing the side panel OC277-56Removing the fan motor Removing the sirocco fanRemoving the Indoor coil thermistor Operating Procedure PhotosOC277-57 Removing the vane motorRemove the intake grille OC277-58Removing the drain pan Removing the guide vaneRemoving the heat exchanger OC277-59Removing the support heater Structural Part PCH24GK Parts ListOC277-60 OC277-61 Structural Part PCH30GK PCH36GK PCH42GK OC277-62OC277-63 FAN and Heater Parts PCH24GK OC277-64FAN and Heater Parts PCH30GK PCH36GK PCH42GK OC277-65Electrical Parts PCH24GK10 PCH30GK PCH36GK PCH42GK OC277-66OC277-67 TimerOptional Parts SET Back Display PAC-SC32PTA Weekly Timer Setting DisplayOC277-68 Names and functionsRefrigerant Pipes Timer AdapterMultiple Remote Controller Adapter OC277-69Specifications are subject to change without notice