2-9 Dip switch functions

Each figure shows the initial factory setting.

(1). On remote controller board

1.SW17(Address selector)

12 3 4 5 6 7 8

ON

OFF

SW17-1~6) For address setting

SW17-7) When two remote controllers are used,this switch sets the controller function.

OFF:The remote controller is set as a main controller.

ON:The remote controller is set as a sub controller.

SW17-8) Switch for system back-up.

OFF:Without back-up

ON:With back-up

2.SW18(Function selector)

12 3 4 5 6 7 8

ON OFF

SW18-1) Switch for timer

OFF:Single day ON:timer every day

SW18-2) Switch for filter sign

OFF:filter sign absent

ON:filter sign present

SW18-3) Switch for filter sign time setting.

OFF:100Hr ON:2500Hr

SW18-4~8) Not for use.

(2). On indoor controller board

1. SW1 (Mode selector)

1 2 3 4 5 6 7 8 9 10

ON

OFF

SW1-1) Switch that changes between FAN mode and AUTO mode OFF:AUTO mode for models with heat pump

ON:Fan mode for models without heat pump SW1-2) Switch for drain pump

OFF:The drain pump works in COOL and DRY operation.

ON:The drain pump works in both COOL and DRY and HEAT operation. SW1-3) Switch to change the temperature to start coil frost prevention

OFF:34°F

ON:36°F

SW1-4) Switch for set temperature adjustment in HEAT mode

During HEAT operation,warm air collects near the ceiling.When the indoor unit is installed near the ceiling,the temperature read by room temperature thermistor differs from the actual living-space temperature by about 7 degrees. Therefore,the room temperature read by room temperature thermistor must be lowered by 7 degrees. OFF:7-degree adjustment

ON:NO adjustment

SW1-5) Switch for fan speed during thermostat OFF in HEAT operation

OFF:EXTRA LOW ON:LOW

SW1-6) Switch for fan speed during thermostat OFF in HEAT operation OFF:EXTRA LOW or LOW(set with SW1-5)

ON:LOW or HIGH(set with remote controller)

SW1-7) Switch for detecting abnormalities in the outdoor unit abnormality detection OFF:When an abnormality occurs,it is detected.

ON:Even if an abnormality occurs,it can not be detected. SW1-8) Switch for auto restart function

OFF:This function does not work ON:This function works.

SW1-9, 10) Not for use.

OC277-41

Image 41
Contents OC277-1 ContentsOC277-2 FeaturesImproving Efficiency of Piping Work Easy Maintenance no Maintenance Necessary for 2500 HoursOC277-3 OC277-4 Part Names and FunctionsOC277-5 Remote controller operation buttonsOC277-6 Remote controller displayModels PCH24GK, PCH30GK, PCH36GK, PCH42GK SpecificationsOC277-7 OC277-8 DataModels PCH24GK, PCH30GK, PCH36GK, PCH42GK Performance Data CFM SHC TPCCFM OC277-9Performance Curve OC277-10PCH36GK Cooling Capacity PCH36GK Heating Capacity OC277-11Condensing Pressure and Suction Pressure OC277-12PCH30GK OC277-13PCH36GK OC277-14PCH42GK OC277-15SHF PCH24GK PCH30GK PCH36GK PCH42GK OC277-16Standard Operation Data Operating Range OC277-17Outlet AIR Speed and Coverage Range Additional Refrigerant Charge R22ozNoise Criterion Curves PCH24GK OC277-18PCH30GK PCH36GK PCH42GKIndoor unit PCH24GK Outlines and DimensionsOC277-19 Indoor unit PCH30/36/42GK OC277-20Remote controller Refrigerant System DiagramOC277-21 PCH30GK PCH36GK PCH42GKOC277-22 Wiring DiagramModel PCH24/30/36/42GK Wiring Diagram Main Operation Operation FLOW-CHARTOC277-23 Cooling Operation OC277-24DRY Operation OC277-25DRY YESHeating Operation OC277-26Outline of Microprocessor Control Microprocessor ControlOC277-27 OC277-28 How to operateIndoor Unit Control Compressor controlStart condition OC277-29Coil frost protection Termination conditionsAuto vane control OC277-30Swing Auto ReturnRange a Range B Range C OC277-31Detecting abnormalities in the outdoor unit DRY operation DRY operation time chart How to operateOC277-32 OC277-33 OC277-34 Heat operation time chartHeat operation Display in Heat operationOverheat protection OC277-35Booster heater control Overheat preventionDefrosting operation Indoor coil temperature abnormality detectionOC277-36 Mode change Initial mode How to operateTemperature range OC277-37Auto return OC277-38COOL/DRY operation Timer function Timer operationOC277-39 Test run Before test runBefore emergency operation OC277-40Emergency operation On remote controller board Dip switch functionsOC277-41 On indoor controller boardOC277-42 Fan motor max. rotational frequency Service RefPCH24GK PCH30GK PCH36GK PCH42GK SW7 OFF PCH36, 42GKOC277-43 Trouble ShootingRemote Controller Display Abnormality For group control using one remote controller When malfunction occurs during operationOC277-44 Example Check Unit code addressOC277-45 OC277-46 Wrong Wiring on SiteCool HeatOther Troubles and Causes OC277-47PCH How to check the partsOC277-48 OC277-49 OC277-50 System ControlVariety of System Control Functions PAC-SA89TA-EHow to wire Group Control with a Single Remote ControllerHow to set unit-address OC277-51Remote ON-OFF and Individual Remote Controls Control Using TWO Remote ControllersHow to set SW17-7 See Figure Remote controller LCD indicationBasic wiring Individual Control by Grouping the Remote ControllersSwitch function of remote ON-OFF switch OC277-53Timer Operation or the Operation by AN External Signal Multiple Remote Control DisplayOC277-54 Auto Restart FunctionPCH24GK Operating Procedure Disassembly ProcedureOC277-55 Removing the air intake grilleRemoving the fan motor OC277-56Removing the sirocco fan Removing the side panelOC277-57 Operating Procedure PhotosRemoving the vane motor Removing the Indoor coil thermistorRemoving the drain pan OC277-58Removing the guide vane Remove the intake grilleRemoving the heat exchanger OC277-59Removing the support heater Structural Part PCH24GK Parts ListOC277-60 OC277-61 Structural Part PCH30GK PCH36GK PCH42GK OC277-62OC277-63 FAN and Heater Parts PCH24GK OC277-64FAN and Heater Parts PCH30GK PCH36GK PCH42GK OC277-65Electrical Parts PCH24GK10 PCH30GK PCH36GK PCH42GK OC277-66OC277-67 TimerOptional Parts OC277-68 PAC-SC32PTA Weekly Timer Setting DisplayNames and functions SET Back DisplayMultiple Remote Controller Adapter Timer AdapterOC277-69 Refrigerant PipesSpecifications are subject to change without notice