6. MULTIPLE REMOTE CONTROL DISPLAY

You can control several units with a multiple remote control display, by wiring an optional multiple display adapter (PAC-SA88HA-E) with relays and lamps on the market.

How to wire

(1)Connect the multiple display adapter to the connector CN51 on the indoor controller board.

(2)Wire three of the five wires from the multiple display adapter as shown in the figure below.

<Wiring >

 

 

X2

GL

 

 

 

GREEN

 

5

 

 

 

 

X2

 

 

 

 

 

 

 

CN51

 

YELLOW

X1

RL

Power

 

X1

 

 

 

 

supply

1

 

ORANGE

 

 

 

 

 

 

connector(5P)

RED

 

 

 

 

 

 

 

 

 

 

BROWN Electrical insulation is needed.

 

 

 

Optional multiple display

Wiring at the actual place

 

 

adapter

 

 

 

 

The maximum distance between indoor board and relay is 33ft.

<System>

Power3wires

supply3wires 3wires

2wires

No.1 unit

No.2 unit

No.3 unit

 

 

 

 

Remote

Relay box

 

 

controller

(Field supply)

 

 

cable

 

 

Multiple remote contr

o

l

 

 

 

 

 

 

 

 

 

Remote

Remote

Remote

ON-OFF display

 

 

 

(Field supply)

controller

controller

controller

 

 

 

 

 

 

 

 

 

 

(Operation check)

 

 

 

 

 

 

 

 

 

Indoor controller board

CN51

CN51

[Notes on Signs]

X1:Relay (for operation lamp) X2:Relay (for check lamp) RL:Operation Lamp GL:Check Lamp

[Field supplied parts]

Relays:12V DC with rated coil power consumption below 0.9W.

Lamps:Matching to power supply voltage.

<Wiring diagram>

 

 

 

 

 

 

RL-1

X1-1

 

 

Multiple remote

 

 

 

 

Power

GL-1

X2-1

X1-1

1

controller adapter

supply

 

 

 

 

 

 

 

 

X2-1

5

No.1 unit

 

 

 

 

 

 

RL-2

X1-2

 

 

 

 

 

 

 

 

 

GL-2

X2-2

X1-2

1

 

 

 

 

 

 

 

X2-2

 

No.2 unit

 

 

 

5

 

 

 

X1-3

 

 

 

RL-3

 

 

 

 

 

 

 

 

 

GL-3

X2-3

X1-3

1

No.3 unit

 

 

 

 

 

 

 

 

 

 

X2-3

5

connect to

 

 

 

 

 

the connector CN51

Multiple Remote Control Display

 

Relay box

 

 

7. AUTO RESTART FUNCTION

By setting the dip switch SW1-8 to ON, the air conditioner can be started/stopped by power supply ON/OFF. If the air conditioner is OFF before the power failure, it will not start operation by power restore.

•This function is mainly to emergency performance when the power supply stops temporarily. Therefore, since the protec- tion function (for example, clank case heater and prevention from restarting in 3 minutes, etc.) of the device is not operat- ed, this function should not be used mostly.

8. TIMER OPERATION OR THE OPERATION BY AN EXTERNAL SIGNAL

<Wiring>

 

A : an optional timer adapter

A

 

B : a single-throw switch

 

A

B

 

B

Brown

 

Brown

 

Red

Red

 

Orange Remote controller

Orange Remote controller

 

For remote control, connect the optional timer adapter (PAC-SA89TA-E)

OC277-54

Image 54
Contents Contents OC277-1Features OC277-2Easy Maintenance no Maintenance Necessary for 2500 Hours OC277-3Improving Efficiency of Piping Work Part Names and Functions OC277-4Remote controller operation buttons OC277-5Remote controller display OC277-6Specifications OC277-7Models PCH24GK, PCH30GK, PCH36GK, PCH42GK Models PCH24GK, PCH30GK, PCH36GK, PCH42GK Performance Data DataOC277-8 CFM SHC TPCOC277-9 CFMOC277-10 Performance CurveOC277-11 PCH36GK Cooling Capacity PCH36GK Heating CapacityOC277-12 Condensing Pressure and Suction PressureOC277-13 PCH30GKOC277-14 PCH36GKOC277-15 PCH42GKOC277-16 Standard Operation DataSHF PCH24GK PCH30GK PCH36GK PCH42GK Outlet AIR Speed and Coverage Range OC277-17Operating Range Additional Refrigerant Charge R22ozPCH30GK OC277-18Noise Criterion Curves PCH24GK PCH36GK PCH42GKOutlines and Dimensions OC277-19Indoor unit PCH24GK OC277-20 Indoor unit PCH30/36/42GKOC277-21 Refrigerant System DiagramRemote controller PCH30GK PCH36GK PCH42GKWiring Diagram Model PCH24/30/36/42GK Wiring DiagramOC277-22 Operation FLOW-CHART OC277-23Main Operation OC277-24 Cooling OperationDRY OC277-25DRY Operation YESOC277-26 Heating OperationMicroprocessor Control OC277-27Outline of Microprocessor Control Indoor Unit Control How to operateOC277-28 Compressor controlCoil frost protection OC277-29Start condition Termination conditionsSwing OC277-30Auto vane control Auto ReturnOC277-31 Detecting abnormalities in the outdoor unitRange a Range B Range C DRY operation time chart How to operate OC277-32DRY operation OC277-33 Heat operation Heat operation time chartOC277-34 Display in Heat operationBooster heater control OC277-35Overheat protection Overheat preventionIndoor coil temperature abnormality detection OC277-36Defrosting operation Temperature range Initial mode How to operateMode change OC277-37OC277-38 COOL/DRY operationAuto return OC277-39 Timer operationTimer function Test run Before test runOC277-40 Emergency operationBefore emergency operation OC277-41 Dip switch functionsOn remote controller board On indoor controller boardPCH24GK PCH30GK PCH36GK PCH42GK SW7 OFF Fan motor max. rotational frequency Service RefOC277-42 PCH36, 42GKTrouble Shooting Remote Controller Display AbnormalityOC277-43 OC277-44 When malfunction occurs during operationFor group control using one remote controller Example Check Unit code addressOC277-45 Cool Wrong Wiring on SiteOC277-46 HeatOC277-47 Other Troubles and CausesHow to check the parts OC277-48PCH OC277-49 Variety of System Control Functions System ControlOC277-50 PAC-SA89TA-EHow to set unit-address Group Control with a Single Remote ControllerHow to wire OC277-51How to set SW17-7 See Figure Control Using TWO Remote ControllersRemote ON-OFF and Individual Remote Controls Remote controller LCD indicationSwitch function of remote ON-OFF switch Individual Control by Grouping the Remote ControllersBasic wiring OC277-53OC277-54 Multiple Remote Control DisplayTimer Operation or the Operation by AN External Signal Auto Restart FunctionOC277-55 Disassembly ProcedurePCH24GK Operating Procedure Removing the air intake grilleRemoving the sirocco fan OC277-56Removing the fan motor Removing the side panelRemoving the vane motor Operating Procedure PhotosOC277-57 Removing the Indoor coil thermistorRemoving the guide vane OC277-58Removing the drain pan Remove the intake grilleOC277-59 Removing the support heaterRemoving the heat exchanger Parts List OC277-60Structural Part PCH24GK OC277-61 OC277-62 Structural Part PCH30GK PCH36GK PCH42GKOC277-63 OC277-64 FAN and Heater Parts PCH24GKOC277-65 FAN and Heater Parts PCH30GK PCH36GK PCH42GKOC277-66 Electrical Parts PCH24GK10 PCH30GK PCH36GK PCH42GKTimer Optional PartsOC277-67 Names and functions PAC-SC32PTA Weekly Timer Setting DisplayOC277-68 SET Back DisplayOC277-69 Timer AdapterMultiple Remote Controller Adapter Refrigerant PipesSpecifications are subject to change without notice