S I G 4 0 0
MAIN OVEN | Natural Gas | L.P.Gas |
Heat Input | 2.4kW (8189Btu/h) | 2.4kW (172.4 g/h) |
Injector Marking | 108 | 078 |
Flame Supervision Device | Diamond'H' GSD 213 | Diamond 'H' GSD 214 |
Thermostat | Diamond'H' | Diamond 'H' |
Thermostat | 69 | 78 |
SECOND OVEN | Natural Gas | L.P.Gas |
Heat Input | 2.4kW (8189 Btu/h) | 2.4kW (172.4 g/h) |
Injector Marking | 108 | 078 |
Flame Supervision Device | Diamond 'H' GSD 100/31 | Diamond 'H' GSD 100/34 |
Dual Control | Sourdillon 60112/982 | Sourdillon 60525/952 |
Dual Control | 0.53kW (1808 Btu/h) | 0.62kW (445 g/h) |
GENERAL |
|
|
Ignition | H. T. Spark |
|
Spark Gap |
|
IMPORTANT - SAFETY REQUIREMENTS
This appliance must be installed in accordance with the Gas Safety (Installation and Use) Regulations Current Editions and the I.E.E. Wiring Regulations. Detailed recommendations are contained in the following British Standard Codes of Practice - BS.6172, BS.5440: Part 2 and B.S.6891. All British Standards must be 'Current Editions'.
PROVISION FOR VENTILATION
This appliance is not connected to a combustion products evacuation device. It shall be installed and connected in accordance with the current installation regulations. Particular attention shall be given to the relevant requirements regarding ventilation.
The room containing the appliance should have an air supply in accordance with BS. 5440: Part 2 Current Edition. All rooms require an openable window or equivalent and some rooms will require a permanent vent as well. For room volumes up to 5m³ an air vent of 100cm² is required: for room volumes between 5m³ and 10m³ an air vent of 50cm² is required. If the room has a door that opens directly to the outside, no air vent is required. For room volumes that exceed 11m³ no air vent is required. If there are other fuel burning appliances in the same room, BS.5440: Part 2 Current Edition should be consulted to determine the requisite air vent requirements.
Prolonged intensive use of the appliance may call for additional ventilation, for example opening a window, or more effective ventilation, for example increasing the level of mechanical ventilation where present.
42