Emerson 2700, 1700 installation manual Digital communication, Service port, HART/Bell202

Page 65

Specifications

Model 2700 transmitters with non-incendive FOUNDATION fieldbus outputs option board (output option code N)

One FOUNDATION fieldbus H1 output:

-FOUNDATION fieldbus wiring is non-incendive

-Manchester-encoded digital signal conforms to IEC 1158-2

Model 2700 transmitters with PROFIBUS-PA outputs option board (output option code G)

One PROFIBUS-PA output:

-PROFIBUS-PA wiring is intrinsically safe with an intrinsically safe PROFIBUS-PA network power supply

-Manchester-encoded digital signal conforms to IEC 1158-2

A.1.3 Digital communication

Model 1700/2700 transmitters support the following digital communications:

Service port

One service port can be used for temporary connection only

Address 111

Uses RS-485 Modbus RTU signal, 38.4 kilobaud, one stop bit, no parity

HART/Bell202

A HART/Bell202 signal can be superimposed on the primary mA output and used for interface with a host system:

Frequency: 1.2 and 2.2 kHz

Amplitude: 0.8 mA peak-to-peak

1200 baud

Requires 250 to 600 Ohms load resistance

HART/RS485 or Modbus/RS485 (transmitters with analog outputs option board only)

One pair of terminals provides RS-485 communications:

Can be used for direct connection to a HART or Modbus host system

Accepts baud rates between 1200 baud and 38.4 kilobaud

FOUNDATION fieldbus or PROFIBUS-PA transmitters

One pair of terminals provides FOUNDATION fieldbus or PROFIBUS-PA communications:

Resource, transducer, and function blocks per FOUNDATION or PROFIBUS specification

Output Wiring – Intrinsically Safe

Output Wiring – Configurable I/O Output Wiring – Fieldbus/PROFIBUS

Specifications

Installation Manual

61

Image 65
Contents Micro Motion Model 1700 Model 2700 Transmitters Page Contents Index Overview SafetyBefore You Begin Flowmeter components Flowmeter documentation 1Flowmeter documentation resources Transmitter installation proceduresMicro Motion customer service Installation architecture Installing the Transmitter1Installation types Power source Temperature limitsAC power requirements Determining an appropriate location1Typical power cable resistances at 68 F 20 C DC power requirementsMaximum cable lengths Accessibility for maintenance2Maximum cable lengths Mounting the transmitter2Rotating the transmitter Integral installations34-wire remote Wall mount or pipe mount 59-wire remote Wall mount or pipe mount 3 9-wire remote installationsMounting the remote core processor 6Transmitter/core processor assembly Exploded view7Remote core processor Wall mount or pipe mount 3Grounding methods for flowmeter components Grounding the flowmeter componentsRotating the display Supplying powerInstalling the Transmitter 10Display components Cable types Wiring the Transmitter to the SensorWiring for 4-wire remote installations 1 4-wire cable2 9-wire cable 3Wiring to the mating connector Core processor on transmitter Wiring for 9-wire remote installationsSubtask 1 Wire the remote core processor to the transmitter 5Cable glands 7Wrapping the shield drain wires 10Gland body and core processor housing 129-wire cable between sensor and core processor Subtask 2 Wiring the sensor to the remote core processorWiring the Transmitter to the Sensor Output wiring Output Wiring Model 1700/2700 Analog TransmittersOutput terminals and output types 1Terminals and output types1Basic analog wiring 2HART/analog single-loop wiring Smart Family Output Wiring Intrinsically Safe Safe area mA output wiring Safe area output wiring2Safe area mA output load resistance values 5Safe area frequency/discrete output wiring Safe area frequency/discrete output wiringHazardous area safety parameters Hazardous area output wiringHazardous area voltage 2Safety parametersHazardous area current Hazardous area capacitanceHazardous area frequency/discrete output wiring Hazardous area mA output wiringHazardous area Channel configuration Output Wiring Model 2700 Configurable I/O TransmittersMA output wiring 1Channel configuration2Basic mA wiring Frequency output wiring 5Frequency output Terminals 3 & 4 Channel B Internal power 7Frequency output Terminals 5 & 6 Channel C Internal power 9Discrete output 1 Terminals 3 & 4 Channel B Internal power Discrete output wiring11Discrete output 2 Terminals 5 & 6 Channel C Internal power Volts Voltage Output Level High 2Input voltage ranges for external power Discrete input wiring16Discrete input Terminals 5 & 6 Channel C Internal power Micro Motion Model 1700 and 2700 Transmitters 1Connecting the fieldbus communication wires Foundation fieldbus wiring2Connecting the PROFIBUS-PA communication wires PROFIBUS-PA wiringFunctional specifications SpecificationsPower connection Service port connectionFisco and Fnico approval Input/output signals Input signal from sensorCore processor connection Specifications Operating Absolute minimum = 100 Ohms for V supply 25.6 volts Specifications Digital communication Service portHART/Bell202 Foundation fieldbus or PROFIBUS-PA transmittersEnvironmental requirements Ambient temperature limits Power supplyAmbient temperature effect EMC complianceTransmitter UL and CSAOutputs Atex and IECExPhysical specifications Performance specificationsHousing MountingInterface/display WeightDimensions Dimensions in inchesmm Inches Dimensions in mm Or M20 × 11/16 160 13/16 139 ″-14 NPT 158 182 × Ø3/8 13/16 148 15/16 × 1/2″-14 NPT Figure A-5Dimensions Remote core processor Atex IndexRemote core processor with remote Index Micro Motion Model 1700 and 2700 Transmitters Page 20001700