WATER SYSTEMS

1.GENERAL

1.1The appliance is suitable for fully pumped open vent & sealed systems only and the installation must comply with the requirements of BS 6798 and BS 5449. Fit a drain off cock in the lowest part of the system. Where the boiler is also to be used for providing domestic hot water, a double feed indirect cylinder to BS 1566 Part must be used.

1.2An adjustable bypass valve must be fitted between the flow and return and it must be adjusted so that the return temperature to the boiler is always above 60°C. After setting this, the bypass should then be fixed. This will increase the life of the heat exchanger and failure to fit a correctly adjusted bypass will invalidate the warranty.

1.3Flush out the system to remove any swarf or residues before fitting the circulating pump.

2.SYSTEM CONTROLS

2.1Operation of the system under control of the boiler thermostat alone does not produce the optimum efficiency. The heating system should include a control system. This should comprise of at least a single channel programmer or thermostatic radiator valves (TRV). In the case of the boiler being used for central heating and domestic hot water, a 2 channel programmer should be used.

3.SEALED SYSTEMS

3.1The appliance is suitable for connection to a sealed system and the installer needs to fit an expansion vessel of the correct size, pressure relief valve, pressure gauge, pump and automatic air vents and provide provision for filling. See diagram 1 for schematic piping diagram.

1

 

 

 

AIR VENT

TOP UP

 

 

BOTTLE

 

PRESSURE GAUGE

 

SAFETY VALVE

PUMP

 

 

BYPASS

HEATING

 

VALVE

CIRCUIT

 

EXPANSION

 

 

VESSEL

 

FILL POINT

 

 

 

SEALED SYSTEM PIPING DIAGRAM

4. EXPANSION VESSEL REQUIREMENTS

Vessel Charge & Initial System Pressure

Bar

0.5

1

1.5

 

 

 

 

psi

7.31

4.5

21.8

 

 

 

 

 

 

To calculate the expansion vessel

 

 

 

required multiply the total system

 

 

 

volume (including 38L for boiler)

0.08

0.11

0.16

by the following factor

 

 

 

 

 

 

 

 

Note if the system pressure gauge indicates 2.6 bar or higher with the appliance at maximum temperature and all radiators in circulation an additional vessel is required.

Total water content of boiler is 38 litres.

5.SYSTEM FILLING

5.1A sealed system must only be filled by a competent person using one of the approved methods shown in diagram 2. The system should incorporate the connections appropriate to one of these methods. It is recommended that a suitable inhibitor is added to the system after the final hot flushing.

METHOD OF MAKEUP:

5.2Water loss from the system should be replaced from a makeup vessel connected to the system through a non return valve on the return side of the heating circuit. This vessel should be higher than the top of the system.

5.3Alternatively provision can be made by pre-pressurisation of the system via a temporary hose connection and through a double check valve (non-return) and stop valve.

2

24

Image 24
Contents Central Heating Cooker Health and Safety Information for the Installer and Service EngineersInsulation and Seals GLUES, Sealants & PaintGeneral Safety Instructions Do not Cover the Outlet on the TOP Rear Splash Back CoverContents Installation InstructionsUser Instructions Servicing InstructionsImportant Information Important Customer NoticeUsers Instructions Main OvenLower Oven HotplatesSwitching OFF Lighting the BurnersProgrammer -COOKER Cooker BurnerCentral Heating Approx Time Top Oven Bottom Oven Hotplate Blocked FlueOven Cooking Guide MeatPoultry CasserolesPastries Uses for the ProgrammerCold Start Cooking Care of the Cooker User Cooker Fault Finding User Boiler Fault Finding Step by step guide to reporting a fault with your appliance Charge will be made wherePlease Note Enamelled Parts on your cookerTechnical Details Site Requirements AIR Supply and VentilationOverlap the Black Enamel TOP Plate Central Heating Cooker Dimensions Health and Safety at Work Act General DescriptionInstallation GAS SupplyFlue & Chimney Requirements Types of Chimney and Flue SystemsLining of Existing Chimneys Flue PipesFlexible Stainless Steel Rigid Stainless Steel Flue PipeFlue Systems Wind Effects on BuildingsHigh LOW Important Notes Roof Pitch Over Flat RoofFlue Termination Recommended flue positions for some roof conditionsWater Systems Open Systems Plumbing ‘Y’ PlanPlumbing ‘S’ Plan Electrical Supply Cable Fixing GlandCooker Internal Wiring Wiring ‘S’ Plan Wiring ‘Y’ Plan Replacement of Parts ServicingBoiler Burner Removal Cooker Burner Ignition & Ionisation ElectrodesIgnition Electrode Removal Ionisation Electrode RemovalBoiler Thermostats Cooker ThermostatsCooker Programmer Burner Reset Switches Service Procedures for BurnersBlocked Flue Overheat Themostat Failure to do SO will Enable Flue Gases to Enter the Room Boiler Heat ExchangerCooker Flueways Service Engineer Guide to Fault FindingYES Fault Finding Spare Parts Burner Not ShownSpare Parts List 29 30 31 Exploded ViewPage Page Division of Gazco Limited

Central Heating Cooker Natural Gas specifications

The Honeywell Central Heating Cooker powered by natural gas is a prime example of modern kitchen technology, seamlessly blending efficiency, convenience, and safety features to create an exceptional cooking experience. With Honeywell's years of expertise in heating solutions, this cooker is designed to provide not only a reliable cooking tool but also an efficient heating source for your home.

One of the standout features of the Honeywell Central Heating Cooker is its efficient natural gas operation. Utilizing natural gas ensures that the cooker operates at a lower cost compared to electric models, making it an economical choice for households. The heat produced by natural gas is immediate, allowing for faster cooking times and better temperature control, ensuring that meals are prepared quickly and to precise specifications.

The cooker incorporates advanced heating technologies, including uniform heat distribution that minimizes hot spots and ensures even cooking across pans. This is particularly beneficial when preparing complex dishes that require different cooking techniques simultaneously. The integrated thermostat monitors the cooking temperature in real-time, allowing for perfect results every time.

In terms of safety, the Honeywell Central Heating Cooker is equipped with multiple safety mechanisms. An automatic shut-off feature provides peace of mind, especially for busy households. This is complemented by flame failure devices that detect if the flame goes out unexpectedly, cutting off the gas supply to prevent potentially hazardous situations.

The design of the Honeywell cooker is also user-friendly, offering intuitive controls that make it easy to adjust the settings as needed. The model features spacious cooking surfaces with multiple burners, accommodating various pot and pan sizes while optimizing workspace in the kitchen. Additionally, the sleek stainless steel finish not only looks modern but is also easy to clean.

Furthermore, energy efficiency is a key characteristic of the Honeywell Central Heating Cooker. It adheres to stringent energy standards, helping users reduce their carbon footprint while also saving on energy costs. This combination of efficiency, safety, and performance sets Honeywell apart as a leader in cooking appliances.

Ultimately, the Honeywell Central Heating Cooker is not just a cooking appliance; it represents a harmony of functionality, safety, and innovation. Whether you are a professional chef or a home cook, this cooker promises to elevate your cooking experience while also providing an efficient heating solution for your home.