Main Flame will not | Flame Monitor | (There should be a visible main flame at this time.) |
stay lit |
| To check for flame monitor operation, connect a |
|
| digital volt meter (capable of measuring D.C. micro |
|
| amperes) between the flame sensor and terminal |
|
| #15 on the flame monitor. The flame monitor |
|
| requires a minimum of 4 micro amp. D.C. for proof |
|
| of flame. If these readings are not achieved, |
|
| replace sensor assembly. Also check for any type |
|
| of damage to flame sensor wire and connections. |
|
| If the reading is above the minimum required, and |
|
| the flame monitor will not supply 220 VAC to the |
|
| relay coil, replace the flame monitor. |
Intermittent Heating | As Follows | Both the main fan motor and burner blower motor |
|
| are equipped with thermal protection and will cease |
|
| to operate if overheating occurs. This can cause |
|
| the units to cycle on and of intermittently. This may |
|
| be caused by improper ventilation. Also, most of |
|
| the problems listed under "oven will not heat" can |
|
| cause intermittent failure. |
Conveyor will not run | Conveyor Switch | Check for 120 VAC to conveyor switch. If no |
|
| voltage is present, trace wiring back to the power |
|
| supply. WITH POWER OFF: Check continuity |
|
| between switch terminals |
| Conveyor Fuse(3A) | Check, replace if necessary. |
| Fuseholder | Check, replace if necessary. |
| Conveyor Control | Check for 120 VAC supply to primary (Stepper) |
|
| Transformer of transformer, if voltage is not |
|
| present, trace wiring back to the fuseholder. If |
|
| voltage is present, check for output voltage from |
|
| the transformer secondary. NOTE: this control |
|
| transformer outputs (2) secondary voltages: Red |
|
| Leads 29 VAC Brown Leads 10 VAC. If BOTH |
|
| secondary voltages are not present, replace the |
|
| transformer. |
| Speed Adjustment | This is a 0 to 50K ohm, 10 turn potentiometer. |
| Potentiometer | WITH POWER OFF: remove the 3 pin |
|
| potentiometer cable plug from the motor control |
|
| board. With a digital multimeter, check the ohm |
|
| reading across the red lead to the black lead, this |
|
| reading should be 50K ohms ± 5% as the |
|
| potentiometer is rotated through its 10 turn rotation. |
|
| Place the meter leads on the red lead and white |
|
| lead. Rotating the potentiometer slowly, from low to |
|
| high, the meter should show an even transition |
|
| from 0 to 50K ohms ± 5% through the 10 turn |
|
| rotation of the potentiometer. There should be no |
|
| dead or open spots through the 10 turns of the |
|
| potentiometer. Check all three leads to ground. |
|
| There should be no continuity to ground. If any of |
|
| the above checks fail, replace the potentiometer. |
| Conveyor Motor(Stepper) | NOTE: if the conveyor drive motor becomes |
| Control | jammed or begins to run at an uncontrolled speed, |
|
| the conveyor motor will stop running. To reset, turn |
|
| off the conveyor switch, wait 30 seconds, turn the |
|
| conveyor switch on. If the motor does not run after |
|
| attempting |
|
| motor terminals 1 to 2 and 3 to 5 on, the conveyor |
|
| motor control. If voltage is not present at both sets |
|
| of terminals, replace control. |
50 | Impinger I |