Lennox International Inc GWB9-100IH-2, GWB9-075IH-2, GWB9-050IH-2 installation instructions Start UP

Page 37

START UP

Water Quality, Water Treatment and Freeze Protection - see Appendix A

Filling Boiler With Water And Purging Air For Systems With Diaphragm Type Expansion Tanks

Refer to the appropriate diagrams,“Near Boiler Piping” on page 11 for more information.

1.Close all zone service valves on the supply and return piping. Open the feed valve and fill boiler with water. Make sure air vent is open. Hold relief valve open until water runs air free for five seconds to rapidly bleed air from boiler, then let the relief valve snap shut.

2.Open the zone service valve on the supply pipe for the first zone. Open the purge valve on the first zone. Feed water will fill the zone, pushing air out the purge valve. Close the purge valve when the water runs air free.

Close the zone service valve.

3.Repeat step 2 for all remaining zones.

4.Open all service valves. Any air remaining trapped in the return lines between the service valves and the boiler will be pushed towards the air vent when the boiler is placed in operation.

5.Inspect piping system. Repair any leaks immediately.

Purging Air For Systems With Conventional Closed Type Expansion Tanks:

Refer to the appropriate diagrams“Near Boiler Piping” on page 11 for more information.

1.Close all zone service valves on the supply and return piping and close the expansion tank service valve. Drain expansion tank. Open the feed valve and fill boiler with water. Hold relief valve open until water runs air free for five seconds to rapidly bleed air from boiler, then let the relief valve snap shut.

2.Open the zone service valve on the supply pipe for the first zone. Open the purge valve on the first zone. Feed water will fill the zone, pushing air out the purge valve. Close the purge valve when the water runs air free.

Close the zone service valve.

3.Repeat step 2 for all remaining zones.

4.Open the expansion tank service valve and the tank vent. Fill the tank to the proper level and close the tank vent. Remove the handle from the expansion tank service valve so the homeowner doesn’t accidentally close it.

5.Open all service valves. Any air remaining trapped in the return lines between the service valves and the boiler will be pushed towards the expansion tank when the boiler is placed in operation.

6.Inspect piping system. Repair any leaks immediately.

37

Image 37
Contents Installation Instructions Boiler Dimensions Introduction IntroductionGeneral Important Safety InformationNet Ahri Rating Shipping Flue Diameter SEA Level Ratings Natural and Propane Gases90 50/75/100 Series 2 Natural GAS Boilers for USE AT High Altitude United States Installations43331093 43331096 90 50/75 Series 2 Propane GASBoiler Sizing Before Installing the BoilerBoiler Location Considerations Locating The Boiler Boiler InstallationCombustion Air And Vent Pipe Requirements Extreme cold climate areas, use ¾ Armaflex or equivalentBoiler is not to be installed on carpeting Install boiler on level surfaceCondensate Drain Requirements Foundation RequirementsNear Boiler Piping Clean the System FirstSupply And Return Lines Single Zone Boiler Piping Two Zone Boiler Piping With Zone Valves Multi-Zone SystemsTwo Zone Boiler Piping With Circulators Page Page Page Expansion Tank And Make-Up Water Safety Relief ValveTerminate pipe with plain end not threaded Diaphragm Type Expansion Tank Piping Conventional Closed Type Expansion Tank Piping Condensate Drain Piping Reinstall vent drain lineFilling Condensate Trap With Water Chilled Water PipingConnections And Termination Combustion AIR and Vent PipeExample Elbow @ 3 ft. + 1 elbow @ 3 ft. = 6 equivalent ft. of pipeBoiler Size InstallationRoof Vent / Intake Terminations Vent AIR IntakeLess Than 12 Clearance CombustionVent Air Concentric Vent TerminationsFeet minimum total equivalent length for all models Combustion Air and Vent Piping Boiler ConnectionsGAS Supply Piping Connecting The Gas PipingCheck Gas Supply Leak Check Gas Piping625,000 Gas Pipe Sizes445,000 365,000Electric Power Supply Electrical WiringThermostat Installation Connect Circulator Pump WiringWiring Schematic Ladder Wiring Diagram Page Ladder Diagram for Figure Controls and Accessories Drain Valve Casting Temperature Safety SwitchDraft Inducer Circulator PumpStart UP To Turn Off Gas To Appliance Operating InstructionsUser Parameters Adjusting Settings S9381A Integrated Boiler Control Operation and AdjustmentsDisplay State Code Definitions Sequence of Operation Check OUT Procedure and Adjustment Review All Instructions Set Thermostat To Desired Room TemperatureVR8205 Maintenance and Cleaning Igniter wires Gas valve wires Annual Examination And Cleaning Of Boiler ComponentsRemove draft inducer and gasket from top of flue connector Initial Service Checks TroubleshootingError Codes Boiler Differential Pressure Differential AIR Pressure Switch CheckAluminum Series Fill Water and Chemistry Clean System FirstEliminate System Leaks General Guidelines When Using Antifreeze Antifreeze Products Boiler Model Serial # Date Installed Measured BTU/HR input Installation and CHECK-OUT CertificatePage Lennox Industries Inc. Dallas, Texas
Related manuals
Manual 32 pages 41.03 Kb