10.REMOVAL AND REPLACEMENT OF CONDENSING PRESSURE REGULATOR (C.P.R.) - REMOTE AIR-COOLED MODEL ONLY

IMPORTANT

Always install a new Drier every time the sealed refrigeration system is opened. Do not replace the Drier until after all other repair or replacement has been made.

1)Turn off the power supply.

2)Remove the panels from the remote condenser unit.

3)Recover the refrigerant and store it in an approved container.

4)Before heating, break off the stub on the dome to release the dome charge.

5)Disconnect the C.P.R. using brazing equipment.

6)Install the new C.P.R. Use nitrogen gas at the pressure of 3 - 4 PSIG when brazing the C.P.R.

CAUTION

Always protect the C.P.R. body by using a damp cloth to prevent the C.P.R. from overheating. Do not braze with the C.P.R. body exceeding 250°F.

7)Install the new Drier in the icemaker.

8)Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.

9)Evacuate the system and charge it with refrigerant. See the Charge Label in the machine compartment in the icemaker.

10)Replace the panels in their correct positions.

11)Turn on the power supply.

51

Image 51
Contents KM-1300MAH KM-1300MWH KM-1300MRH Hoshizaki AMERICA, INC Contents Maintenance KM-1300MAH Air-cooled Specifications2a. KM-1300MWH Water-cooled 2b. KM-1300MWH Water-cooled Serial No. M10156D KM-1300MRH Remote air-cooled Condensing Unit URC-12F Specifications Model URC-12F II. General Information Construction KM-1300MWH Water-cooled KM-1300MRH Remote air-cooled Controller Board Features of Control Products E Controller BoardController Board SOLID-STATE ControlPage Freeze Cycle Beep every 3 sec. = High Evaporator Temperature 127 FMinute Fill Cycle Harvest CycleControl Products HOS-001A Board Sequence 1st Cycle 2nd Cycle and after with pump drain 2nd Cycle and after with no pump drain Controls and Adjustments Setting Time Setting Frequency Checking the Controller Board Page III. Technical Information KM-1300MWH Water-cooled KM-1300MRH Remote air-cooled KM-1300MAH Air-cooled and KM-1300MWH Water-cooled Wiring DiagramsCut-out 412 ±21.3 Psig Cut-in 327±21.3 Psig Timing Chart Page Performance Data Serial # L00001F to M10155C KM-1300MWH Water-cooled Serial # M10156D KM-1300MRH Remote air-cooled Problem Possible Cause Remedy IV. Service Diagnosis No ICE ProductionController Board Problem Possible Cause Remedy LOW ICE Production Evaporator is Frozen UPOthers Abnormal ICEService for Refrigerant Lines Refrigerant RecoveryEvacuation and Recharge R-404A Brazing Removal and Replacement of Compressor Important Removal and Replacement of Drier Removal and Replacement of Expansion Valve Removal and Replacement of HOT GAS Valve and Line Valve Removal and Replacement of Evaporator Important Page Page Page Removal and Replacement of Thermistor Important Removal and Replacement of FAN Motor Removal and Replacement of Pump Motor Removal and Replacement of Water ValveRemoval and Replacement of Spray Tubes Preparing the Icemaker for Long Storage VI. Maintenance and Cleaning InstructionsPage Cleaning Cleaning Procedure Sanitizing Procedure Following Cleaning Procedure Page Maintenance