VI. MAINTENANCE AND CLEANING INSTRUCTIONS

IMPORTANT

Ensure all components, fasteners and thumbscrews are securely in place after any maintenance or cleaning is done to the equipment.

1. PREPARING THE ICEMAKER FOR LONG STORAGE

IMPORTANT

When shutting off the icemaker for an extended time, drain out all water from the water tank and remove the ice from the Storage Bin. The Storage Bin should be cleaned and dried. Drain the icemaker to prevent damage to the water supply line at sub-freezing temperatures, using air or carbon dioxide. Shut off the icemaker until the proper ambient temperature is resumed.

When the icemaker is not used for two or three days, it is sufficient to move the Con- trol Switch to the “OFF” position, unless the icemaker will be at sub-freezing tempera- tures.

[1]On water-cooled model only, first remove the water from the water-cooled condenser:

1)Remove the Front Panel.

2)Move the Control Switch, on the Control Box, to the “OFF” position.

3)Wait 3 minutes.

4)Move the Control Switch to the “ICE” position.

5)Allow 5 minutes for the icemaker to fill with water and the Water Pump to start operating.

6)Close the Water-cooled Condenser Water Supply Line Shut-off Valve.

7)Open the Drain Valve for the water-cooled condenser water supply line.

8)Allow the line to drain by gravity.

9)Attach compressed air or carbon dioxide supply to the Condenser Water Line Drain Valve.

10)Quickly blow the water-cooled condenser out using compressed air or carbon dioxide until water stops coming out.

56

Image 56
Contents KM-1300MAH KM-1300MWH KM-1300MRH Hoshizaki AMERICA, INC Contents Maintenance Specifications KM-1300MAH Air-cooled2a. KM-1300MWH Water-cooled 2b. KM-1300MWH Water-cooled Serial No. M10156D KM-1300MRH Remote air-cooled Condensing Unit URC-12F Specifications Model URC-12F II. General Information Construction KM-1300MWH Water-cooled KM-1300MRH Remote air-cooled Features of Control Products E Controller Board Controller BoardSOLID-STATE Control Controller BoardPage Beep every 3 sec. = High Evaporator Temperature 127 F Minute Fill CycleHarvest Cycle Freeze CycleControl Products HOS-001A Board Sequence 1st Cycle 2nd Cycle and after with pump drain 2nd Cycle and after with no pump drain Controls and Adjustments Setting Time Setting Frequency Checking the Controller Board Page III. Technical Information KM-1300MWH Water-cooled KM-1300MRH Remote air-cooled Wiring Diagrams KM-1300MAH Air-cooled and KM-1300MWH Water-cooledCut-out 412 ±21.3 Psig Cut-in 327±21.3 Psig Timing Chart Page Performance Data Serial # L00001F to M10155C KM-1300MWH Water-cooled Serial # M10156D KM-1300MRH Remote air-cooled IV. Service Diagnosis No ICE Production Problem Possible Cause RemedyController Board Problem Possible Cause Remedy Evaporator is Frozen UP LOW ICE ProductionAbnormal ICE OthersEvacuation and Recharge R-404A Service for Refrigerant LinesRefrigerant Recovery Brazing Removal and Replacement of Compressor Important Removal and Replacement of Drier Removal and Replacement of Expansion Valve Removal and Replacement of HOT GAS Valve and Line Valve Removal and Replacement of Evaporator Important Page Page Page Removal and Replacement of Thermistor Important Removal and Replacement of FAN Motor Removal and Replacement of Water Valve Removal and Replacement of Pump MotorRemoval and Replacement of Spray Tubes VI. Maintenance and Cleaning Instructions Preparing the Icemaker for Long StoragePage Cleaning Cleaning Procedure Sanitizing Procedure Following Cleaning Procedure Page Maintenance