Hoshizaki KM-1300MRH, KM-1300MWH, KM-1300MAH service manual Setting Frequency

Page 23

3) Drain Timer

The Drain Timer is factory-adjusted, and no adjustment is required.

SETTING

 

TIME

Dip Switch

Dip Switch

 

 

No. 3

No. 4

T1

T2

OFF

OFF

10 seconds

150 seconds

ON

OFF

10 seconds

180 seconds

OFF

ON

10 seconds

120 seconds

ON

ON

20 seconds

180 seconds

T1: Time to drain the Water Tank

T2: Time to restrain defrost completion

4) Drain Counter

CAUTION

Do not adjust the Drain Counter, or the Evaporator may freeze up.

The Drain Counter is factory-adjusted to drain the Water Tank every 10 cycles, and no adjustment is required. However, where water quality is bad and the icemaker needs a pump drain more often, the Drain Counter can be adjusted as shown in the table below:

SETTING

 

FREQUENCY

Dip Switch

Dip Switch

 

No. 5

 

No. 6

 

OFF

 

OFF

every cycle

ON

 

OFF

every 2 cycles

OFF

 

ON

every 5 cycles

ON

 

ON

every 10 cycles

23

Image 23
Contents KM-1300MAH KM-1300MWH KM-1300MRH Hoshizaki AMERICA, INC Contents Maintenance KM-1300MAH Air-cooled Specifications2a. KM-1300MWH Water-cooled 2b. KM-1300MWH Water-cooled Serial No. M10156D KM-1300MRH Remote air-cooled Condensing Unit URC-12F Specifications Model URC-12F II. General Information Construction KM-1300MWH Water-cooled KM-1300MRH Remote air-cooled Controller Board Features of Control Products E Controller BoardController Board SOLID-STATE ControlPage Freeze Cycle Beep every 3 sec. = High Evaporator Temperature 127 FMinute Fill Cycle Harvest CycleControl Products HOS-001A Board Sequence 1st Cycle 2nd Cycle and after with pump drain 2nd Cycle and after with no pump drain Controls and Adjustments Setting Time Setting Frequency Checking the Controller Board Page III. Technical Information KM-1300MWH Water-cooled KM-1300MRH Remote air-cooled KM-1300MAH Air-cooled and KM-1300MWH Water-cooled Wiring DiagramsCut-out 412 ±21.3 Psig Cut-in 327±21.3 Psig Timing Chart Page Performance Data Serial # L00001F to M10155C KM-1300MWH Water-cooled Serial # M10156D KM-1300MRH Remote air-cooled Problem Possible Cause Remedy IV. Service Diagnosis No ICE ProductionController Board Problem Possible Cause Remedy LOW ICE Production Evaporator is Frozen UPOthers Abnormal ICEEvacuation and Recharge R-404A Service for Refrigerant LinesRefrigerant Recovery Brazing Removal and Replacement of Compressor Important Removal and Replacement of Drier Removal and Replacement of Expansion Valve Removal and Replacement of HOT GAS Valve and Line Valve Removal and Replacement of Evaporator Important Page Page Page Removal and Replacement of Thermistor Important Removal and Replacement of FAN Motor Removal and Replacement of Pump Motor Removal and Replacement of Water ValveRemoval and Replacement of Spray Tubes Preparing the Icemaker for Long Storage VI. Maintenance and Cleaning InstructionsPage Cleaning Cleaning Procedure Sanitizing Procedure Following Cleaning Procedure Page Maintenance