Hoshizaki KM-1300MAH, KM-1300MWH, KM-1300MRH service manual Setting Time

Page 22

1) Defrost Control

A thermistor (Semiconductor) is used for a defrost control sensor. The resistance varies depending on the Suction Line temperatures. The Thermistor detects the temperature of the Evaporator outlet to start the Defrost Timer. No adjustment is required. If necessary, check for resistance between Thermistor leads, and visually check the Thermistor mount- ing, located on the Suction Line next to the Evaporator outlet.

Temperature (°F)

Resistance (k)

0

14.401

10

10.613

32

6.000

50

3.871

70

2.474

90

1.633

Check a thermistor for resistance by using the following procedures.

(i)Disconnect the connector K3 on the board.

(ii)Remove the Thermistor. See “V. 11. REMOVAL AND REPLACEMENT OF THERMIS- TOR.”

(iii)Immerse the Thermistor sensor portion in a glass containing ice and water for 2 or 3 minutes.

(iv)Check for a resistance between Thermistor leads.

Normal reading is within 3.5 to 7 k. Replace the Thermistor if it exceeds the normal reading.

2) Defrost Timer

No adjustment is required under normal use, as the Defrost Timer is adjusted to the suit- able position. However, if necessary when all the ice formed on the Evaporator does not fall into the bin in the harvest cycle, adjust the Defrost Timer to longer setting by adjusting the Dip Switch (No. 1 & 2) on the Controller Board.

SETTING

 

TIME

Dip Switch

Dip Switch

 

No. 1

 

No. 2

 

OFF

 

OFF

60 seconds

ON

 

OFF

90 seconds

OFF

 

ON

120 seconds

ON

 

ON

180 seconds

22

Image 22
Contents KM-1300MAH KM-1300MWH KM-1300MRH Hoshizaki AMERICA, INC Contents Maintenance Specifications KM-1300MAH Air-cooled2a. KM-1300MWH Water-cooled 2b. KM-1300MWH Water-cooled Serial No. M10156D KM-1300MRH Remote air-cooled Condensing Unit URC-12F Specifications Model URC-12F II. General Information Construction KM-1300MWH Water-cooled KM-1300MRH Remote air-cooled SOLID-STATE Control Features of Control Products E Controller BoardController Board Controller BoardPage Harvest Cycle Beep every 3 sec. = High Evaporator Temperature 127 FMinute Fill Cycle Freeze CycleControl Products HOS-001A Board Sequence 1st Cycle 2nd Cycle and after with pump drain 2nd Cycle and after with no pump drain Controls and Adjustments Setting Time Setting Frequency Checking the Controller Board Page III. Technical Information KM-1300MWH Water-cooled KM-1300MRH Remote air-cooled Wiring Diagrams KM-1300MAH Air-cooled and KM-1300MWH Water-cooledCut-out 412 ±21.3 Psig Cut-in 327±21.3 Psig Timing Chart Page Performance Data Serial # L00001F to M10155C KM-1300MWH Water-cooled Serial # M10156D KM-1300MRH Remote air-cooled IV. Service Diagnosis No ICE Production Problem Possible Cause RemedyController Board Problem Possible Cause Remedy Evaporator is Frozen UP LOW ICE ProductionAbnormal ICE OthersRefrigerant Recovery Service for Refrigerant LinesEvacuation and Recharge R-404A Brazing Removal and Replacement of Compressor Important Removal and Replacement of Drier Removal and Replacement of Expansion Valve Removal and Replacement of HOT GAS Valve and Line Valve Removal and Replacement of Evaporator Important Page Page Page Removal and Replacement of Thermistor Important Removal and Replacement of FAN Motor Removal and Replacement of Water Valve Removal and Replacement of Pump MotorRemoval and Replacement of Spray Tubes VI. Maintenance and Cleaning Instructions Preparing the Icemaker for Long StoragePage Cleaning Cleaning Procedure Sanitizing Procedure Following Cleaning Procedure Page Maintenance