Manitowoc Ice S1800M manual Installation Instructions Section Location of Ice Machine

Page 10

Installation Instructions

Section 2

 

 

Location of Ice Machine

The location selected for the ice machine must meet the following criteria. If any of these criteria are not met, select another location.

The location must be free of airborne and other contaminants.

The air temperature must be at least 35°F (1.6°C), but must not exceed 110°F (43.4°C).

The location must not be near heat-generating equipment or in direct sunlight and must be protected from weather.

The location must not obstruct air flow through or around the ice machine. Refer to the chart below for clearance requirements.

S1800M

Water-Cooled*

Top/Sides

8" (20.3 cm)

Back

5" (12.7 cm)

*There is no minimum clearance required for water-cooled or remote ice machines. This value is recommended for efficient operation and servicing only.

!Caution

The ice machine must be protected if it will be subjected to temperatures below 32°F (0°C). Failure caused by exposure to freezing temperatures is not covered by the warranty. See “Removal from Service/Winterization”.

Ice Machine Heat of Rejection

Series

Heat of Rejection

Ice Machine

Air Conditioning

Peak

S1800M

24000

36000

B.T.U./Hour

Because the heat of rejection varies during the ice making cycle, the figure shown is an average.

Ice machines, like other refrigeration equipment, reject heat through the condenser. It is helpful to know the amount of heat rejected by the ice machine when sizing air conditioning equipment where self-contained air- cooled ice machines are installed.

This information is also necessary when evaluating the benefits of using water-cooled or remote condensers to reduce air conditioning loads. The amount of heat added to an air conditioned environment by an ice machine using a water-cooled or remote condenser is negligible.

Knowing the amount of heat rejected is also important when sizing a cooling tower for a water-cooled condenser. Use the peak figure for sizing the cooling tower.

2-2

Part Number 80-1633-3

Image 10
Contents S1800M Model Ice Machines Installation Use and Care Manual Read These Before Proceeding Personal Injury PotentialTable of Contents Section Maintenance Table of Contents Section Ice Machine OperationSection Before Calling For Service Model Numbers How to Read a Model NumberSection General Information Ice Cube SizesGeneral Information Section Accessories Section General Information Model/Serial Number Location Model/Serial Number LocationWarranty Coverage General Section Installation InstructionsIce Machine Dimensions S1800 WATER-COOLED ICE MachinesInstallation Instructions Section Location of Ice Machine Ice Machine Heat of RejectionMinimum Circuit Ampacity Section Installation Instructions Electrical ServiceVoltage Electrical RequirementsSelf Contained ICE Machine 208-230/3/60 For United Kingdom OnlySelf Contained ICE Machine 115/1/60 or 208-230/1/60 Self Contained ICE Machine 230/1/50Water Inlet Lines Cooling Tower ApplicationsWater Supply Drain ConnectionsTypical Water Supply Drain Installation Installation Instructions SectionWater Supply and Drain Line SIZING/CONNECTIONS Section Installation Instructions Installation Check List AuCS Automatic Cleaning System Potential Personal Injury SituationSection Ice Machine Operation Section Ice Machine OperationComponent Identification Ice Machine Operation Section Sequence Of Operation Initial START-UP or START-UP After Automatic SHUT-OFFHarvest Safety TimersHarvest Sequence 5. Water Purge Automatic SHUT-OFF 7. Automatic Shut-OffICE Thickness Check Ice Machine Operation Section Operational ChecksWater Level Ice Thickness CheckWater Purge Adjustment Harvest Sequence Water PurgeIce Machine Operation Section Ice Machine Inspection Section MaintenanceExterior Cleaning Water-Cooled Condenser Water Regulating ValveSachet Replacement Frequency Maintenance Section GuardianInstallation Sachet Replacement ProcedureCleaning Procedure Section Maintenance Interior Cleaning and SanitizingStep Maintenance Section Sanitizing ProcedureRemoval of Parts for CLEANING/SANITIZING Water Curtain Removal Ice Thickness Probe Water CurtainIce Thickness Probe Removal Water Trough Water Distribution TubeWater Distribution Tube Removal Water Pump Water Level ProbeWater Pump Removal Dump Valve Disassembly Water Dump ValveEvaporator Tray Removal Drain Line Check ValveWater Inlet Valve Pry Open the Water Regulating Valve AUCS→ Accessory Maintenance Section Removal from Service/WinterizationSELF-CONTAINED WATER-COOLED ICE Machines Section Before Calling For Service ChecklistBefore Calling For Service Section Safety Limit FeaturePage Manitowoc ICE, INC