ICE Series | Remote Condenser Guidelines |
Remote Condenser Installation
For proper operation of the
Remote condensers must be installed per local building codes. A two to four inch diameter roof penetration will be needed for refrigerant lines and electrical conduit. The penetration should be within two feet of where the condenser will be located. A roof jack must be installed at the penetration.
Installation Guidelines
Ambient operating temperatures:
Maximum refrigerant line length: 60 ft. (18.29 Meters)
Maximum vertical rise:16 ft. (4.88 Meters)
Minimum condenser height: ICE Series ice machine remote condensers must not be installed more than 6 feet (1.3 meters) below the refrigerant line quick connects at the rear of the ice machine. No part of the refrigerant lines, between the ice machine and the remote condenser, should fall below this point. Condensers must have a vertical airflow.
Air Flow
Page 4