MFI Series | For the Installer |
Installation Guidelines:
For proper operation of the
Ambient Operating Temperatures:
Minimum Operating Temperature: 50°F (10°C)
Maximum Operating Temperature 100°F (38°C)
Note:
Incoming Water Supply
Minimum incoming water temperature: 40°F (4.5°C)
Maximum incoming water temperature: 100°F (38°C)
Minimum incoming water pressure: 20 psi (1.4 bar)
Maximum incoming water pressure: 80 psi (5.6 bar)
Note: If water pressure exceeds 80 psi a water pressure regulator must be installed.
Drains
All drain lines must be installed per local codes. Flexible tubing is not recommended. Route bin drain, vented float overflow drain and water condenser drain individually to a floor drain. The use of condensate pumps for draining water is not recommended by
Water Filtration
A water filter system should be installed with the ice machine.
Clearance Requirements
Stacking
Dispenser Application
The MFI ice machine is approved for specific dispenser applications, reference page 3.
Electrical Specifications
Refer to the serial plate at the rear of the ice machine to make sure proper voltage and circuit breaker size have been supplied. Make sure the machine is on a dedicated circuit. The MFI Series are not supplied with an electrical power cord and will need to be installed and wired per local electrical codes.
Adjustments
Level the machine within 1/8 inch in all directions. Adjust the cabinet or bin legs as required. Check the bin control for proper operation.
Check the water level in the reservoir for proper adjustment. Check the water regulating valve adjustment if water cooled.
Page 1