Ice-O-Matic MFI Electrical Sequence, Shut Down, Control Board Protection Devices, To Reset, Page

Page 19

MFI Series

Electrical Sequence

Electrical Sequence:

There are 7 indicator lights on the control board:

●WTR-OK:(Water OK) Green. Normal=Glowing. Glow when there is water in the reservoir.

●PWR-OK:(Power OK) Green. Normal=Glowing. Glows when the power board has power and is functional.

●Service: Red. Normally Off.

●Freeze: Red. Normally glowing when making ice.

●Bin Full: Red. Normally Off when making ice.

●LED1: White. Located next to the Control Board’s Compressor Relay. Normally glowing when making ice.

●LED2: White. Located next to the Control Board’s Auger Motor Relay. Normally glowing when making ice.

If the machine is switched OFF at the mode switch, but otherwise ready to go, switching the mode switch ON does the following:

●The PWR-OKlight glows.

●If there is water in the float reservoir, the WTR-OKlight glows.

●After 10 seconds the Freeze, LED1 and LED3 lights glow and the machine starts up.

Start Up:

●The compressor relay and auger motor relay become energized, connecting power to the windings of the auger motor and contactor coil.

●The contactor is energized, connecting power to the compressor, and the compressor starts.

●As ice is made it passes between the ice level sensors but because it is not a continuous stream it only interrupts the sensor’s infrared beam momentarily. The bin full light remains off and the machine stays on until ice builds up in the bin and blocks the path between the sensors for 6 seconds or longer. When that occurs the bin full light glows and the machine shuts down.

Shut Down:

●The compressor relays opens, LED1 goes out. ●The compressor contactor opens.

●The auger motor stays on for 1 more minute, clearing out ice in the evaporator, and then ●The auger motor relay opens, LED3 goes out and the auger motor stops.

The compressor will not restart until 2 minutes or more have passed after last shutdown. If the path between the ice level sensors remains clear for more than 10 seconds the ice machine will restart.

Control Board Protection Devices:

●When the water level in the reservoir falls below the water level sensor’s tip, the WTR-OKlight goes out and the machine shuts down. When water refills the reservoir the WTR-OKlight glows and the machine starts up again.

●If the auger drive motor currents becomes excessive the compressor and auger drive motor will be switched OFF and the Service light will blink. The control board will restart the auger drive motor in 4 minutes. If during the first 60 seconds after restart the auger motor current stays within limits, the compressor is restarted and the machine returns to normal operation. If the auger motor’s current is excessive within 60 seconds after restart, the process will be repeated once more. If during that try the current is still excessive the machine shuts down and must be manually reset. The Service light will then be glowing continuously.

To Reset:

●Switch power to the unit off and then back on.

Other Protection Devices:

●If the high pressure control cut out switch opens the machine will stop immediately. It will automatically reset when the high pressure falls below its cut in point.

●If the low pressure control cut out switch opens the machine will stop immediately. It will automatically reset when the pressure rises above its cut in point.

●The mode (ON-OFF)switch is the manual control for the complete machine, but it is not a service disconnect.

Page 13

Image 19
Contents Denver, Colorado SERVICE AND INSTALLATION MANUAL MFI SeriesIce-O-Matic 11100 East 45th AvePage Page MFI SeriesIntroduction Keep this manual for future referencePage Table Of ContentsTable of Contents MFI SeriesConcealed Loss or Damage Freight Claim ProcedureInspect Promptly Visible Loss or DamageMFI Series WarrantyPage Adjustments For the InstallerInstallation Guidelines Electrical SpecificationsMFI Series For The InstallerPage MFI Series Ice Machine SpecificationsBin Application For the InstallerWater Limitations LocationStorage Bin Ice machinePage For the InstallerMFI Series Allow 6 “Clearance for Air CirculationAIR COOLED MODELS For the PlumberWater Inlet WATER COOLED MODELSAir Cooled Models For the ElectricianElectrical Connections Water Cooled ModelsPage Final Check ListFor the Installer MFI SeriesMFI Series Start UpPre-StartInspection Start UpPage Component DescriptionAir Cooled Model Shown MFI SeriesPage MFI SeriesComponent Description Potential Relay The compressor start relayIce Sweep Bearing Breaker/Divider Auger MFI SeriesComponent Description PageShut Down To ResetElectrical Sequence Electrical SequencePage Operation WaterWater System MFI SeriesTypical Low Side Pressure High Pressure Cut Out- Automatic ResetLow Pressure Cut Out- Automatic Reset Operation PerformanceKEEP OUT OF THE REACH OF CHILDREN Sanitizing and CleaningICE MAKING SYSTEM In place cleaning scheduled at a minimum of twice a yearMFI Series Bearing MaintenanceBearing Maintenance Note Left Hand ThreadsMFI Series Sensor MaintenanceBin Control Sensor Water SensorPage Maintenance Air CooledClean the air cooled condenser MFI Series2. Turn off the water supply to the ice machine Auger Maintenance1. Disconnect electrical power to the ice machine AugerProbable Correction Service DiagnosisSymptom Possible CausePossible Cause Service DiagnosisSymptom MFI SeriesPage Control System Diagnostics4.High pressure cut out check MFI SeriesMFI Series R&R- Water Reservoir, Bin ControlWater Reservoir Bin Controls Ice Level SensorsPage To Remove the Breaker Bearing AssemblyR&R-Bearingand Breaker MFI SeriesPage R&R-AugerTo Remove the Auger MFI SeriesTo Replace the Water Seal R&R-WaterSealTo Remove the Water Seal Removal of the Water SealMFI Series R&R-EvaporatorTo Replace the Evaporator To Reassemble the Evaporator and AugerTo Inspect the Gear Motor To Remove and Repair the Gear Motor AssemblyR&R-GearMotor To Check the Gear MotorPage To Remove the Condenser Fan Motor AssemblyR&R-FanBlade and Motor MFI SeriesInstructions for Liquid Charging R404A Refrigeration System ServiceService RefrigerationPage MFI0500 Wiring DiagramWiring Diagram MFI0500 Air, MFI0500 Water MFI SeriesMFI Series MFI0800 Wiring DiagramPage Page MFI0805/1255 Wiring DiagramWiring Diagram MFI0805, MFI1255 Air MFI SeriesPage MFI1256 Wiring DiagramWiring Diagram MFI1256 Air MFI SeriesPage Service HistoryWhat to Do Before Calling for Service MFI Series