Ice-O-Matic Maintenance Air Cooled, Clean the air cooled condenser, MFI Series, Page

Page 25
Maintenance: Air Cooled

MFI Series

Maintenance: Air Cooled

Clean the air cooled condenser:

Air flow on this model is from front to back, so the inside of the ice machine will have to be available to clean the air cooled condenser. Use a vacuum cleaner or coil cleaner if needed. DO NOT use a wire brush.

Disconnect electrical power, and remove the air filter if applicable. The filter may be cleaned or replaced.

Clean the condenser: the condenser may appear to be clean on the surface, but it can still be clogged internally. Check with a flashlight from the front to see if light can be seen through the condenser fins.

Step 1. Remove the Top Panel Step 2. Remove two screws and

unplug fan motors.

Step 3. Pull fan motor assembly up and to the right to remove.

Step 4. Clean the condenser.

Step 1. Remove the Top Panel Step 2. Remove the top portion

of the fan shroud. Step 3. Clean the condenser.

Page 19

Image 25
Contents Ice-O-Matic SERVICE AND INSTALLATION MANUAL MFI Series11100 East 45th Ave Denver, ColoradoPage Introduction MFI SeriesKeep this manual for future reference PageTable of Contents Table Of ContentsMFI Series PageInspect Promptly Freight Claim ProcedureVisible Loss or Damage Concealed Loss or DamageMFI Series WarrantyPage Installation Guidelines For the InstallerElectrical Specifications AdjustmentsMFI Series For The InstallerPage Bin Application Ice Machine SpecificationsFor the Installer MFI SeriesStorage Bin LocationIce machine Water LimitationsMFI Series For the InstallerAllow 6 “Clearance for Air Circulation PageWater Inlet For the PlumberWATER COOLED MODELS AIR COOLED MODELSElectrical Connections For the ElectricianWater Cooled Models Air Cooled ModelsFor the Installer Final Check ListMFI Series PagePre-StartInspection Start UpStart Up MFI SeriesAir Cooled Model Shown Component DescriptionMFI Series PageComponent Description MFI SeriesPotential Relay The compressor start relay PageComponent Description MFI SeriesPage Ice Sweep Bearing Breaker/Divider AugerElectrical Sequence To ResetElectrical Sequence Shut DownWater System Operation WaterMFI Series PageLow Pressure Cut Out- Automatic Reset High Pressure Cut Out- Automatic ResetOperation Performance Typical Low Side PressureICE MAKING SYSTEM In place cleaning Sanitizing and Cleaningscheduled at a minimum of twice a year KEEP OUT OF THE REACH OF CHILDRENBearing Maintenance Bearing MaintenanceNote Left Hand Threads MFI SeriesBin Control Sensor Sensor MaintenanceWater Sensor MFI SeriesClean the air cooled condenser Maintenance Air CooledMFI Series Page1. Disconnect electrical power to the ice machine Auger MaintenanceAuger 2. Turn off the water supply to the ice machineSymptom Service DiagnosisPossible Cause Probable CorrectionSymptom Service DiagnosisMFI Series Possible Cause4.High pressure cut out check Control System DiagnosticsMFI Series PageWater Reservoir R&R- Water Reservoir, Bin ControlBin Controls Ice Level Sensors MFI SeriesR&R-Bearingand Breaker To Remove the Breaker Bearing AssemblyMFI Series PageTo Remove the Auger R&R-AugerMFI Series PageTo Remove the Water Seal R&R-WaterSealRemoval of the Water Seal To Replace the Water SealTo Replace the Evaporator R&R-EvaporatorTo Reassemble the Evaporator and Auger MFI SeriesR&R-GearMotor To Remove and Repair the Gear Motor AssemblyTo Check the Gear Motor To Inspect the Gear MotorR&R-FanBlade and Motor To Remove the Condenser Fan Motor AssemblyMFI Series PageService Refrigeration System ServiceRefrigeration Instructions for Liquid Charging R404AWiring Diagram MFI0500 Air, MFI0500 Water MFI0500 Wiring DiagramMFI Series PageMFI Series MFI0800 Wiring DiagramPage Wiring Diagram MFI0805, MFI1255 Air MFI0805/1255 Wiring DiagramMFI Series PageWiring Diagram MFI1256 Air MFI1256 Wiring DiagramMFI Series PageWhat to Do Before Calling for Service Service HistoryMFI Series Page