FULL SIZE ELECTRIC CONVECTION OVENS - SERVICE PROCEDURES AND ADJUSTMENTS
d.Rotate the knob to the lowest temperature setting then back to 350°F.
e.Repeat the average temperature calculation in step 7.
NOTE: Allow the oven to cycle at least two times between adjustments before performing the calculation.
a)If the average temperature still differs more than 10 °F from the dial setting, adjust the thermostat calibration until the average temperature is within tolerance.
C.If the above adjustment cannot be obtained:
1)Turn the power switch OFF.
WARNING: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AT THE MAIN CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT BOX INDICATING THE CIRCUIT IS BEING SERVICED.
2)Replace the temperature control and check calibration.
MECHANICAL (KX)
THERMOSTAT CALIBRATION
1.Place a thermocouple in the geometric center of the oven cavity.
2.Set the power switch to ON.
3.Set the thermostat dial to 350 °F.
4.Allow the oven temperature to stabilize (normally 3 cycles).
5.Record the temperature when the thermostat cycles OFF and ON for at least three complete cycles.
6.Calculate the differential by subtracting the temperature indicated when heat lamp goes out from temperature indicated when heat lamp comes on.
Differential Heat lamp OFF Heat lamp ON Example: 360(lamp off) 340(lamp on) 20
A.The differential calculated should be less than 30F.
1)If the differential is 30 °F or less, the thermostat is functioning properly.
a. Proceed to step 7.
2)If the differential is more than 30 F, the thermostat is malfunctioning.
a.Install a replacement thermostat and check calibration.
7.Calculate the average temperature by adding the temperature indicated when the heat lamp goes out to the temperature indicated when the heat lamp comes on and dividing this answer by 2.
[Temp. (lamp off) Temp. (lamp on)] ÷ 2 Average Temp.
Example: 360340÷ 2 350
A.If the average temperature is 15 F or less from the dial setting, the thermostat is properly calibrated.
B.If the average temperature is more than 15 F of the dial setting, the thermostat calibration must be adjusted.
1)Remove the thermostat knob.
2)Hold the thermostat shaft and turn the inner set screw clockwise to decrease temperature or counterclockwise to increase temperature (¼ turn = 35F).
8.Replace the knob and verify the setting is still at 350°F.
9.Repeat step 7 until the average temperature is within tolerance.
NOTE: Allow the oven to cycle at least two times between adjustments before performing the calculation.
F25105 (December 2001) |
| Page 18 of 60 |
|