Trane CVHE-SVU01E-ENX39640712050 manual Oil Pump Heater Operation, Seasonal Unit Shutdown

Page 87

Unit Shutdown

Unit Shutdown Procedures

Daily Unit Shutdown

Note: Refer to Start-Run Shutdown sequence in General Information Overview Sequence of Operation.

1.Press STOP.

2.After compressor and water pumps shutdown turn Pump Contactors to OFF or open pump disconnects.

Seasonal Unit Shutdown

CAUTION

Oil Pump Heater

Operation!

CONTROL POWER DISCONNECT SWITCH MUST REMAIN CLOSED TO ALLOW OIL SUMP HEATER OPERATION. Failure to do this will allow refrigerant to condense in the oil pump.

3.Open all disconnect switches except the control power disconnect switch.

4.Drain the condenser piping and cooling tower, if used. Rinse with clean water.

5.Remove the drain and vent plugs from the condenser headers to drain the condenser. Air dry bundle of residual water.

6.Once the unit is secured for winter, the maintenance procedures described under “Annual Maintenance” in the Periodic Maintenance section of this

manual should be performed by qualified Trane service technicians.

Note: During extended shutdown, be sure to operate the purge unit for a 2- hour period every two weeks. This will prevent the accumulation of air and noncompensable in the machine. To start the purge, change the purge mode to ON in the DynaViewSettings Purge Menu. Remember to turn the purge mode to Adaptive after the 2-hour run time.

Trouble Analysis

If the ALARM indicator on the control panel is flashing, an MMR diagnostic has occurred. Refer to Diagnostic section for trouble shooting information. (page 35)

CVHE-SVU01E-EN

87

Image 87
Contents Operation Maintenance Read these carefully Contents Unit Nameplate General InformationLiterature change About this manualC0000000K01G14C10W1A03B1 CVHF091NAL00ACU2758W7E8TBControl Optional Packages Commonly Used AcronymsCvhf OverviewGeneral Information General Information Cvhf Compressor Cooling CycleCVHE, Cvhg pressure enthalpy curve Cvhf pressure enthalpy curve DynaView Human Interface TechView Chiller Service ToolCVHE, CVHF, and Cvhg sequence of operation running General Information Oil and Refrigeration Pump Surface TemperaturesOil refrigerant pump 20 100 percent RLA Base Loading Control AlgorithmGeneral Information Ice Machine Control Free Cooling Cycle Free Cooling Frcl Hot Gas Bypass Hot Water control Auxiliary Condensers Heat Recovery CycleUnit Control Panel UCP Control Panel Devices and Unit Mounted DevicesUnit Control Panel UCP User-defined language support Variable water flow through the evaporatorDynaView main processor Operator InterfaceOperator Interface How It Works Chiller Stop Prevention/Inhibit FeatureTop Level Mode Description Minsec System ResetReference Main Screen Diagnostic Screen Back button provides navigation back to the chiller screen Operator Interface Condenser Report Items Units Reports Evaporator Report items UnitsPurge Report Items Units Compressor Report Items UnitsMotor Report Items Units RPMPPM Historic Diagnostics LogAshrae Chiller Log Units RLAChilled Water Setpoint Chiller Feature SettingsMode Overrides Description Units Default Monitor ValueDescription Units Default Display SettingsPurge Operator Interface Operator Interface Operator Interface Operator Interface Operator Interface Binding Interprocessor CommunicationInter Processor Communications IPC3 IPC3 Definitions Bus ManagementControl System Components Control panel components layout and approximate dimensionsControl System Components Control Panel Devices Opst Machine Shutdown Manual Reset MMRHead Relief Request Output Compressor Running RelayExop Refrigerant Monitor Input 1A17Cdrp Condenser Refrigerant Pressure Output Frcl Free Cooling OptionHgbp Hot Gas Bypass Option Trmm TRM4 Tracer Comm 4 interfaceTemperature based Condenser Pressure OutputPressure based Refrigerant Differential Pressure Indication Output Gbas Generic Building Automation System GbasPercent RLA Output Wpsr WFC Water Pressure Sensing Option Module CharacteristicsExternal Chilled Water Setpoint Ecws External Current Limit SetpointComm + 1A8, 1A9, 1A11, 1A12 Quad Relay Output Status1A13, 1A18, 1A19, 1A20 Dual Binary input module 1A14 Communication interface ModuleRecommended Length to Run external Output signals 1A15, 1A16, 1A17, 1A21 Dual Analog Input/output ModuleAnalog Input Unit mounted devices Control Sequence of Operation Electrical SequenceUCP and Wye-Delta Starter Control Circuits Delay time 200 msec. Opens 2K1 Control Sequence of Operation Test and start timing sequence AFD Machine Protection Adaptive Control Momentary Power Loss MPL ProtectionOverload trip time versus percent RLA Current Overload ProtectionPhase Loss Protection Current Limit ProtectionReverse Rotation Protection Differential to Start or Stop SoftLoadingMinimum and Maximum Capacity Limit Evaporator Limit Leaving Water Temperature CutoutMain Processor Software Revision 6.0 and higher Low Refrigerant Temperature CutoutCutout strategy Condenser Limit Evaporator Variable Flow CompensationClear Restart Inhibit Restart Inhibit Start to Start Time SettingRestart Inhibit Restart Inhibit Free StartsHigh Vacuum Lockout Oil Temperature Control Return Water Controls Chilled Water Reset CWROutdoor Air Temperature Maximum ResetEquation Values for start reset typesDegrees of Reset Constant ReturnOutdoor air temperature versus degrees of reset Reset RatioReset function for return CWR Reset Ratio = 50% Return CWR Unit Start-Up Procedures Unit StartupDaily Unit Start-Up Seasonal Unit Start-Up Before changeover to heating modeLive Electrical Components Toxic HazardsSeasonal Unit Shutdown Unit Shutdown ProceduresUnit Shutdown Oil Pump Heater OperationRecord Keeping Forms Periodic MaintenanceDaily Maintenance and Checks Moisture ContaminationEvery 3 Months Weekly MaintenanceNormal Chiller Operating Characteristics Hazardous Voltage w/ CapacitorsAnnual Maintenance Off-Season MaintenanceCompressor Oil Change on Oil MaintenanceOil Change Procedure Heater DamageReplacing Oil Filter Oil Filter ReplacementLubrication MaintenanceOil Supply System Problems Other Maintenance RequirementsFront View with Refrigerant Pump Do not Leave Grease Fittings InstalledRefrigerant Charge Contains RefrigerantProper Water Treatment Recovery and Recycle ConnectionsLeak Testing Cleaning the CondenserCleaning the Evaporator Control Settings AdjustmentsUnit Corrosion Damage Unit Preparation Purge SystemHazardous Voltage w/ Capacitors 100 101 102 103 104 105 106 107 108 109 110 111 Trane

CVHE-SVU01E-ENX39640712050 specifications

The Trane CVHE-SVU01E-ENX39640712050 is a high-efficiency centrifugal chiller designed for commercial and industrial applications. This state-of-the-art unit is engineered to provide reliable cooling performance, energy efficiency, and optimized operational flexibility. It is particularly suitable for large-scale facilities that require significant cooling capacity and robust performance under varying load conditions.

One of the most notable features of the CVHE-SVU01E series is its advanced variable speed drive technology. This technology enables the chiller to adjust its speed according to the cooling demands of the facility, resulting in substantial energy savings. By operating at optimal speeds, this unit reduces power consumption and enhances overall efficiency. This is noteworthy in the context of rising energy costs and increasing sustainability demands across various industries.

Moreover, the CVHE-SVU01E is equipped with Trane’s proprietary Compliant Scroll compressor technology. This innovative compressor design minimizes mechanical losses and increases the efficiency of the chiller system. Additionally, the compressor is specifically designed to handle varying refrigerant flow rates, allowing the chiller to maintain performance even when faced with fluctuating conditions.

Another significant characteristic of this chiller model is its use of environmentally friendly refrigerants, aligning with global regulations aimed at reducing greenhouse gas emissions. This commitment to sustainability ensures that the CVHE-SVU01E not only provides excellent cooling performance but also adheres to contemporary environmental standards.

The unit utilizes an advanced control system that simplifies operation and enhances troubleshooting capabilities. The intuitive interface allows facility managers to monitor performance metrics, optimize operation schedules, and conduct remote diagnostics, significantly reducing costly downtime and maintenance efforts.

Furthermore, the compact and modular design of the CVHE-SVU01E makes it easy to install in various settings. Its durability is ensured through the use of high-quality materials and components, designed to withstand the rigors of demanding environments. With reduced maintenance requirements, facility operators can focus on core business functions without frequent interruptions.

In summary, the Trane CVHE-SVU01E-ENX39640712050 combines cutting-edge technologies and features to deliver exceptional performance, efficiency, and reliability in commercial cooling applications. Its advanced design contributes to reduced energy costs, minimal environmental impact, and greater operational flexibility, making it an excellent choice for organizations seeking sustainable and efficient cooling solutions.