Trane Tracer Unit Ventilator, ZN.520 manual Input/Output Summary, Input and output summary

Page 27

Input/Output Summary

Input/Output Summary

The following lists all possible bi- nary and analog inputs and out- puts available for the classroom unit ventilator applications. Some of the points listed may be mutual- ly exclusive and some are optional. (See Table 8: Input and output

summary)

Table 8: Input and output summary

Most binary inputs and outputs are wired from the factory based on unit configuration and options. If the generic inputs and outputs are to be used, wiring connections are made at the 1/4” quick-connect ter- minals provided.

Analog inputs from a wall-mount- ed zone sensor, humidity sensor, CO2 sensor, or a generic device

must be wired to the 1/4” quick- connect terminals provided. Most other analog inputs will be wired from the factory.

Input

Binary Inputs

Binary Outputs

Description

Freezestat

Fan Status

Occupancy/Generic

J1-1 Fan High Speed

J1-3 Fan Low Speed

J1-2 Exhaust Fan

J1-5 Cooling Open (Modulating valve/DX/ Isolation valve)

J1-6 Cooling Close

J1-7 Face and Bypass Damper

Open

J1-8 Face and Bypass Damper

Close

J1-9 Heat Open (Modulating

valve/Isolation valve) or 1 st

Stage Electric Heat

J1-10 Heat Close or 2 n d Stage

Electric Heat

J1-11 Economizer Damper

Open

J1-12 Economizer Damper

Close

TB4-1 Generic/Baseboard

Heat

TB4-2 24 VAC

30

UV-SVP01A-EN

Image 27
Contents Tracer ZN.520 for Classroom Unit Ventilator Installation Owner DiagnosticsInstallation of New Units Start-up ProceduresPower Up Sequence Tracer ZN.520 Overview General InformationGeneral Information Tracer ZN.520 unit controller circuit board Controller Circuit Board FeaturesController Features ServiceTypical Components Communication Configurations Peer-to-Peer CommunicationsIntegrated Comfort System Stand-Alone Communication InterfaceInteroperability Description End Device SpecificationsCharacteristic Standard End DevicesStandard End Devices Way Control Valve Time clock Zone sensor Dpdt Control Transformer Specifications Installation and WiringBinary Inputs Generic/baseboard Heat Binary Output Binary OutputsAnalog inputs Analog InputsMounting Vertical classroom unit ventilator end pocket Power WiringProper zone sensor placement Installing the Wall- Mounted Zone Sensor OptionalHumidity and CO2 Sensors Typical Wiring Diagram-Wall Mounted Zone Sensor Typical Wiring Diagram-Unit Mounted Zone Sensor Typical Wiring Diagram-Unit Input and output summary Input/Output SummaryInput/Output Summary Heating source ConfigurationConfigurable parameters Cooling sourceBinary Outputs1 Analog input summary Binary input summary ConfigurationBinary Inputs1 Analog Inputs1Default Fan ConfigurationEnd Device Configurations Fan configuration rangesDischarge Air Limits Setpoint defaults Default Valid rangeDischarge air limit ranges Default Valid range SetpointsOccupied Bypass Timer Power-Up Control WaitMaintenance Timers Location Identifier Unit Identification TagWinking Occupancy Power-UpUnit Operation Heating And Cooling Changeover LogicHeat/Cool Changeover logic Fan Operation Fan Off DelayCooling Operation Heating OperationModulating Valves Valve OperationFace-and-Bypass Damper Operation Exhaust fan/damper operationTemperature Assumed1 Entering Water Temperature SamplingWater assumption chart Unit ConfigurationBaseboard Heat Operation Economizer OperationDX Operation Electric Heat OperationOther Modes Filter Status/ Maintenance TimerOutput Overrides Fan StatusSimple data sharing application Data Sharing-LonWorksMore complex data sharing application Heating And Cooling Changeover Logic Heat/Cool Changeover logic Cooling Operation Valve Operation Entering Water Temperature Sampling Economizer Operation Output Overrides Data Sharing-LonWorks More complex data sharing application Yellow Comm LED TroubleshootingRed Service LED Black Service Push ButtonExit6 Test ProcedureTroubleshooting Outdoor Air Temperature Failure Space Temperature FailureEntering Water Temperature Failure Discharge Air Temperature LimitDiagnostics Troubleshooting Translating Multiple Diagnostics Fans Rover service toolValves Valves stay closed Probable cause Possible ExplanationValves stay open Probable cause Possible Explanation DX/Electric Heat Outside Air DamperOutdoor air damper stays closed Probable cause Explanation Probable Cause Explanation Outdoor air damper stays openReplacing Circuit Boards Tracer ZN.520 Unit Controller ReplacementAppendix Hardwired Setpoint AdjustmentFan Switch Resistance Values Hardwired Thermistor ValuesFunction Appendix-Binary ConfigurationBinary Configuration Binary configuration details Binary input or outputUnit Operation Based On The Effective HEAT/COOL Output Heat/cool mode input NviHeatCoolEffective heat/ cool mode output nvoHeatCool Appendix-Unit OperationAppendix-Unit Operation Input/output listing1 Configuration properties1Appendix-Data Lists Data ListsSet the Program Setting the Time ClockAppendix-Timeclock Set the Time and DayOverride Program Manual Operation Review and Change ProgramsAppendix-Timeclock Appendix-Location Identifier Location Identifier Location Identifier Location Identifier Trane Company