Configuration
Binary Inputs1
Table 11: Binary input summary
Binary input
BI 1
BI 2
BI 3
BI 4
Configuration
Low coil temperature detection or not used
Not used
Occupancy, generic, or not used
Fan status or not used
Valid range
Normally open Normally closed
Normally open Normally closed
Normally open Normally closed
Normally open Normally closed
1. Trane Rover service tool uses the unit type to determine and download the proper default binary input configuration.
Analog Inputs1
Table 12: Analog input summary
Analog input
Zone
Set
Fan
AI 1
AI 2
AI 3
AI 4
Configuration
Space temperature
Setpoint (hardwired)
Fan switch
Entering water temperature
Discharge air temperature
Outdoor air temperature or generic temperature input (Note 2)
Humidity, CO2 or generic
Calibration range
+/- 10.0°F (0.1°F resolution)
+/- 10.0°F (0.1°F resolution)
NA
NA
NA
NA
NA
1.Trane Rover service tool uses the unit type to determine and download the proper default analog input configuration.
2.Analog input 3 (AI 3) configured as generic temperature input does not affect unit operation. When configured, the Tracer™ ZN .520 Unit
Controller communicates the generic temperature value to Rover or Tracer Summit and displays it as generic temperature.