Trane Tracer Unit Ventilator, ZN.520 manual Appendix-Binary Configuration, Function

Page 67

Appendix—Binary

Configuration

Binary Configuration

Table 38: Binary configuration details

Binary input or output

BI 1

BI 2

BI 3

BI 4

Defrost

J1-1

J1-2

J1-3

TB4-1 and TB4- 2

Function

Low temp detection

Condensate overflow

Occupancy

Fan status2

Defrost

Fan high

Fan Medium\Exhust

Fan low

Generic binary output/base board heat

Configuration

Normally closed

Normally closed

Normally closed

Normally open

Normally open

NA

Normally open

Normally open

Normally open

Normally open

Description

Closed: BIP 1 is Normal (no diagnostic)

Open: BIP 1 is Active (diagnostic)

Closed: BIP 2 is Normal (no diagnostic)

Open: BIP 2 is Active (diagnostic)

Closed: BIP 3 is Normal (Occupied)

Open: BIP 3 is Active (Unoccupied)1

Open: BIP 3 is Normal (Occupied)

Closed: BIP 3 is Active (Unoccupied)1

When the controller commands the fan on and the binary input remains open for one minute, BIP is normal (diagnostic).

When the controller commands the fan on and the binary input closes, BIP is active (no diagnostic).

When input is Open, BIP is Active (Defrost activated)

When input is Closed, BIP is Normal (no Defrost)

De-energized: Fan off

Energized: Fan high

De-energized: Fan\Exhaust off

Energized: Fan Medium\Exhust on

De-energized: Fan off

Energized: Fan low

De-energized: Output off (de-energized)

Energized: Output on (energized)

1.The occupancy input applications vary for standalone and communicated instances. For more information, see Occupancy arbitration tables in the Appendix.

2.The fan status device is normally closed during normal fan operation. When the fan is off either from a fan failure or the controller commanding the fan off, the binary input device opens.

UV-SVP01A-EN

61

Image 67
Contents Tracer ZN.520 for Classroom Unit Ventilator Installation Owner DiagnosticsInstallation of New Units Start-up ProceduresPower Up Sequence Tracer ZN.520 Overview General InformationGeneral Information Tracer ZN.520 unit controller circuit board Controller Circuit Board FeaturesService Controller FeaturesTypical Components Peer-to-Peer Communications Communication ConfigurationsIntegrated Comfort System Communication Interface Stand-AloneInteroperability Description End Device SpecificationsCharacteristic Standard End DevicesStandard End Devices Way Control Valve Time clock Zone sensor Dpdt Control Transformer Specifications Installation and WiringBinary Inputs Generic/baseboard Heat Binary Output Binary OutputsAnalog inputs Analog InputsMounting Vertical classroom unit ventilator end pocket Power WiringProper zone sensor placement Installing the Wall- Mounted Zone Sensor OptionalHumidity and CO2 Sensors Typical Wiring Diagram-Wall Mounted Zone Sensor Typical Wiring Diagram-Unit Mounted Zone Sensor Typical Wiring Diagram-Unit Input and output summary Input/Output SummaryInput/Output Summary Heating source ConfigurationConfigurable parameters Cooling sourceBinary Outputs1 Analog input summary Binary input summary ConfigurationBinary Inputs1 Analog Inputs1Default Fan ConfigurationEnd Device Configurations Fan configuration rangesDischarge Air Limits Setpoint defaults Default Valid rangeDischarge air limit ranges Default Valid range SetpointsPower-Up Control Wait Occupied Bypass TimerMaintenance Timers Unit Identification Tag Location IdentifierWinking Occupancy Power-UpUnit Operation Heating And Cooling Changeover LogicHeat/Cool Changeover logic Fan Operation Fan Off DelayCooling Operation Heating OperationModulating Valves Valve OperationFace-and-Bypass Damper Operation Exhaust fan/damper operationTemperature Assumed1 Entering Water Temperature SamplingWater assumption chart Unit ConfigurationBaseboard Heat Operation Economizer OperationDX Operation Electric Heat OperationOther Modes Filter Status/ Maintenance TimerOutput Overrides Fan StatusSimple data sharing application Data Sharing-LonWorksMore complex data sharing application Heating And Cooling Changeover Logic Heat/Cool Changeover logic Cooling Operation Valve Operation Entering Water Temperature Sampling Economizer Operation Output Overrides Data Sharing-LonWorks More complex data sharing application Yellow Comm LED TroubleshootingRed Service LED Black Service Push ButtonExit6 Test ProcedureTroubleshooting Outdoor Air Temperature Failure Space Temperature FailureEntering Water Temperature Failure Discharge Air Temperature LimitDiagnostics Troubleshooting Translating Multiple Diagnostics Fans Rover service toolValves stay closed Probable cause Possible Explanation ValvesValves stay open Probable cause Possible Explanation Outside Air Damper DX/Electric HeatOutdoor air damper stays closed Probable cause Explanation Probable Cause Explanation Outdoor air damper stays openReplacing Circuit Boards Tracer ZN.520 Unit Controller ReplacementAppendix Hardwired Setpoint AdjustmentFan Switch Resistance Values Hardwired Thermistor ValuesFunction Appendix-Binary ConfigurationBinary Configuration Binary configuration details Binary input or outputUnit Operation Based On The Effective HEAT/COOL Output Heat/cool mode input NviHeatCoolEffective heat/ cool mode output nvoHeatCool Appendix-Unit OperationAppendix-Unit Operation Input/output listing1 Configuration properties1Appendix-Data Lists Data ListsSet the Program Setting the Time ClockAppendix-Timeclock Set the Time and DayOverride Program Manual Operation Review and Change ProgramsAppendix-Timeclock Appendix-Location Identifier Location Identifier Location Identifier Location Identifier Trane Company