Trane ZN.520, Tracer Unit Ventilator manual Valve Operation

Page 48

Unit Operation

seconds. This provides the ample torque required to start all fan mo- tors from the off position.

Exhaust fan/damper operation

This binary point is a shared point with medium fan speed. For this point to be used for exhaust con- trol, the controller must be config- ured for a 1- or 2-speed fan. The exhaust fan/damper is coordinated with the unit fan and outdoor damper operation. The exhaust output is energized only when the unit fan is operating and the out- door damper position is greater than or equal to the configurable exhaust enable point. The exhaust fan output is disabled when the outdoor air damper position drops 10% below the exhaust enable point. If the enable point is less than 10%, the unit turns on at the enable point and off at 0.

Valve Operation

Modulating Valves

The Tracer ZN.520 controller sup- ports one or two modulating valves for hydronic heating and cooling operation. The main valve/ coil is used for cooling only, heat/ cool changeover (2-pipe applica- tions), or cooling (4-pipe applica- tions). The auxiliary valve/coil provides heating in 4-pipe and heating only applications.

At power-up, the Tracer ZN.520 controller drives the modulating valves to the closed position. The controller calibrates to the full closed position by overdriving the actuator 135%. Whenever the con- troller requests a valve position of zero or 100%, the controller over- drives the actuator 135% regard- less of the current valve position.

Face-and-Bypass

Isolation Valves

Face-and-bypass units may use isolation valves to prevent unwant- ed water flow in the coil. This elim- inates problems such as radiant heat or excessive condensate in 2- pipe systems.

In 4-pipe applications, the isolation valves are used to prevent conflict- ing capacities within the unit.

Face-and-Bypass Damper Operation

Note: The Face-and-bypass actuator is located in the right- hand end pocket of the classroom unit ventilator.

The Tracer ZN.520 controller actu- ates a face-and- bypass damper to modulate a percentage of air to the face of the coil to maintain space comfort. When a requested capaci- ty is present, the unit modulates the damper to allow more air to the face of the coil. An averaging sen- sor is used on the discharge air to provide accurate capacity control.

Figure 18: Horizontal unit with face-and-bypass damper option.

42

UV-SVP01A-EN

Image 48
Contents Installation Owner Diagnostics Tracer ZN.520 for Classroom Unit VentilatorStart-up Procedures Installation of New UnitsPower Up Sequence General Information Tracer ZN.520 OverviewGeneral Information Controller Circuit Board Features Tracer ZN.520 unit controller circuit boardController Features ServiceTypical Components Communication Configurations Peer-to-Peer CommunicationsIntegrated Comfort System Stand-Alone Communication InterfaceInteroperability End Device Specifications CharacteristicStandard End Devices DescriptionStandard End Devices Way Control Valve Time clock Zone sensor Dpdt Control Transformer Installation and Wiring SpecificationsBinary Inputs Binary Outputs Generic/baseboard Heat Binary OutputAnalog Inputs Analog inputsMounting Vertical classroom unit ventilator end pocket Wiring PowerInstalling the Wall- Mounted Zone Sensor Optional Proper zone sensor placementHumidity and CO2 Sensors Typical Wiring Diagram-Wall Mounted Zone Sensor Typical Wiring Diagram-Unit Mounted Zone Sensor Typical Wiring Diagram-Unit Input/Output Summary Input and output summaryInput/Output Summary Configuration Configurable parametersCooling source Heating sourceBinary Outputs1 Binary input summary Configuration Binary Inputs1Analog Inputs1 Analog input summaryFan Configuration End Device ConfigurationsFan configuration ranges DefaultSetpoint defaults Default Valid range Discharge air limit ranges Default Valid rangeSetpoints Discharge Air LimitsOccupied Bypass Timer Power-Up Control WaitMaintenance Timers Location Identifier Unit Identification TagWinking Power-Up Unit OperationHeating And Cooling Changeover Logic OccupancyHeat/Cool Changeover logic Fan Off Delay Cooling OperationHeating Operation Fan OperationValve Operation Face-and-Bypass Damper OperationExhaust fan/damper operation Modulating ValvesEntering Water Temperature Sampling Water assumption chartUnit Configuration Temperature Assumed1Economizer Operation DX OperationElectric Heat Operation Baseboard Heat OperationFilter Status/ Maintenance Timer Output OverridesFan Status Other ModesData Sharing-LonWorks Simple data sharing applicationMore complex data sharing application Heating And Cooling Changeover Logic Heat/Cool Changeover logic Cooling Operation Valve Operation Entering Water Temperature Sampling Economizer Operation Output Overrides Data Sharing-LonWorks More complex data sharing application Troubleshooting Red Service LEDBlack Service Push Button Yellow Comm LEDTest Procedure Exit6Troubleshooting Space Temperature Failure Entering Water Temperature FailureDischarge Air Temperature Limit Outdoor Air Temperature FailureDiagnostics Troubleshooting Translating Multiple Diagnostics Rover service tool FansValves Valves stay closed Probable cause Possible ExplanationValves stay open Probable cause Possible Explanation DX/Electric Heat Outside Air DamperOutdoor air damper stays closed Probable cause Explanation Outdoor air damper stays open Probable Cause ExplanationTracer ZN.520 Unit Controller Replacement Replacing Circuit BoardsHardwired Setpoint Adjustment Fan Switch Resistance ValuesHardwired Thermistor Values AppendixAppendix-Binary Configuration Binary ConfigurationBinary configuration details Binary input or output FunctionHeat/cool mode input NviHeatCool Effective heat/ cool mode output nvoHeatCoolAppendix-Unit Operation Unit Operation Based On The Effective HEAT/COOL OutputAppendix-Unit Operation Configuration properties1 Appendix-Data ListsData Lists Input/output listing1Setting the Time Clock Appendix-TimeclockSet the Time and Day Set the ProgramReview and Change Programs Override Program Manual OperationAppendix-Timeclock Appendix-Location Identifier Location Identifier Location Identifier Location Identifier Trane Company