Trane ZN.520 Fan Configuration, End Device Configurations, Fan configuration ranges, Default

Page 32

Configuration

Fan Configuration

Table 13: Fan configuration ranges

Fan configuration

Fan operation in heating

Fan operation in cooling

Number of fan speeds Configurable fan speed heating Configurable fan speed cooling Zone sensor fan switch

Default

Continuous

Continuous

Varies 2

Varies 2

Varies 2

Enable

Valid range

Continuous (during occupied)

Cycling with capacity (unoccupied)

Continuous (during occupied)

Cycling with capacity (unoccupied)

1, 2

Off, low, high, auto

Off, low, high, auto

Disable or enable

End Device Configurations

Table 14: End device ranges

Main, cooling/changeover valve stroke time

Entering water sampling

Auxiliary, heating valve stroke time

Outdoor air damper stroke time

Occupied outdoor air damper minimum position

Occupied standby outside air damper minimum position

Alternate minimum outside air damper position for low fan speed

Economizer enable temperature

Exhaust fan enable setpoint1

Face-and-bypass damper stroke time

Default

Varies2

Varies2

Varies2

Varies2

15%

15%

40%

55°F

9%

65 seconds

Valid range

30 - 360 seconds

Disable or enable

30 to 360 seconds

30 to 360 seconds

0 to 100%

0 to 100%

0 to 100%

30 to 70°F

0 to 100%, 101% disables the

exhaust fan

30-360 seconds

1.The exhaust fan is energized when the outdoor air damper is equal to or greater than the exhaust fan enable point, and the exhaust fan is turned off when the outdoor air damper is 10% less than the exhaust fan enable point.

2.Varies with unit configuration.

UV-SVP01A-EN

35

Image 32
Contents Installation Owner Diagnostics Tracer ZN.520 for Classroom Unit VentilatorStart-up Procedures Installation of New UnitsPower Up Sequence General Information Tracer ZN.520 OverviewGeneral Information Controller Circuit Board Features Tracer ZN.520 unit controller circuit boardTypical Components Controller FeaturesService Integrated Comfort System Communication ConfigurationsPeer-to-Peer Communications Interoperability Stand-AloneCommunication Interface End Device Specifications CharacteristicStandard End Devices DescriptionStandard End Devices Way Control Valve Time clock Zone sensor Dpdt Control Transformer Installation and Wiring SpecificationsBinary Inputs Binary Outputs Generic/baseboard Heat Binary OutputAnalog Inputs Analog inputsMounting Vertical classroom unit ventilator end pocket Wiring PowerInstalling the Wall- Mounted Zone Sensor Optional Proper zone sensor placementHumidity and CO2 Sensors Typical Wiring Diagram-Wall Mounted Zone Sensor Typical Wiring Diagram-Unit Mounted Zone Sensor Typical Wiring Diagram-Unit Input/Output Summary Input and output summaryInput/Output Summary Configuration Configurable parametersCooling source Heating sourceBinary Outputs1 Binary input summary Configuration Binary Inputs1Analog Inputs1 Analog input summaryFan Configuration End Device ConfigurationsFan configuration ranges DefaultSetpoint defaults Default Valid range Discharge air limit ranges Default Valid rangeSetpoints Discharge Air LimitsMaintenance Timers Occupied Bypass TimerPower-Up Control Wait Winking Location IdentifierUnit Identification Tag Power-Up Unit OperationHeating And Cooling Changeover Logic OccupancyHeat/Cool Changeover logic Fan Off Delay Cooling OperationHeating Operation Fan OperationValve Operation Face-and-Bypass Damper OperationExhaust fan/damper operation Modulating ValvesEntering Water Temperature Sampling Water assumption chartUnit Configuration Temperature Assumed1Economizer Operation DX OperationElectric Heat Operation Baseboard Heat OperationFilter Status/ Maintenance Timer Output OverridesFan Status Other ModesData Sharing-LonWorks Simple data sharing applicationMore complex data sharing application Heating And Cooling Changeover Logic Heat/Cool Changeover logic Cooling Operation Valve Operation Entering Water Temperature Sampling Economizer Operation Output Overrides Data Sharing-LonWorks More complex data sharing application Troubleshooting Red Service LEDBlack Service Push Button Yellow Comm LEDTest Procedure Exit6Troubleshooting Space Temperature Failure Entering Water Temperature FailureDischarge Air Temperature Limit Outdoor Air Temperature FailureDiagnostics Troubleshooting Translating Multiple Diagnostics Rover service tool FansValves stay open Probable cause Possible Explanation ValvesValves stay closed Probable cause Possible Explanation Outdoor air damper stays closed Probable cause Explanation DX/Electric HeatOutside Air Damper Outdoor air damper stays open Probable Cause ExplanationTracer ZN.520 Unit Controller Replacement Replacing Circuit BoardsHardwired Setpoint Adjustment Fan Switch Resistance ValuesHardwired Thermistor Values AppendixAppendix-Binary Configuration Binary ConfigurationBinary configuration details Binary input or output FunctionHeat/cool mode input NviHeatCool Effective heat/ cool mode output nvoHeatCoolAppendix-Unit Operation Unit Operation Based On The Effective HEAT/COOL OutputAppendix-Unit Operation Configuration properties1 Appendix-Data ListsData Lists Input/output listing1Setting the Time Clock Appendix-TimeclockSet the Time and Day Set the ProgramReview and Change Programs Override Program Manual OperationAppendix-Timeclock Appendix-Location Identifier Location Identifier Location Identifier Location Identifier Trane Company