Greenheck Fan PVE-20 Typical Control Center Components, Electric Heater Application/Operation

Page 10

Typical Control Center Components

1. Main Disconnect (non-fusible, lockable)

2. Motor Starter

3. Motor Starter

4. Power Distribution Blocks

5. 24 VAC Control Transformer

6. 24 VAC Terminal Strip

7. Temperature Sensor with Override (used for Economizer Mode)

8. Dirty Filter Sensor

9. Dirty Filter Sensor

15

6

4

7

2

3

8

9

 

 

Electric Heater Application/Operation

Factory installed electric heaters are optionally provided in order to provide preheat frost control. An electric preheater warms the outdoor air prior to being drawn through the PVe plate heat exchanger. Electric heaters are available in 208, 230, or 460 VAC. Refer to heater nameplate for voltage rating.

Preheaters: If an optional preheater is supplied with the unit, it is installed as a single stage on/off control. Preheaters are single-point wired at the factory. A thermocouple type

temperature sensor is mounted in the outdoor airstream after the preheater and that thermocouple will switch the preheater on. See Frost Control Application/Operation for typical set points. If the temperature falls below the set point and a pressure drop sensor is triggered, the preheater will turn on.

10Model PVe Heat Recovery Unit

Image 10
Contents General Safety Information Models PVe-20 PVe-35 PVe-45 PVe-55Unpacking Inspection and Maintenance during StorageReceiving HandlingInstallation Table of ContentsSupplemental Installation Operation and Maintenance Manuals Basic OperationLifting with a Crane Installation StagesLifting Lifting with a ForkliftService Clearances Roof Curb and Rail MountingRoof Curb Mounting Curb Dimensions and WeightsDuctwork Connections Access Panel Description and Location Rail Mounting / LayoutDimensional Data Drain TrapElectrical Information Typical Control Center Components Electric Heater Application/OperationEconomizer Application/Operation Optional AccessoriesFrost Control Application/Operation Timed Exhaust frost controlFactory Set Points Variable Frequency Drives for Energy Recovery BlowersDrive Operation Modulating Control for FAN Speed Typical Wiring Diagram CO2 Sensor Service OutletDirty Filter Sensor Vapor Tight LightsDay Timer or On/Off Switch Remote Control Panel and Wiring SchematicsIndicator Lights powered by the ER Unit Hand/Off/Auto SwitchSensors Mounted by Factory Drawing Terminal Strip LabelsStart-Up Pre Start-Up Checklist check as items areStart-Up Checklist General Start-Up InformationEconomizer Application / Operation section Optional Accessories ChecklistOptional Accessories section Variable Frequency Drives sectionUnit Start-Up Vibration Maintenance Overview Dampers Routine MaintenanceLubrication Fan BeltsDoor Seal Maintenance External Filter MaintenanceInternal Filter Maintenance Fan Wheel & FastenersBasic Unit Parts List Sequence of OperationOther Accessories Summer OperationDesign Airflow Troubleshooting AirflowTest and Balance Report Measured AirflowTroubleshooting Unit Symptom Possible Cause Corrective ActionTroubleshooting Unit Maintenance Log Maintenance Log Maintenance Log Warranty