Troubleshooting – Unit
Symptom | Possible Cause | Corrective Action | |
|
|
| |
One or both |
|
| |
blowers turn off |
| Adjust frost temperature sensor set point as | |
intermittently and | Exhaust Only frost control sensors are tripping. | ||
needed. | |||
back on after |
| ||
|
| ||
about 2 minutes |
|
| |
|
|
| |
| Fan wheel rubbing on inlet. | Adjust wheel and/or inlet cone. Tighten wheel | |
| hub or bearing collars on shaft. | ||
|
| ||
|
|
| |
| Bearings. | Replace defective bearing(s). Lubricate | |
| bearings. Tighten collars and fasteners. | ||
|
| ||
|
|
| |
| Wheel out of balance. | Replace or rebalance. | |
|
|
| |
| Loose wheel on shaft. | Tighten wheel setscrew. | |
|
|
| |
| Loose motor or blower sheave. | Tighten sheave setscrew. | |
|
|
| |
| Belts too loose. | Adjust belt tension after 24 hours of operation. | |
Excessive noise |
|
| |
Belts too tight. | Loosen to maintain a 3/8 inch deflection per | ||
or vibration | |||
foot of span between sheaves. | |||
|
| ||
|
|
| |
| Worn belt. | Replace. | |
|
|
| |
| Motor base or blower loose. | Tighten mounting bolts. | |
|
|
| |
| Buildup of material on wheel. | Clean wheel and housing. | |
|
|
| |
| Bearing and drive misaligned. | Realign. | |
|
|
| |
|
| Make sure ductwork is supported properly. | |
| Noise being transmitted by duct. | Make sure ductwork metal thickness is sized for | |
| proper stiffness. Check duct size at discharge to | ||
|
| ||
|
| ensure that air velocities are not too high. | |
|
|
|
Always have a completed Pre
28 Model PVe Heat Recovery Unit