Factory Set Points - continued
Resetting the V1000 drive to factory defaults To reset the V1000 drive back to Greenheck factory defaults go to parameter
MODULATING CONTROL FOR FAN SPEED
(0-10 VDC)
| Parameter | Setting | ||
| V1000 | J1000 | ||
|
| |||
|
|
|
| |
Access Level | 2 | 2 | ||
|
|
|
| |
VFD | 1 | 1 | ||
|
|
|
| |
Acceleration Time | 30 sec. | 30 sec. | ||
|
|
|
| |
Deceleration Time | 30 sec. | 30 sec. | ||
Carrier Frequency | 1 | 1 | ||
|
|
|
| |
Ref Lower Limit | 50% | 50% | ||
Motor Rated FLA | Motor | Motor | ||
FLA | FLA | |||
|
| |||
Terminal A1 Bias | 50% | 50% | ||
|
|
|
| |
Access Level | 0 | 0 |
CO2 SENSOR CONTROL FOR FAN SPEED
(1/2 speed WHEN C02 drops below 700 PPM) (FULL SPEED WHEN C02 RISES ABOVE 800 PPM)
| Parameter | Setting | ||
|
|
| ||
| V1000 | J1000 | ||
|
| |||
|
|
|
| |
Access Level | 2 | 2 | ||
Reference Source (Frequency) | 0 | 0 | ||
|
|
|
| |
VFD | 1 | 1 | ||
Acceleration Time | 30 sec. | 30 sec. | ||
|
|
|
| |
Deceleration Time | 30 sec. | 30 sec. | ||
Carrier Frequency | 1 | 1 | ||
|
|
|
| |
Frequency Reference 1 | 60 Hz | 30 Hz | ||
Frequency Reference 2 | 30 Hz | 60 Hz | ||
|
|
|
| |
Ref Lower Limit | 50% | 50% | ||
|
|
|
| |
Motor Rated FLA | Motor | Motor | ||
FLA | FLA | |||
|
| |||
A2 Not Used | F | NA | ||
Access Level | 0 | 0 | ||
|
|
|
|
multispeed control FOR FAN SPEED
(1/3 or 1/2 speed reduction)
| Parameter | Setting | ||
|
|
| ||
| V1000 | J1000 | ||
|
| |||
|
|
|
| |
Access Level | 2 | 2 | ||
|
|
|
| |
Reference Source (Frequency) | 0 | 0 | ||
|
|
|
| |
VFD | 1 | 1 | ||
|
|
|
| |
Acceleration Time | 30 sec. | 30 sec. | ||
|
|
|
| |
Deceleration Time | 30 sec. | 30 sec. | ||
Carrier Frequency | 1 | 1 | ||
|
|
|
| |
Frequency Reference 1 | 60 Hz | 60 Hz | ||
Frequency Reference 2 | 40 Hz | 40 Hz | ||
|
|
|
| |
Frequency Reference 3 | 30 Hz | 30 Hz | ||
Frequency Reference 4 | 60 Hz | 60 Hz | ||
|
|
|
| |
Ref Lower Limit | 50% | 50% | ||
Motor Rated FLA | Motor | Motor | ||
FLA | FLA | |||
|
| |||
Multfunction Input Sel 4 | 3 | 3 | ||
(Terminal S4) | ||||
|
|
| ||
|
|
|
| |
Multifunction Input Sel 5 | 4 | 4 | ||
(Terminal S5) | ||||
|
|
| ||
|
|
|
| |
Multifunction Input Sel 6 | 5 | NA | ||
(Terminal S6) | ||||
|
|
| ||
A2 Not Used | F | NA | ||
|
|
|
| |
Access Level | 0 | 0 | ||
|
|
|
|
Model PVe Heat Recovery Unit 13