Greenheck Fan PVE-55, PVE-35, PVE-20 Fan Wheel & Fasteners, Bearings, External Filter Maintenance

Page 24

Fan Wheel & Fasteners

Wheels require very little attention when moving clean air. Occasionally oil and dust may accumulate on the wheel causing imbalance. When this occurs the wheel and housing should be cleaned to assure smooth and safe operation. Inspect fan impeller and housing for fatigue, corrosion or wear.

Routinely check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and accessories for tightness. A proper maintenance program will help preserve the performance and reliability designed into the fan.

Bearings

Most bearings are permanently lubricated and require no further lubrication under normal use. Normal use being considered -20ºF to 120ºF and in a relatively clean environment. Some bearings are relubricatable and will need to be regreased depending on fan use. Check your bearings for grease zerk fittings to find out what type of bearing you have. If your fan is not being operated under normal use, bearings should be checked monthly for lubrication.

External Filter Maintenance

Aluminum mesh, 2-inch deep filters are located in the supply weatherhood (if the weatherhood option was purchased). Filters should be checked and cleaned on a regular basis for best efficiency. The frequency of cleaning depends upon the cleanliness of the incoming air. These filters should be cleaned prior to start-up.

Clean filters by rinsing with a mild detergent in warm water.

Internal Filter Maintenance

The PVe units are always provided with 2-inch, pleated filters in the outdoor air and exhaust airstreams. These filters should be checked per a routine maintenance schedule and replaced as necessary to ensure proper airflow through the unit. See table for pleated filter size and quantity for each unit. Replacement filters shall be of same performance and quality as factory installed filters. Filter type must be pleated design with integral metal grid. Two acceptable filter replacements are Aerostar Series 400 or Farr 30/30®.

Filter Size and Quantities

Unit Size

Pleated Filter Size

Quantity

 

 

 

Supply and Exhaust

Supply

Exhaust

 

 

 

 

 

PVe-20

12 x 25 x 2

3

3

 

 

 

 

PVe-35

16 x 25 x 2

3

3

 

 

 

 

PVe-45

20 x 25 x 2

3

3

 

 

 

 

PVe-55

24 x 24 x 2

3

3

 

 

 

 

All dimensions in inches.

Outdoor Air Filters: Access to the outdoor air filters is through the door labeled as “Filter Access” on the outdoor air side of the unit.

Exhaust Air Filters: Access to the exhaust air filters is through the door labeled as “Filter Access” on the exhaust air side of the unit.

Refer to Access Door Descriptions section for additional information on filter locations.

Door Seal Maintenance

Slip-on type seal is installed on the door. Inspect at least annually to ensure that seal is still pliable and intact.

24Model PVe Heat Recovery Unit

Image 24
Contents General Safety Information Models PVe-20 PVe-35 PVe-45 PVe-55Inspection and Maintenance during Storage ReceivingUnpacking HandlingTable of Contents Supplemental Installation Operation and Maintenance ManualsInstallation Basic OperationInstallation Stages LiftingLifting with a Crane Lifting with a ForkliftService Clearances Roof Curb and Rail MountingCurb Dimensions and Weights Roof Curb MountingDuctwork Connections Access Panel Description and Location Rail Mounting / LayoutDimensional Data Drain TrapElectrical Information Typical Control Center Components Electric Heater Application/OperationOptional Accessories Frost Control Application/OperationEconomizer Application/Operation Timed Exhaust frost controlVariable Frequency Drives for Energy Recovery Blowers Factory Set PointsDrive Operation Modulating Control for FAN Speed Typical Wiring Diagram Service Outlet Dirty Filter SensorCO2 Sensor Vapor Tight LightsRemote Control Panel and Wiring Schematics Indicator Lights powered by the ER UnitDay Timer or On/Off Switch Hand/Off/Auto SwitchSensors Mounted by Factory Drawing Terminal Strip LabelsPre Start-Up Checklist check as items are Start-Up ChecklistStart-Up General Start-Up InformationOptional Accessories Checklist Optional Accessories sectionEconomizer Application / Operation section Variable Frequency Drives sectionUnit Start-Up Vibration Maintenance Overview Routine Maintenance LubricationDampers Fan BeltsExternal Filter Maintenance Internal Filter MaintenanceDoor Seal Maintenance Fan Wheel & FastenersParts List Sequence of Operation Other AccessoriesBasic Unit Summer OperationTroubleshooting Airflow Test and Balance ReportDesign Airflow Measured AirflowTroubleshooting Unit Symptom Possible Cause Corrective ActionTroubleshooting Unit Maintenance Log Maintenance Log Maintenance Log Warranty