TO CHECK WITH BUBBLES

Soap each connection and observe all sides of the connection with a bright light and a mirror. A leak will blow bubbles. Without careful examination and plenty of pressure this test is not reliable.

TO CHECK WITH AN ELECTRONIC DETECTOR

Use a detector designed for HFCs. Slowly trace the area with the probe. Refrigerant is heavier than air, therefore, trace below the fitting. Most units can be calibrated to home in, on a leak. (See detector instructions). We use and recommend electronic detection. TIF brand detectors can accurately detect leaks as low as 1/2-oz loss per year. This sensitivity exceeds S.A.E. leak specifications. Be sure to test the operation of the detector before and after you leak check the system

IF A LEAK IS DETECTED

Try tightening the Swagelok nut slightly. (See "Swagelok fittings"). If the leak is not stopped, it is possible that the fitting was incorrectly assembled. Discharge (reclaim) the refrigerant, and then disassemble the fitting for inspection. After reassembly, proceed with evacuation leak test.

SPECIAL NOTE

-Be aware that propellants and solvents in sprays and foams may upset electronic detectors.

-To confirm a leak detected with a detector use bubbles and be sure it is a leak and not some erroneous vapor that is upsetting the machine.

-Electronic detectors do not function below 40.F.

-A good leak detector is able to pick up leaks as low as 1/2 oz per year.

FINAL CHARGING

This procedure must follow "Evacuation Leak Test" and "Introducing Initial Charge".

1.With the refrigerant supply still attached to the suction service port from the previous procedure, open the cylinder valve (and the appropriate gauge wheel).

2.While closely observing the sight glass in the RFD, start the compressor by switching on the circuit breaker and then turning on the thermostat.

23

Image 23
Contents Operation & Installation Instructions Table of Contents View of the Future Controls BG 2000 OperationDefrosting ICE MakingHarvesting ICE Storage of ICE CubesRoutinely Check BG 2000 MaintenanceCleaning Routine Service and InspectionLAY-UP Winterizing HOW Refrigeration Works Page Tube Bending InstallationTube Handling Tube CuttingPage Step DrawingReconnecting PRE-SWAGED Fittings Mounting Service AccessCondensing Unit Location and Mounting Receiver Filter Drier RFD VisibilityInstalling the Thermostatic Expansion Valve Running the Tubing Pump InstallationFinal Assembly AC Line Circuit Thermostat WiringConnection Access ThermostatRefrigerant Wiring the PumpRefrigerant Handling and Safety General Safety this is IMPORTANT. Read thisAccess to the System Service Ports Procedures for Working with R-404a Venting the Gauge SET Disconnecting Gauges Gauges Evacuation Leak Test Commissioning Procedure Evacuation with a Vacuum PumpLeak Checking a Charged System About Pressures NEW System Charging Introducing Initial ChargeLeak Checking Special Note To Check with BubblesTo Check with AN Electronic Detector If a Leak is DetectedReading the Sight Glass General Information RFD Sight Glass DetailProper Charge Amount Discharging the System Reclaiming Checking the Refrigerant Charge Periodic InspectionHigh Pressure CUTOUT/MANUAL Reset Button TroubleshootingCharge Loss Indicates a Leak That Must be Corrected Call US with ANY Questions BG 2000 Specifications and Operating Characteristics Page Water Circuit Page Page Page Thermostat Calibration Instructions Holdover Plates Stainless Steel Evaporator Plates