Installation

Prior to installation, ensure that the local distribution conditions (nature of the gas and gas pressure) and the adjustment conditions are compatible. The adjustment conditions for this appliance are stated on the data badge which is fitted on the back panel.

This appliance is not designed to be connected to a combustion products evacuation device. It must be installed and connected in accordance with current installation regulations. particular attention should be given to the relevant requirements regarding ventilation.

MODEL NUMBERS KD6G25X, KDP60G

Category II2H3+ (GB)

These models are set to burn NATURAL GAS (G20) at 20 mbar but can be converted for use on BUTANE (G30) at 28-30mbar or PROPANE (G31) at 37mbar with the use of the LPG conversion kit that can be obtained free of charge, if you contact our Genuine Parts and Accessories department (see Key Contacts, back page).

GAS SAFETY (INSTALLATION & USE) REGULATIONS

It is the law that all gas appliances are installed by competent persons in accordance with the current edition of the above regulations. It is in your interest and that of safety to ensure compliance with the law.

In the UK, CORGI registered installers work to safe standards of practice. The cooker must also be installed in accordance with BS 6172.

Failure to install the cooker correctly could invalidate the warranty liability claims and could lead to prosecution.

LOCATION

The cooker may be located in a kitchen, kitchen/diner or a bed-sitting room, but not in a room containing a bath or shower. The cooker must not be installed in a bed-sitting room of less than 20m3.

When adjusted for use on Butane (G30) or Propane (G31), the cooker must not be installed in a room or internal space below ground level, e.g. in a basement.

PROVISION FOR VENTILATION

The room containing the cooker should have an air supply in accordance with BS 5440: Part 2.

The room must have an opening window or equivalent; some rooms may also require a permanent vent. If the room has a volume between 5 and 10m3, it will require an air vent of 50cm2 effective area unless it has a door which opens directly to outside. If the room has a volume of less than 5m3, it will require an air vent of 100cm2 effective area. If there are other fuel burning appliances in the same room, BS 5440: Part 2 should be consulted to determine air vent requirements.

24

Image 24
Contents Free Standing Gas Cooker Contents Introduction For your Safety Please read the precautions below before using your cookerNever 00.00 12.00 Clock and Minute Minder00.20 13.23 Hotplate To USE the HotplateSafety Requirements for Deep FAT Frying HOW to Deal with a FAT FireGrill Grill PAN and HandleTo USE the Grill Relighting the BurnerMain Oven To USE the Main OvenCold Start Cooking Roasting of Large PoultryStorage and RE-HEATING of Food ‘COOK CHILL’ DishesMain Oven Cooking Chart Meat and PoultryCAKES, Pastries and Biscuits Top Oven Guidance on Using the TOP Oven To USE the TOP OvenTop Oven Cooking Chart CAKES, Pastries and BiSCUITS Care and Cleaning Replacement of Oven Light BulbCooker Finish Cleaning Method Problem Check Something Wrong with your CookerWhen grill / oven used First time Oven cooks too fast Slight odour or smallAmount of smoke Or too slowInstallation GAS Safety Installation & USE RegulationsModel Numbers KD6G25X, KDP60G LocationTechnical Data G20 at 20mbar G30 at 28-30mbar G31 at 37mbarBurner Space for Fixing Cooker HoodsUnpacking the Cooker LevellingConversion for USE on Butane G30 or Propane G31 Connecting to GAS Supply Stability ChainElectrical Connection Connect to a 230-240V A.C. Supply onlyInstallation and Operational Checks Contact the Service Office UK 08709 066 If it Still Won’t WorkAfter Sales Service Repair Service and Information Help DeskGenuine Parts and Accessories Extended Warranties