Load Application

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. SeeTable 6.

„„When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

„„When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

„„When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA70USI2 60 hz Generator • operation and parts manual — rev. #0 (06/28/11) — page 25

Image 25
Contents Model dca70USI2 Proposition 65 warning Administrator Reporting Safety DefectsDCA70USI2 Generator Table of ContentsChoose from three easy options SaFeTY meSSageS Safety InformationGeneraTor SaFeTY General SaFeTYRestricted. If the air fl ow is EngIne SaFeTYIf operating in speed ranges above the maximum allowable ToWIng SaFeTY FUel SaFeTY„ never use fuel as a cleaning agent From fuel vapors or if fuel is spilled on a hot engineGrounding Safety EleCTrICal SaFeTYPower Cord/Cable Safety EnvIronmenTal SaFeTY BaTTerY SaFeTYIsuzu BJ-4JJ1XYGD-02 Tier SpecificationsDimensions DimensionsTypical Generator Grounding Application InstallationIndoor Installation Outdoor InstallationMounting Generator GroundingGeneral Information Item no Major ComponentsOFF Generator Control PanelPage Engine Operating Panel Engine Operating Panel Terminal legs O and Ground are considered bonded grounds Output Terminal FamiliarizationOutput Terminal Panel is provided with the following VAC Gfci Receptacles Removing the Plastic Face Plate Hard Wire Hookup PanelOver Current Relay Connecting LoadsThree Phase Load Single Phase LoadLoad Application Voltage Selector Switch Locking Button Voltage Selector SwitchGenerator Output Voltages Generator AmperageGenerator OUTPUTS/gauge reading How to Read the ac ammeter and ac voltage gaugesAC Voltmeter Gauge Reading AC Ammeter Gauge Reading3Ø-240/139 Uvwo Terminal Output Voltages Uvwo Terminal Output Voltages3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output VoltagesCircuit Breakers Inspection/SETUPLubrication Oil Fuel CheckOnly use #2 diesel fuel when refueling Refueling ProcedureAir Cleaner Fan Belt Tension Cleaning the RadiatorCoolant Antifreeze/Summer Coolant/ Water Operation in Freezing WeatherBattery Cable Installation BatteryWiring AlternatorBefore Starting Place the engine speed switch in the LOW down positionStarting Starting ManualEngine Speed Switch High Emergency Shutdown Procedure Normal Shutdown ProcedurePlace the Mpec Control Switch in the OFF/RESET position Automatic Shut-down SystemGeneral Inspection Air Cleaner MaintenanceAir Cleaner with Dust Indicator Fuel Addition Cleaning Inside the Fuel TankRemoving Water from the Fuel Tank Fuel Tank InspectionCheck Oil Level Radiator CleaningReplacing Oil Filter Flushing Out Radiator and Replacing CoolantTrailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Brakes Brake AdjustmentHydraulic Surge Brakes ActuatorTire Wear/Inflation Tires/Wheels/Lug NutsSuspension Never use an pneumatic air gun to tighten wheel lug nuts Lug Nut Torque RequirementsTrailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramEngine Controller Controller Wiring DiagramTroubleshooting Generator Method of Operation Troubleshooting Diagnostic lampExplanation of Code in Remarks Column To 3 units Suggested Spare PartsGenerator Assy 0601820083 B51100004020601822664 B3120100804Control box Assy 0330000180 M22130015120330000610 0330000045Control box Assy 5825500290 8970119490M2213500604 M2270100204Control box Assy 0601810141 06021250900601831395 M1224100104Engine and Radiator Assy 8980388560 M29232001348980188580 0605000451Engine and Radiator Assy 0605515149 0191500680M3326200204 001698020Output Terminal Assy M9220100304 M3230700003M9220100404 0039316000Battery Assy M9310500014 0602220199M9103000304 0602220920Muffler Assy 0017112030 M2330101103M2333001403 M2333200404Fuel Tank Assy 0605505070 M23630001020605501079 0605516090Enclosure #1 Assy M2363300603 M24130020020603306797 M2423001702Enclosure ASSY. #1 35A 0030014000 001011404035B 0040014000 35C 0041214000Enclosure 2 Assy M2493305103 M2443001202M2443301803 M2493305904Rubber Seals Assy REMArks Nameplate and Decals Assy M15000020 M1550000204M1550002203 M15000220Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help