Multiquip DCA70USI2 manual Battery Cable Installation, Alternator, Wiring

Page 33

inspection/SETUP

Battery

This unit is of negative ground DO NOT connect in reverse. Always maintain battery fluid level between the specified marks. Battery life will be shortened, if the fluid level are not properly maintained. Add only distilled water when replenishment is necessary.

DO NOT over fill. Check to see whether the battery cables are loose. Poor contact may result in poor starting or malfunctions. Always keep the terminals firmly tightened. Coating the terminals with an approved battery terminal treatment compound. Replace battery with only recommended type battery.

The battery is sufficiently charged if the specific gravity of the battery fluid is 1.28 (at 68° F). If the specific gravity should fall to 1.245 or lower, it indicates that the battery is dead and needs to be recharged or replaced.

Before charging the battery with an external electric source, be sure to disconnect the battery cables.

Battery Cable Installation

ALWAYS be sure the battery cables (Figure 35) are properly connected to the battery terminals as shown below. The red cable is connected to the positive terminal of the battery, and the black cable is connected to the negative terminal of the battery.

CAUTION

ALWAYS disconnect the negative terminal FIRST and reconnect negative terminal LAST.

Figure 35. Battery Connections

When connecting battery do the following:

1.NEVER connect the battery cables to the battery terminals when the MPEC Control Switch is in either the MANUAL position. ALWAYS make sure that the MPEC Control Switch is in the OFF/RESET position when connecting the battery.

2.Place a small amount of battery terminal treatment compound around both battery terminals. This will ensure a good connection and will help prevent corrosion around the battery terminals.

NOTICE

If the battery cable is connected incorrectly, electrical damage to the generator will occur. Pay close attention to the polarity of the battery when connecting the battery.

CAUTION

Inadequate battery connections may cause poor starting of the generator, and create other malfunctions.

Alternator

The polarity of the alternator is negative grounding type. When an inverted circuit connection takes place, the circuit will be in short circuit instantaneously resulting the alternator failure.

DO NOT put water directly on the alternator. Entry of water into the alternator can cause corrosion and damage the alternator.

Wiring

Inspect the entire generator for bad or worn electrical wiring or connections. If any wiring or connections are exposed (insulation missing) replace wiring immediately.

Piping and Hose Connection

Inspect all piping, oil hose, and fuel hose connections for wear and tightness. Tighten all hose clamps and check hoses for leaks.

If any hose (fuel or oil) lines are defective replace them immediately.

DCA70USI2 60 hz Generator • operation and parts manual — rev. #0 (06/28/11) — page 33

Image 33
Contents Model dca70USI2 Proposition 65 warning Administrator Reporting Safety DefectsDCA70USI2 Generator Table of ContentsChoose from three easy options SaFeTY meSSageS Safety InformationGeneraTor SaFeTY General SaFeTYEngIne SaFeTY Restricted. If the air fl ow isIf operating in speed ranges above the maximum allowable ToWIng SaFeTY FUel SaFeTY„ never use fuel as a cleaning agent From fuel vapors or if fuel is spilled on a hot engineEleCTrICal SaFeTY Grounding SafetyPower Cord/Cable Safety EnvIronmenTal SaFeTY BaTTerY SaFeTYIsuzu BJ-4JJ1XYGD-02 Tier SpecificationsDimensions DimensionsTypical Generator Grounding Application InstallationIndoor Installation Outdoor InstallationMounting Generator GroundingGeneral Information Item no Major ComponentsOFF Generator Control PanelPage Engine Operating Panel Engine Operating Panel Output Terminal Familiarization Terminal legs O and Ground are considered bonded groundsOutput Terminal Panel is provided with the following VAC Gfci Receptacles Removing the Plastic Face Plate Hard Wire Hookup PanelOver Current Relay Connecting LoadsSingle Phase Load Three Phase LoadLoad Application Voltage Selector Switch Locking Button Voltage Selector SwitchGenerator Output Voltages Generator AmperageGenerator OUTPUTS/gauge reading How to Read the ac ammeter and ac voltage gaugesAC Voltmeter Gauge Reading AC Ammeter Gauge ReadingUvwo Terminal Output Voltages 3Ø-240/139 Uvwo Terminal Output Voltages3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output VoltagesCircuit Breakers Inspection/SETUPLubrication Oil Fuel CheckOnly use #2 diesel fuel when refueling Refueling ProcedureAir Cleaner Fan Belt Tension Cleaning the RadiatorCoolant Antifreeze/Summer Coolant/ Water Operation in Freezing WeatherBattery Cable Installation BatteryWiring AlternatorBefore Starting Place the engine speed switch in the LOW down positionStarting Starting ManualEngine Speed Switch High Emergency Shutdown Procedure Normal Shutdown ProcedurePlace the Mpec Control Switch in the OFF/RESET position Automatic Shut-down SystemMaintenance General Inspection Air CleanerAir Cleaner with Dust Indicator Fuel Addition Cleaning Inside the Fuel TankRemoving Water from the Fuel Tank Fuel Tank InspectionCheck Oil Level Radiator CleaningReplacing Oil Filter Flushing Out Radiator and Replacing CoolantTrailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Brakes Brake AdjustmentHydraulic Surge Brakes ActuatorTires/Wheels/Lug Nuts Tire Wear/InflationSuspension Never use an pneumatic air gun to tighten wheel lug nuts Lug Nut Torque RequirementsTrailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramEngine Controller Controller Wiring DiagramTroubleshooting Generator Method of Operation Troubleshooting Diagnostic lampExplanation of Code in Remarks Column To 3 units Suggested Spare PartsGenerator Assy 0601820083 B51100004020601822664 B3120100804Control box Assy 0330000180 M22130015120330000610 0330000045Control box Assy 5825500290 8970119490M2213500604 M2270100204Control box Assy 0601810141 06021250900601831395 M1224100104Engine and Radiator Assy 8980388560 M29232001348980188580 0605000451Engine and Radiator Assy 0605515149 0191500680M3326200204 001698020Output Terminal Assy M9220100304 M3230700003M9220100404 0039316000Battery Assy M9310500014 0602220199M9103000304 0602220920Muffler Assy 0017112030 M2330101103M2333001403 M2333200404Fuel Tank Assy 0605505070 M23630001020605501079 0605516090Enclosure #1 Assy M2363300603 M24130020020603306797 M2423001702Enclosure ASSY. #1 35A 0030014000 001011404035B 0040014000 35C 0041214000Enclosure 2 Assy M2493305103 M2443001202M2443301803 M2493305904Rubber Seals Assy REMArks Nameplate and Decals Assy M15000020 M1550000204M1550002203 M15000220Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help