Multiquip DCA70USI2 Before Starting, Starting Manual, Engine’s exhaust contains harmful emissions

Page 34

GENERATOR START-UP PROCEDURE

Before Starting

CAUTION

The engine’s exhaust contains harmful emissions.

ALWAYS have adequate ventilation when operating. Direct exhaust away from nearby personnel.

WARNING

NEVER manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.

1.Place the main,G.F.C.I.,and aux. circuit breakers (Figure 36) in the OFF position prior to starting the engine.

Figure 36. Main, Aux. and GFCI

Circuit Breakers (OFF)

2.Make sure the voltage change-over board has been configured for the desired output voltage.

3.Connect the load to the receptacles or the output terminal lugs as shown inFigure 11. These load connection points can be found on the output terminal panel and the output terminal panel’s hard wire hookup panel.

4.Tighten terminal nuts securely to prevent load wires from slipping out.

5.Close all engine enclosure doors (Figure 37).

Starting

1.Place the voltage selector switch in the desired voltage position (Figure 38).

Figure 38. Voltage Selector Switch

Starting (Manual)

1.Place the engine speed switch (Figure 39) in the LOW (down) position.

Figure 39. Engine Speed Switch (Low)

2.Place the MPEC control switch in the MANUAL position to start the engine (Figure 40).

Figure 40. MPEC Control Switch

(Manual Position)

3.Depending on the temperature of the coolant (cold weather conditions), the pre-heat lamp (Figure 41) will light (ON) and remain on until the pre-heating cycle has been completed. After completion of the pre-heating cycle, the light will go OFF and the engine will start up automatically.

CORRECT

INCORRECT

 

Figure 37. Engine Enclosure Doors

Figure 41. Pre-Heat Lamp

4. Once the engine starts, let the engine run for 1-2 minutes. Listen for any abnormal noises. If any abnormalities exist, shut down the engine and correct

page 34 — DCA70USI2 60 hz Generator • operation and parts manual — rev. #0 (06/28/11)

Image 34
Contents Model dca70USI2 Proposition 65 warning Reporting Safety Defects AdministratorTable of Contents DCA70USI2 GeneratorChoose from three easy options Safety Information SaFeTY meSSageSGeneral SaFeTY GeneraTor SaFeTYRestricted. If the air fl ow is EngIne SaFeTYIf operating in speed ranges above the maximum allowable „ never use fuel as a cleaning agent FUel SaFeTYToWIng SaFeTY From fuel vapors or if fuel is spilled on a hot engineGrounding Safety EleCTrICal SaFeTYPower Cord/Cable Safety BaTTerY SaFeTY EnvIronmenTal SaFeTYSpecifications Isuzu BJ-4JJ1XYGD-02 TierDimensions DimensionsInstallation Typical Generator Grounding ApplicationMounting Outdoor InstallationIndoor Installation Generator GroundingGeneral Information Major Components Item noGenerator Control Panel OFFPage Engine Operating Panel Engine Operating Panel Terminal legs O and Ground are considered bonded grounds Output Terminal FamiliarizationOutput Terminal Panel is provided with the following Removing the Plastic Face Plate Hard Wire Hookup Panel VAC Gfci ReceptaclesConnecting Loads Over Current RelayThree Phase Load Single Phase LoadLoad Application Generator Output Voltages Voltage Selector SwitchVoltage Selector Switch Locking Button Generator AmperageAC Voltmeter Gauge Reading How to Read the ac ammeter and ac voltage gaugesGenerator OUTPUTS/gauge reading AC Ammeter Gauge Reading3Ø-240/139 Uvwo Terminal Output Voltages Uvwo Terminal Output Voltages3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output VoltagesLubrication Oil Inspection/SETUPCircuit Breakers Fuel CheckRefueling Procedure Only use #2 diesel fuel when refuelingCoolant Antifreeze/Summer Coolant/ Water Cleaning the RadiatorAir Cleaner Fan Belt Tension Operation in Freezing WeatherWiring BatteryBattery Cable Installation AlternatorStarting Place the engine speed switch in the LOW down positionBefore Starting Starting ManualEngine Speed Switch High Place the Mpec Control Switch in the OFF/RESET position Normal Shutdown ProcedureEmergency Shutdown Procedure Automatic Shut-down SystemGeneral Inspection Air Cleaner MaintenanceAir Cleaner with Dust Indicator Removing Water from the Fuel Tank Cleaning Inside the Fuel TankFuel Addition Fuel Tank InspectionReplacing Oil Filter Radiator CleaningCheck Oil Level Flushing Out Radiator and Replacing CoolantTrailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Hydraulic Surge Brakes Brake AdjustmentBrakes ActuatorTire Wear/Inflation Tires/Wheels/Lug NutsSuspension Lug Nut Torque Requirements Never use an pneumatic air gun to tighten wheel lug nutsTrailer Wiring Diagram Trailer/Towing Vehicle Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramController Wiring Diagram Engine ControllerTroubleshooting Generator Troubleshooting Diagnostic lamp Method of OperationExplanation of Code in Remarks Column Suggested Spare Parts To 3 unitsGenerator Assy 0601822664 B51100004020601820083 B3120100804Control box Assy 0330000610 M22130015120330000180 0330000045Control box Assy M2213500604 89701194905825500290 M2270100204Control box Assy 0601831395 06021250900601810141 M1224100104Engine and Radiator Assy 8980188580 M29232001348980388560 0605000451Engine and Radiator Assy M3326200204 01915006800605515149 001698020Output Terminal Assy M9220100404 M3230700003M9220100304 0039316000Battery Assy M9103000304 0602220199M9310500014 0602220920Muffler Assy M2333001403 M23301011030017112030 M2333200404Fuel Tank Assy 0605501079 M23630001020605505070 0605516090Enclosure #1 Assy 0603306797 M2413002002M2363300603 M2423001702Enclosure ASSY. #1 35B 0040014000 001011404035A 0030014000 35C 0041214000Enclosure 2 Assy M2443301803 M2443001202M2493305103 M2493305904Rubber Seals Assy REMArks Nameplate and Decals Assy M1550002203 M1550000204M15000020 M15000220Terms and Conditions of Sale Parts Freight PolicyPage HERE’S HOW to GET Help