Multiquip DCA25USI manual Generator Output Voltages, Voltage Selector Switch, Generator Amperage

Page 24

GENERATOR OUTPUTS

Generator Output Voltages

A wide range of voltages are available to supply voltage for many different applications.Voltages are selected by using the voltage selector switch (Figure 13). To obtain some of the voltages as listed in Table 7 (see below) will require a fine adjustment using the voltage regulator (VR) control knob located on the control panel.

Voltage Selector Switch

The voltage selector switch (Figure 13) is located above the output terminal panel’s Hard Wire Hook-up Panel. It has been provided for ease of voltage selection.

Generator Amperage

Table 8 shows the maximum amps the generator can provide. DO NOT exceed the maximum amps as listed..

Table 8. Generator Maximum Amps

Rated Voltage

Maximum Amps

 

 

1Ø 120 Volt

55.6 amps (4 wire)

60A x 2 (Zigzag)

 

1Ø 240 Volt

27.8 amps (4 wire)

60A (Zigzag)

 

3Ø 240 Volt

60 amps

 

 

3Ø 480 Volt

30 amps

 

 

Figure 13. Voltage Selector Switch

Voltage Selector Switch Locking Button

To lock the voltage selector switch, press and hold the red button located at the bottom of the switch. While holding the red button down, insert a pad lock into the hole next to the button to retain it in the inward locked position. When the lock is removed, the red button is spring loaded and will return to its normal outward unlocked position .

CAUTION

NEVER change the position of the voltage selector switch while the engine is running. ALWAYS place circuit breaker in the OFF position before selecting voltage.

Table 7. Voltages Available

UVWO Output

Voltage Selector Switch

Voltage Selector Switch

Terminal Lugs

3-Phase 240/139V Position

3-Phase 480/270V Position

 

 

 

 

 

 

 

Line-Line

208V

220V

240V

416V

440V

480V

 

 

 

 

 

 

 

Line-Neutral

120V

127V

139V

240V

254V

277V

 

 

 

 

 

 

 

Voltage Selector Switch Single-Phase 240/120V Position

 

 

 

 

 

 

 

 

Line-Neutral/

120V

N/A

N/A

240V

N/A

N/A

Line-Line

Line-Neutral

Line-Line

 

 

 

 

 

 

 

 

 

 

 

GFCI Receptacle Load Capability

The load capability of the GFCI receptacles is directly related to the voltage being supplied at either the output terminals or the two twist lock auxiliary receptacles.

Table 9 and Table 10 show what amount of current is available at the GFCI receptacles when the output terminals and twist lock receptacles are in use. Be careful that your load does not to exceed the available current capability at the receptacles.

Table 9. 1Ø GFCI Receptacle Load Capacity

KW in Use

Available Load

Twist Lock (C6369)

Current (Amps)

1Ø 240/120V

GFCI Duplex

5-20R 120V

 

14.4

0 amps/receptacle

13.2

5 amps/receptacle

12.0

10 amps/receptacle

 

 

10.8

15 amps/receptacle

 

 

9.6

20 amps/receptacle

 

 

Table 10. 3Ø Generator Maximum Amps

KVA in Use

Available Load

(UVWO Terminals)

Current (Amps)

3Ø 240/480V

GFCI Duplex

5-20R 120V

 

25

0 amps/receptacle

 

 

20.8

5 amps/receptacle

 

 

16.7

10 amps/receptacle

 

 

12.5

15 amps/receptacle

 

 

8.4

20 amps/receptacle

 

 

page 24 — DCA25Usi 60 hz Generator • operation and parts manual — rev. #3 (07/19/11)

Image 24
Contents Parts List NO. M1871400104 parts list no. m1871400114c Model dca25USIProposition 65 warning Reporting Safety Defects AdministratorTable of Contents DCA25USI 60 Hz GeneratorChoose from three easy options Safety Information SaFeTY messagesSaFeTY sYmBols General saFeTY GeneraTor saFeTYEngine saFeTY Restricted. If the air fl ow isIf operating in speed ranges above the maximum allowable FUel saFeTY ToWing saFeTY„ never use fuel as a cleaning agent From fuel vapors or if fuel is spilled on a hot engineEleCTriCal saFeTY Grounding safetyPower Cord/Cable safety DeathBaTTerY saFeTY EnvironmenTal saFeTYSpecifications ModelModel Isuzu AA-4LE2 Tier 2 Certified Dimensions DimensionsInstallation Typical Generator Grounding ApplicationOutdoor Installation Indoor InstallationMounting Generator GroundingGeneral Information Major Components Item noGenerator Control Panel Generator Control PanelEngine Operating Panel Output Terminal Familiarization Terminal legs O and Ground are considered bonded groundsOutput Terminal Panel is provided with the following Removing the Plastic Face Plate Hard Wire Hookup Panel VAC Gfci ReceptaclesConnecting Loads Over Current RelaySingle Phase Load Three Phase LoadLoad Application Type of LoadVoltage Selector Switch Voltage Selector Switch Locking ButtonGenerator Output Voltages Generator AmperageHow to Read the ac ammeter and ac voltage gauges Generator OUTPUTS/gauge readingAC Voltmeter Gauge Reading AC Ammeter Gauge ReadingUvwo Terminal Output Voltages 3Ø-240/139 Uvwo Terminal Output Voltages3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output VoltagesInspection/SETUP Circuit BreakersLubrication Oil Fuel CheckRefueling Procedure Only use #2 diesel fuel when refuelingCleaning the Radiator Air Cleaner Fan Belt TensionCoolant Antifreeze/Summer Coolant/ Water Operation in Freezing WeatherBattery Battery Cable InstallationWiring AlternatorBefore Starting StartingEngine’s exhaust contains harmful emissions Coolant Temperature Gauge Normal Shutdown Procedure Emergency Shutdown ProcedureNever stop the engine suddenly except in an emergency Maintenance General Inspection Air CleanerAir Cleaner with Dust Indicator Cleaning Inside the Fuel Tank Fuel AdditionRemoving Water from the Fuel Tank Fuel Tank InspectionRadiator Cleaning Check Oil LevelReplacing Oil Filter Flushing Out Radiator and Replacing CoolantTrailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Brake Adjustment BrakesHydraulic Surge Brakes ActuatorTires/Wheels/Lug Nuts Tire Wear/InflationSuspension Lug Nut Torque Requirements Never use an pneumatic air gun to tighten wheel lug nutsTrailer Wiring Diagram Trailer/Towing Vehicle Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramEngine Wiring Diagram Troubleshooting Generator Symptom Possible Problem SolutionPage Explanation of Code in Remarks Column Suggested Spare Parts Qty DescriptionGenerator Assy B1110200602 79610250040601822630 8001070003Control box Assy M1215000612 06018088200021005080 0601823240Control box Assy 0601808985 AC AMMETER, 0~50A/100A5A 0601801040 06018068590601801041 0601840121Engine and Radiator Assy B1925200254 897230-93908944567411 M1305200304Engine and Radiator Assy M9602000003 0150000018M1312600204 0199901600Output Terminal Assy M1230700003 M9220000004M9220000104 0039308000Battery Assy 0602220185 M9310500014M9103000304 0602220920Muffler Assy M1332000002 81000001 ~M133200012 M1335000103Fuel Tank Assy M1365000302 06055050700605501071 0605516090Enclosure Assy M1415000502 M1414000402M1495000104 M1415100202Enclosure Assy M1445300103 27A M149530050427B M1495300604 M1445400103Enclosure Assy 51A C9312500004 52A 0030006000M9112100504 0601850097Rubber Seals Assy REMArks Nameplate and Decals Assy M1512400002 M11240000AM1512400102 M11240010ATerms and Conditions of Sale Parts Freight PolicyPage HERE’S HOW to GET Help