Kohler 24RCL manual Cooling System, Checking and Filling Coolant, Exhaust System Inspection Points

Page 55

Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install carbon monoxide detectors on each level of the building. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturer’s instructions.

CAUTION

Hazardous noise.

Can cause hearing loss.

Never operate the generator set without a muffler or with a faulty exhaust system.

At the interval specified in the service schedule, inspect the exhaust system components (exhaust manifold, exhaust outlet, exhaust line, exhaust clamps, and muffler) for cracks, leaks, and corrosion.

Exhaust System Inspection Points

DCheck for corroded or broken metal parts and replace them as needed.

DCheck that the exhaust outlet is unobstructed.

DCheck the exhaust gas color. If the exhaust is blue or black, contact your local authorized Kohler distributor/ dealer.

DVisually inspect for exhaust leaks (blowby). Check for carbon or soot residue on exhaust components. Carbon and soot residue indicates an exhaust leak. Seal leaks as needed.

DCheck that all covers and doors are undamaged, in place, and locked.

DCheck for the installation and operation of carbon monoxide (CO) detectors on each level of any building near the generator set.

4.6 Cooling System

WARNING

Hot coolant and steam.

Can cause severe injury or death.

Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.

Allow the engine to cool. Release pressure from the cooling system before removing the pressure cap. To release pressure, cover the pressure cap with a thick cloth and then slowly turn the cap counterclockwise to the first stop. Remove the cap after pressure has been completely released and the engine has cooled. Check the coolant level at the tank if the generator set has a coolant recovery tank.

4.6.1Checking and Filling Coolant

Maintain the coolant level in the coolant overflow bottle between the Hot and Cold markings. See Section 1, Service Views, for the coolant overflow bottle location.

Note: Periodically check the coolant level by removing the radiator’s pressure cap. Do not rely solely on the level in the coolant overflow bottle.

Ethylene glycol-based long-life coolant is recommended. Use a coolant mixture of 50% long-life coolant and 50% clean, softened water to inhibit rust/corrosion and prevent freezing. Add fresh coolant until the level is just below the overflow tube opening.

A coolant solution of 50% ethylene glycol-based coolant provides freezing protection to --37°C (--34°F) and overheating protection to 149°C (300°F). A coolant solution with less than 50% ethylene glycol may not provide adequate freezing and overheating protection. A coolant solution with more than 50% ethylene glycol can cause engine or component damage. Do not mix long-life coolant and conventional coolants. Do not mix different types and/or colors of long life coolants.

TP-6905 6/14

Section 4 Scheduled Maintenance 55

Image 55
Contents TP-6905 6/14 RDC2Generator Set Identification Numbers Accessory Number Accessory DescriptionProduct Identification Information Controller IdentificationTable of Contents Troubleshooting Scheduled MaintenanceAppendix a Abbreviations Accidental starting Can cause severe injury or death Safety Precautions and InstructionsBattery Accidental StartingExhaust System Engine Backfire/Flash FireFuel System Airborne particles Can cause severe injury or blind- ness Hazardous NoiseHazardous noise Can cause hearing loss Hazardous voltage Will cause severe injury or deathHot coolant and steam Can cause severe injury or death Hot PartsNameplate IntroductionLiterature Type Part Number List of Related LiteratureService Assistance Service Assistance TP-6905 6/14 Cooling System Detail Service ViewsService Views TP-6905 6/14 Keep the generator set area clear. Maintain at least Prestart ChecklistGenerator Set Operation Operating AreaGenerator Set Operation Exercising the Generator SetExercise Automatic Operation with Model RDT or RSB Transfer SwitchesUnloaded Cycle Exercise with Complete System Diagnostics System DiagnosticsUnloaded Full-Speed Exercise Power Failure During ExerciseExerciser Reset Setting the Exerciser at Power-upProcedure to Change the Exercise Setting Changing the Exercise Setting2RDC2 Main Menu 3Procedure to Set the Exerciser Procedure to Reset the Controller after a Fault Shutdown FaultsATS Communication Errors Resetting the Controller after a Fault ShutdownATS Fault RDC2 Fault OnCuer Condition Check PlusECM Air filter 5Controller Fault Messages Event Log Model RXT Transfer Switch OperationProcedure to View Event History SettingNormal Source Fails Time DelaysATS Load Control Relay Time Delay ATS Control Sequence of OperationRDC2 Controller Operation Controls and IndicatorsLED Operation Controller Keypad LED IndicatorsButton Button FunctionActive Alert LCD DisplayProcedure to Change Settings Controller PowerBattery Charging Changing Settings6Changing Settings Changing Settings on the RDC2 ControllerMain Menu Controller MenusEngine Metering Menu Overview MenuVoltage Calibration Generator Metering MenuGenset Run Time Menu Generator Set Information MenuGenset System Menu Voltage Regulator VR Voltage AdjustSetting the Exerciser Adjusting the Display ContrastScreens on this page do not appear ATS Status MenuChanging ATS Configuration Settings ATS Configuration MenuDate and Time 02Dec2014 1234pm Time Format 12hr24hr Date and Time Menu17Networking Information Menu Networking Information MenusDhcp Networking Status SubmenuOnCue Plus Password Networking Configuration Submenu OnCue Plus Password20RBUS Information Submenu Rbus Information Submenu21Remote Devices Submenu Remote Devices SubmenuProgrammable Interface Module PIM Menus 23Load Control Status Menu Load Control MenusGeneral Maintenance Scheduled MaintenanceScheduled Maintenance TP-6905 6/14 Service Schedule Oil Additions Oil SpecificationsLubrication System Oil CheckCheck for leaks Reset the maintenance timer on the RDC2Replace the oil filter Stop the generator set. Check the oil level. AddAir Cleaner Service Procedure Air CleanerChecking and Filling Coolant Cooling SystemExhaust System Inspection Points Draining Cooling System Flushing and CleaningFlushing and Cleaning Procedure Cooling System InspectionModel Spark plug gap Ignition System511 Battery Storage Procedure USB Port TroubleshootingFault Messages IntroductionProblem Possible Cause Corrective Action Generator Set Troubleshooting2RDC2 Troubleshooting Chart Controller TroubleshootingTroubleshooting TP-6905 6/14 Ansi Appendix a AbbreviationsLCB Page By Kohler Co. All rights reserved

24RCL specifications

The Kohler 24RCL is a powerful, compact generator designed to provide reliable backup power for residential applications. Equipped with a robust 24 kW output, this generator is engineered for both efficiency and durability, making it an excellent choice for homeowners looking to safeguard their property against outages.

One of the standout features of the Kohler 24RCL is its quiet operation. With a noise level significantly lower than that of traditional generators, it allows homeowners to maintain their comfort without the disruptive sounds often associated with backup power systems. This is particularly important in residential neighborhoods where maintaining peace and quiet is essential.

The generator is powered by a liquid-cooled Kohler engine, which ensures consistent performance and longevity. Liquid-cooled engines are known for their ability to provide better thermal management, thereby extending the life of the engine while also improving efficiency. Moreover, the Kohler 24RCL utilizes a proven design that enables quick starts and reliable operation, even in the most challenging conditions.

Another key technology in the 24RCL is its integrated transfer switch, which automatically detects power outages and switches the home’s electrical supply to the generator. This seamless transition ensures that there is no disruption in power, making it an ideal solution for critical loads such as refrigerators, medical equipment, and security systems. The generator’s advanced control system allows for easy monitoring and maintenance, providing users with peace of mind whenever they rely on their backup power.

The Kohler 24RCL boasts a weather-resistant enclosure, designed to withstand the elements and provide protection against rain, snow, and harsh winds. This rugged construction also contributes to the longevity of the unit, ensuring that it can perform reliably year after year.

Sustainability is another driving factor in the design of the Kohler 24RCL. The generator features efficient fuel consumption, which not only helps to reduce operating costs but also minimizes the environmental impact. With many homeowners increasingly focused on eco-friendly solutions, the 24RCL fits seamlessly into a sustainable lifestyle.

Overall, the Kohler 24RCL is a powerful, efficient, and quiet backup generator that combines advanced technology with rugged reliability. Its features make it a standout choice for homeowners seeking a dependable power solution that prioritizes convenience, safety, and sustainability. Whether facing severe weather or unexpected outages, the Kohler 24RCL ensures that homes remain powered and protected.