Kohler 24RCL ATS Control Sequence of Operation, Time Delays, ATS Load Control Relay Time Delay

Page 28

2.7.2ATS Control Sequence of Operation

See Figure 2-8 for time delay settings.

Normal Source Fails:

1.The load control contact opens.

2.The engine start time delay times out.

3.The generator set is signaled to start.

4.The generator starts and the emergency source becomes available.

5.The normal-to-emergency time delay times out.

6.The transfer switch transfers to the emergency source.

7.The load control contact time delay times out.

8.The load control contact closes.

Normal Source Returns:

1.The emergency-to-normal time delay times out.

2.The contactor transfers to the normal source.

3.The engine cooldown time delay times out.

4.The generator is signaled to stop.

2.7.3Time Delays

Time delays are factory-set to the values shown in Figure 2-8. An authorized distributor/dealer can adjust time delays using a personal computer and Kohlerr SiteTecht software.

Time delays described in this section operate only when the controller is connected to a Kohlerr Model RXT transfer switch.

The engine start and load transfer time delays prevent engine start and load transfer caused by brief variations in the utility power source.

2.7.4ATS Load Control Relay Time Delay

The load control time delay allows delayed starting of large motor loads (such as air conditioners), preventing simultaneous starting of large motors after transfer to the generator set. The load control time delay is fixed at 5 minutes. It is not adjustable.

The load must be connected to the load control output on the interface board of the Model RXT transfer switch. See the transfer switch operation and installation manual for connection instructions.

Time Delay

Setting

Description

 

 

 

Engine Start

3 seconds

Time delay after utility source is lost until the engine start cycle begins.

 

 

Guards against starting the generator set because of a brief change in

 

 

the utility source.

 

 

 

Transfer, Normal to Emergency

3 seconds

Time delay after emergency source becomes available until transfer to

 

 

emergency source.

 

 

 

Transfer, Emergency to Normal

2 minutes

Time delay after the utility source returns until transfer back to normal.

 

 

Ensures that the the utility source is stable before transferring from the

 

 

emergency source.

 

 

 

Load Control

5 minutes

See Section 2.7.4. Allows delayed connection of selected loads to the

 

 

generator set to prevent simultaneous starting of large motors after

 

 

transfer to the emergency source. Recommended for delayed starting

 

 

of air conditioners.

Figure 2-8 Time Delays

 

 

28 Section 2 Generator Set Operation

TP-6905 6/14

Image 28
Contents RDC2 TP-6905 6/14Accessory Number Accessory Description Product Identification InformationController Identification Generator Set Identification NumbersTable of Contents Troubleshooting Scheduled MaintenanceAppendix a Abbreviations Safety Precautions and Instructions BatteryAccidental Starting Accidental starting Can cause severe injury or deathExhaust System Engine Backfire/Flash FireFuel System Hazardous Noise Hazardous noise Can cause hearing lossHazardous voltage Will cause severe injury or death Airborne particles Can cause severe injury or blind- nessHot Parts Hot coolant and steam Can cause severe injury or deathIntroduction NameplateList of Related Literature Literature Type Part NumberService Assistance Service Assistance TP-6905 6/14 Service Views Cooling System DetailService Views TP-6905 6/14 Prestart Checklist Generator Set OperationOperating Area Keep the generator set area clear. Maintain at leastExercising the Generator Set Generator Set OperationAutomatic Operation with Model RDT or RSB Transfer Switches Unloaded Cycle Exercise with Complete System DiagnosticsSystem Diagnostics ExercisePower Failure During Exercise Exerciser ResetSetting the Exerciser at Power-up Unloaded Full-Speed ExerciseChanging the Exercise Setting Procedure to Change the Exercise Setting2RDC2 Main Menu 3Procedure to Set the Exerciser Faults ATS Communication ErrorsResetting the Controller after a Fault Shutdown Procedure to Reset the Controller after a Fault ShutdownFault RDC2 Fault OnCuer Condition Check Plus ATSECM Air filter 5Controller Fault Messages Model RXT Transfer Switch Operation Procedure to View Event HistorySetting Event LogTime Delays ATS Load Control Relay Time DelayATS Control Sequence of Operation Normal Source FailsControls and Indicators RDC2 Controller OperationController Keypad LED Indicators ButtonButton Function LED OperationLCD Display Active AlertController Power Battery ChargingChanging Settings Procedure to Change SettingsChanging Settings on the RDC2 Controller 6Changing SettingsController Menus Main MenuOverview Menu Engine Metering MenuGenerator Metering Menu Voltage CalibrationGenerator Set Information Menu Genset Run Time MenuVoltage Regulator VR Voltage Adjust Setting the ExerciserAdjusting the Display Contrast Genset System MenuATS Status Menu Screens on this page do not appearATS Configuration Menu Changing ATS Configuration SettingsDate and Time Menu Date and Time 02Dec2014 1234pm Time Format 12hr24hrNetworking Information Menus 17Networking Information MenuNetworking Status Submenu DhcpNetworking Configuration Submenu OnCue Plus Password OnCue Plus PasswordRbus Information Submenu 20RBUS Information SubmenuRemote Devices Submenu 21Remote Devices SubmenuProgrammable Interface Module PIM Menus Load Control Menus 23Load Control Status MenuScheduled Maintenance General MaintenanceScheduled Maintenance TP-6905 6/14 Service Schedule Oil Specifications Lubrication SystemOil Check Oil AdditionsReset the maintenance timer on the RDC2 Replace the oil filterStop the generator set. Check the oil level. Add Check for leaksAir Cleaner Air Cleaner Service ProcedureChecking and Filling Coolant Cooling SystemExhaust System Inspection Points Flushing and Cleaning Flushing and Cleaning ProcedureCooling System Inspection Draining Cooling SystemIgnition System Model Spark plug gap511 Battery Storage Procedure Troubleshooting Fault MessagesIntroduction USB PortGenerator Set Troubleshooting Problem Possible Cause Corrective ActionController Troubleshooting 2RDC2 Troubleshooting ChartTroubleshooting TP-6905 6/14 Appendix a Abbreviations AnsiLCB Page By Kohler Co. All rights reserved

24RCL specifications

The Kohler 24RCL is a powerful, compact generator designed to provide reliable backup power for residential applications. Equipped with a robust 24 kW output, this generator is engineered for both efficiency and durability, making it an excellent choice for homeowners looking to safeguard their property against outages.

One of the standout features of the Kohler 24RCL is its quiet operation. With a noise level significantly lower than that of traditional generators, it allows homeowners to maintain their comfort without the disruptive sounds often associated with backup power systems. This is particularly important in residential neighborhoods where maintaining peace and quiet is essential.

The generator is powered by a liquid-cooled Kohler engine, which ensures consistent performance and longevity. Liquid-cooled engines are known for their ability to provide better thermal management, thereby extending the life of the engine while also improving efficiency. Moreover, the Kohler 24RCL utilizes a proven design that enables quick starts and reliable operation, even in the most challenging conditions.

Another key technology in the 24RCL is its integrated transfer switch, which automatically detects power outages and switches the home’s electrical supply to the generator. This seamless transition ensures that there is no disruption in power, making it an ideal solution for critical loads such as refrigerators, medical equipment, and security systems. The generator’s advanced control system allows for easy monitoring and maintenance, providing users with peace of mind whenever they rely on their backup power.

The Kohler 24RCL boasts a weather-resistant enclosure, designed to withstand the elements and provide protection against rain, snow, and harsh winds. This rugged construction also contributes to the longevity of the unit, ensuring that it can perform reliably year after year.

Sustainability is another driving factor in the design of the Kohler 24RCL. The generator features efficient fuel consumption, which not only helps to reduce operating costs but also minimizes the environmental impact. With many homeowners increasingly focused on eco-friendly solutions, the 24RCL fits seamlessly into a sustainable lifestyle.

Overall, the Kohler 24RCL is a powerful, efficient, and quiet backup generator that combines advanced technology with rugged reliability. Its features make it a standout choice for homeowners seeking a dependable power solution that prioritizes convenience, safety, and sustainability. Whether facing severe weather or unexpected outages, the Kohler 24RCL ensures that homes remain powered and protected.